Tii OF100PFNOPNST1 User Manual

P/N 92237501 • Rev B ECN 12-072 • 3/2/2012
Warranty: If this unit fails during the warranty period, contact tii customer service to authorize return. Unit may be returned prepaid.
25 Pair unit shown
Models OF025PFNOPNST1 OF050PFNOPNST1 OF100PFNOPNST1
FIXED OUTDOOR BET
Installation Note
NOTE:
SPLICE CHAMBER
PROTECTOR BLOCK
GROUND BAR
MS^2 TOOL HOLDER BRACKET
TOOL-LESS IDC TERMINALS
To ensure the proper fusing integrity to maintain the UL Listing, only use No 22 or 24 AWG incoming wire.
4. BETs are surface mount unit to be mounted on the wall. Multiple units can be mounted one above the other and wired from the same OSP cable.
Feature
Description
1. The TII Fixed Outdoor BET panels are compact terminals for applications in commercial and residential buildings. The BETs are available in pair counts of 25, 50 and 100, are equipped with protection fields that accept 5 pin style protector modules and utilize tool-less IDC outputs. IDC outputs are used to terminate 26-22 AWG solid wires. MS² connector bracket is provided to ease connector termination.
2. BETs are supplied with 6 AWG ground strap and ground block.
3. BETs are fabricated from powder coated steel.
Figure 1
MOUNTING HOLES
CABLE GROMMET
OSP CABLE
6 AWG GROUND WIRE
GROUND BAR
Installation
Use and location selection
Fixed outdoor BET is intended for outdoor use and should be located:
1. Mount on the suitable vertical surface that is firm and screw holding power is adequate.
2. Where easily accessible and where maintenance will not block a passageway.
3. Where there is no risk of severe moisture.
4. With adequate clearance from electric light fixtures, equipment and power circuits and where there is no risk of damage by moving machinery, doors etc.
5. Near a suitable earth ground.
Protector Modules
BET will accept five pin protector modules. Protector modules must be listed for primary protection per UL497 in order to maintain the UL listing of the BET.
The BET and Protector Modules shall be installed and connected to earth ground IAW the instructions contained herein and the applicable requirements of the National Electric Code, ANSI/NFPA-70, Article 800 and any applicable local codes.
CAUTION Risk of Electrical Shock - The BET is not to be
used without associated protector modules.
Installation
3. Insert the OSP cable through the cable grommet to fit snuggly around the cable. Terminate a connection with the wires in splice chamber using MS² or equivalent. To ease termination of the MS² connector. BET panels are equipped with MS² connector brackets.
Figure 3
4. Connect 6 AWG ground to the shielding of the OSP cable using a (user supplied) clamp.
1. Align unit in desired location on a vertical mounting surface.
2. Affix unit securely with four # 10 wood screws supplied with the BET.
Figure 4
5. Attached 6 AWG solid copper ground wire to the ground bar.
6. Install the tip and ring wires of the customer premises to the appropriate IDC rockers.
7. Plug the 5 pin protector modules into the corresponding protection fields.
BET units can be vertically stacked. Maximum of 5 100
Figure 2
pair cables cab be passed through the BET.
Loading...