P/N 92229901 • Rev C• 3/3/2008
Warranty: If this unit fails during the warranty period, contact tii customer service to authorize return. Unit may be returned prepaid.
141 Rodeo Drive
Edgewood, NY 11717
Toll Free 888.444.4720
www.tiinettech.com
Model 122/122-1/122H/122H-1
Station Protector Modules
Installation Note
Description
1. The tii 122/122-1/122H/122H-1 Series Station
Protectors modules may be installed in a wide
variety of station protector and network
interface housings. They may also be used as
indoor station protectors when attached to a tii
B1 Mounting Adapter.
2. The modules are self clearing and generally
require no maintenance. Because the wiring
terminals are an integral part of the protector
module, the entire self-contained unit must be
removed and replaced when it reaches its
“end of life” condition
√
NOTE
National Electric Code Requirement. The
protector shall be installed per National
Electric Code ANSI/NFPA 70, Article
800, Section C, and shall meet all
applicable local safety codes.
These modules shall be installed in NID
enclosures evaluated to the requirement
of UL497
Installation
1. Loosen the nut on the appropriate ground stud.
2.
Slide the surge protector ground clip of under the nut
and washer. Tighten down the nut (Figure 1).
3. Ground the module using a No. 6 AWG solid
copper insulated ground wire. Connect one end of
the ground conductor to the appropriate ground
stud and the other end to an appropriate ground
source (Figure 1).
Typical Installation
Station Protector Housing
(Cover Removed)
Ground
Stud
Tip
Conductor
Telco Side Cable
Ground
Conducto
Figure 1
Customer Side Cable
Line 1
Protector
Line 2
Protector
Ring
Conductor
1. Terminate the Telco Side cable (i.e., aerial or
buried drop) in between the bottom set of
washers and bottom nut of the appropriate
stud (one conductor to Tip and one to Ring).
Tighten down the nut (Figure 2).
2. Terminate the Customer Side cable under the
top set of washers and the top nut of the
appropriate stud (one conductor to Tip and
one to Ring). Tighten down the nut (Figure 2).
TelcoSideCable
TerminateBetween
Washers
GroundClip
CustomerSideCable
TerminateBetween
Washers
Figure 2
3. Loop back unused station wire conductors and
coil around the station wire jacket or store in
such a manner as to prevent them from
coming in contact with protector terminals or
bare wires.
4. When more than one cable is placed under a
nut, use washers between the wires.
5. Use caution when terminating small gauge
Customer Side cable on the protector module
terminals, as the wires may catch in the
threads of the terminal and be cut or broken
when nuts are tightened.
6. Check all nuts to make sure they are tight.
Note (Caution/Important)
!
1. When clearing trouble on a line that contains
gas tube protector modules, and when the test
board has indicated that there may still be a
power contact, inspect the non-cable portion
of the line from the ground for any power
contacts or evidence of damage from power
contacts.
2. Special care should be taken in making the
inspections where the line runs through trees
or where visibility is limited.
3. If a power contact is found, notify the proper
authority so it may be corrected.
4. Do not work on the line until the power contact
has been cleared.
5. If no contact is found but the test board still
have indications of a power contact, wear
insulating gloves while working with the test
board to clear the line.