LETHAL VOLTAGE MAY BE PRESENT IN ANY PV INSTALLATION
SAVE THESE INSTRUCTIONS
•This manual contains important instructions for installation and maintenance of the Tigo
product models TS4-L, TS4-O, TS4-S, TS4-M, TS4-A-O, TS4-A-S, TS4-A-M, TS4-A-O-Duo, TS4-A-SDuo, TS4-A-M-Duo, TS4-R-O, TS4-R-S, TS4-R-M, TS4-R-O-Duo, TS4-R-S-Duo, TS4-R-M-Duo, Tigo
Access Point (TAP), Cloud Connect Advanced (CCA), and related Tigo software and
mobile applications.
•Risk of electric shock, do not remove cover, disassemble, or repair, no user serviceable
parts inside. Refer servicing to qualied service personnel.
•Before installing or using the Tigo System, please read all instructions and warning
markings on the Tigo products, appropriate sections of your inverter manual,
photovoltaic (PV) module installation manual, and other available safety guides.
•Failure to adhere to these instructions may result in injury or death, damage to the
system, or voiding the factory warranty.
•To reduce risk of re and shock hazard, install this device with strict adherence to
National Electric Code (NEC) ANSI/NFPA 70 and/or local electrical codes. When the
photovoltaic array is exposed to light, it supplies a DC voltage to the Tigo TS4 units. The
TS4 units start in the “ON” state and their output voltage may be as high as the PV
module open circuit voltage (VOC) when connected to the module. The installer should
use the same caution when handling electrical cables from a PV module with or without
the TS4 units attached.
•Installation must be performed by trained professionals only. Tigo does not assume
liability for loss or damage resulting from improper handling, installation, or misuse of
products.
•Remove all metallic jewelry prior to installing the Tigo TS4 units to reduce the risk of
contacting live circuitry. Do not attempt to install in inclement weather.
•Do not operate the Tigo TS4 units if they have been physically damaged. Check existing
cables and connectors, ensuring they are in good condition and appropriate in rating.
Do not operate Tigo TS4 units with damaged or substandard wiring or connectors. Tigo
TS4 units must be mounted on the high end of the PV module backsheet or racking
system, and in any case above ground.
•Do not connect or disconnect under load. Turning off the Inverter and/or the Tigo
products may not reduce this risk. Internal capacitors within the inverter can remain
charged for several minutes after disconnecting all power sources. Verify capacitors
have discharged by measuring voltage across inverter terminals prior to disconnecting
wiring if service is required. Wait 30 seconds after rapid shutdown activation before
disconnecting DC cables or turning off DC disconnect.
•Always assume TS4 units are in “ON” state, or may turn on when restarting.
•The CCA must be on the same AC branch circuit as the inverter to meet rapid shutdown
requirements.
10/02/2019
2
Page 3
TABLE OF CONTENTS
Tigo System Overview4
TS4 Flex MLPE Versions5
TS4 Flex MLPE Functions6
Communication Accessories7
System Overview: TS4-B8
System Overview: TS4-R9
System Overview: TS4-A10
System Overview: TS4-A-Duo11
MLPE Installation Notes12
TS4-B Installation13
TS4-R Installation14
TS4-A Installation15
TS4-A-Duo Installation16
Congure Module Layout28
Connect CCA To Smartphone29
Congure Network Settings –
Connect CCA To Internet30
Commission The TS4 Units –
Run Discovery30
String Design With TS431
Appendix
Product Specications, Rapid Shutdown,
String Sizing with TS4-L32
Technical Specications –
Smart Module with TS4-B33
Wireless communication device for
monitoring and safety features
Cloud Connect
Advanced (CCA)
Data logger and rapid shutdown
control
4
Page 5
TS4 FLEX MLPE VERSIONS
4-123A
4-123A
TS4-B
TS4-O
4- 123A
• Module electronics are contained in the
junction box, installed at the PV module
factory
• Connected in series like regular modules
• No additional wiring connections to make
TS4-A, TS4-R
TS4-A-O
TS4-R-O
4- 123A
•Bracket clips to module frame without tools
•TS4-R outputs are connected in series
to form a string
•No additional grounding required
TS4-A-Duo, TS4-R-Duo
TS4-A-O-Duo
TS4-R-O-Duo
4- 123A
•Bracket clips to module frame without tools
•Designed to fit two 60 cell modules in series
to one TS4-A-Duo or TS4-R-Duo
•TS4-A-Duo or TS4-R-Duo outputs are
connected in series to form a string
•No additional grounding required
5
Page 6
TS4 FLEX MLPE FUNCTIONS
The TS4 Flex MLPE platform is incremental in functionality.
Select the TS4 version with features that best address the
needs of your project.
MONITORING
TS4-M
DiodesMonitoring
•Reduced O&M costs
•PV-2.0 data synchronization
•Module bar code tracking
SAFETY
TS4-S
•CRM integration
•Warranty tracking
•Fleet management
•NEC 2014 & 2017 690.12 rapid shutdown
compliant
•Module-level deactivation
OPTIMIZATION
TS4-O
•Shade and mismatch tolerance
•Enhanced energy yield
•Greater design exibility
LONG STRINGS
TS4-L
•String length increased by up to 30%
•Fewer BOS components
•Faster installation
DiodesMonitoringSafety
•Automatic or manual shutdown
•Plus all the benets of Monitoring
Diodes
•Maximized roof usage
•Plus all the benets of Safety and Monitoring
•Inverter optimization
•Lower wire-losses
•Plus all the benets of Optimization, Safety,
and Monitoring
MonitoringSafety
SafetyDiodes
Optimization
OptimizationMonitoring
Long Strings
For the TS4-F (Fire Safety) manual, click here
6
Page 7
COMMUNICATION ACCESSORIES
Tigo Access Point (TAP)
access point
Mesh configuration:
•300 TS4 units per TAP
•900 TS4 units per CCA
•7 TAPs per CCA
RS485
terminal
block
Cable
gland
Quick
connect
PWRPWRDATADATA
BBAA
120Ω
resistor
Wireless range:
•33ft (10m) max between TAP and
closest TS4 unit
•115ft (35m) max between TAP and
farthest TS4 unit using mesh
Legacy configuration:
•Same as Gateway, see appendix for more details
Cloud Connect Advanced (CCA)
•CCA is required for monitoring
and rapid shutdown
•CCA is optional for optimization
and long strings
•Install near inverter with access
to AC power and internet
•Ethernet and Wi-Fi
are built-in
RS485 port for
3rdparty devices
AUX RS485-1RS485-2GATEWAYPOWER
Connector for
external switch
(optional)
B AB AB A
DC power
input
TAP/GTWY
7
Page 8
SYSTEM OVERVIEW: TS4-B
1243
accesspoint
AUX RS485-1 RS485-2GATEWAY POWER
B A B A BA
1. Modules with integrated TS4
2. Tigo Access Point (TAP)
3. Cloud Connect Advanced (CCA)
4. Inverter
8
Page 9
SYSTEM OVERVIEW: TS4-R
1243
TS4-R-O
accesspoint
4-123A
AUX RS485-1 RS485-2GATEWAY POWER
B A B A BA
1. Tigo Access Point (TAP)
2. TS4-R installed on standard module
3. Cloud Connect Advanced (CCA)
4. Inverter
Note: connect modules to TS4-R inputs before connecting outputs
•TS4-R mounting is recommended on the upper right as shown, but can
be placed on upper left if needed (due to racking constraints, etc.)
•TS4-R cable glands must not be facing up
•Allow clearance between PV module and mounting surface for air
circulation around TS4-R
•Do not drill additional mounting holes in the frame or metal bracket
9
Page 10
SYSTEM OVERVIEW: TS4-A
1243
TigoRapidShutdown
NEC690.12-2017andC22.1-2015Rule64.218
DONOTDISCONNECT
TS4-A-O
UNDERLOAD
accesspoint
4-123A
AUX RS485-1 RS485-2GATEWAY POWER
B A B A BA
1. Tigo Access Point (TAP)
2. TS4-A installed on standard module
3. Cloud Connect Advanced (CCA)
4. Inverter
Note: connect modules to TS4-A inputs before connecting outputs
•TS4-A mounting is recommended on the upper right as shown, but can
be placed on upper left if needed (due to racking constraints, etc.)
•TS4-A cable glands must not be facing up
•Allow clearance between PV module and mounting surface for air
circulation around TS4-A
•Do not drill additional mounting holes in the frame or metal bracket
10
Page 11
SYSTEM OVERVIEW: TS4-A-DUO
1243
AUX RS485-1 RS485-2GATEWAY POWER
TigoRapidShutdown
NEC690.12-2017andC22.1-2015Rule64.218
DONOTDISCONNECT
TS4-A-O
UNDERLOAD
accesspoint
4-123A
B A B A BA
1. Tigo Access Point (TAP)
2. TS4-A-O-Duo installed on pair of standard modules
(modules are connected in series to TS4 inputs)
3. Cloud Connect Advanced (CCA)
4. Inverter
Note: connect modules to TS4-A inputs before connecting outputs
•TS4-A mounting is recommended on the upper right as shown, but can
be placed on upper left if needed (due to racking constraints, etc.)
•TS4-A cable glands must not be facing up
•Allow clearance between PV module and mounting surface for air
circulation around TS4-A
•Do not drill additional mounting holes in the frame or metal bracket
11
Page 12
MLPE INSTALLATION NOTES
• Note: The following TS4 products are shipped in the ON
position:
• TS4-M, TS4-S, TS4-O, TS4-L
• TS4-A-O, TS4-A-O-Duo
• TS4-R-M, TS4-R-S, TS4-R-O
• TS4-R-M-Duo, TS4-R-S-Duo, TS4-R-O-Duo
• Upon exposure of the PV module to sunlight high voltage is
present. Handle with the appropriate precautionary
measures.
• Optimization and Long Strings features don’t require
communication accessories in order to work.
• To enable Monitoring and Safety features:
• Collect the TS4 removable barcode label from the PV module
junction box.
TS4 - O
4-1234T
• Install and commission communication accessories.
4-1234T
With add-on units, failing to follow the sequence of installation steps
may result in TS4 damage not covered under warranty.
12
Page 13
TS4-B INSTALLATION
Smart modules with an integrated TS4 junction box are installed and
connected in series just like standard PV modules.
No additional grounding is required for the TS4 units.
1
TS4-L
4-123A
TS4-L
4-123A
2
TS4-L
4-123A
TS4-L
4-123A
13
Page 14
TS4-R INSTALLATION
Standard modules can be equipped with TS4-R add-on units as
shown below.
Always connect modules to TS4-R inputs before connecting outputs.
Each TS4-R must have a PV module connected to its inputs before
connecting the outputs of TS4-R units in series.
To disconnect TS4-R from a module, disconnect the TS4-R outputs
from the string before disconnecting the TS4-R inputs from the
module junction box.
1
3
TS4-R-O
4- 123A
TS4-R-O
2
TS4-R-O
4- 123A
4-123A
TS4-R-O
4-123A
14
Page 15
TS4-A INSTALLATION
Standard modules can be equipped with TS4-A add-on units as
shown below.
Always connect modules to TS4-A inputs before connecting outputs.
Each TS4-A must have a PV module connected to its inputs before
connecting the outputs of TS4-A units in series.
To disconnect TS4-A from a module, disconnect the TS4-A outputs
from the string before disconnecting the TS4-A inputs from the
module junction box.
12
3
TS4-A-O
4- 123A
TigoRapid Shutdown
NEC690.12-2017andC22.1-2015Rule64.218
DONOTDISCONNECT
UNDERLOAD
TS4-A-O
4- 123A
TigoRapidShutdown
NEC690.12-2017andC22.1-2015Rule64.218
TigoRapid Shutdown
NEC690.12-2017andC22.1-2015Rule64.218
TS4-A-O
4- 123A
DONOTDISCONNECT
UNDERLOAD
TS4-A-O
4- 123A
DONOTDISCONNECT
UNDERLOAD
TigoRapidShutdown
NEC690.12-2017andC22.1-2015Rule64.218
DONOTDISCONNECT
UNDERLOAD
15
Page 16
TS4-A-DUO INSTALLATION
Standard modules can be equipped with TS4-A-Duo add-on units
as shown below.
Always connect modules to TS4-A inputs before connecting outputs.
TS4-A-Duo must have a PV module connected to its inputs before
connecting the outputs of TS4-A-Duo units in series.
To disconnect TS4-A-Duo from a module, disconnect the TS4-A-Duo
outputs from the string before disconnecting the TS4-A-Duo inputs
from the module junction box.
16
Page 17
COMMUNICATION INSTALLATION
COMMUNICATION DESIGN RULES
• MESH CONFIGURATION
•300 TS4 units per TAP
•900 TS4 units per CCA
•7 TAPs per CCA
•33ft (10m) max between TAP and closest TS4 unit
•115ft (35m) max wireless range using mesh
•No more than 10m between TS4 units on same TAP
• LEGACY CONFIGURATION
•120 TS4 units per TAP
•360 TS4 units per CCA
•7 TAPs per CCA
•50ft (15m) radius with line of sight between TAP & all TS4 units
Wireless signal range can be affected by solid obstructions. Refer to
TAP Placement Guide for more information.
NOTES
•All TS4 units in the same string must be assigned to the same CCA.
•For further design information, click here.
CCA and TAP CALCULATOR
•To estimate the number of CCAs and TAPs required for your
project, click here.
17
Page 18
TAP INSTALLATION -
PWRDATA
B A
MESH CONFIGURATION
accesspoint
230ft (70m) max
33ft (10m) max
access point
Place TAP within 10m of any TS4 unit in the
array, with a maximum distance of 10m
between TS4 units and 35m from TAP to
farthest TS4.
AUX RS485-1RS485-2GATEWAYPOWER
B AB AB A
access pointaccess point
TAP attaches to module frame using
built-in bracket. Mounting holes are
also available in case of frameless
modules.
OR
Quickconnectors:
Connectorblocks:
presswireinto terminal
usescrewterminals
Removeresistor to connect
anotherAccess Point in series.
• A solid red LED indicates that the
Discovery process failed or that the
CCA is not able to connect to the
Tigoserver.Incaseoferrors,
connecttotheCCAusingthe
mobile app for more details.
User PV-OffWarning
• Ablinkinggreenandyellow LED
indicatesthatPV-Offmodewas
activated manually.
• A solid yellow LED indicates that:
Discoveryhasnotbeenrun,
Discovery completed but did not
find all expected TAPs or TS4 units, or
CCA is not able to upload data.
Connect to the CCA using the Tigo
SMART app for more details.
SMART App ActivitySystem OK
• A blinking green LED indicates that
the mobile app is connected to the
CCA and is actively in use.
• Asolid greenLED indicates that
Discovery is complete and found all
expected TAPs and TS4 units, and
CCA is able to connect to the Tigo
server.
DiscoveryPower Off / No Status
• A blinking yellow LED indicates that
the CCA is scanning for TAPs and TS4
units(partofthecommissioning
process).
AUX RS485-1RS485-2GATEWAYPOWER
B AB AB A
• An unlit LED indicates that the CCA
is powered off.
Status LED
21
Page 22
CCA & TAP WIRING
PWRDATA
B A
-
+ B A
AUX RS485-1RS485-2GATEWAYPOWER
B AB AB A
OR
Quickconnectors:
Connectorblocks:
presswire into terminal
usescrew terminals
Remove resistor to connect
another Access Point in series.
INOUT
-
A
B
+
B AB AB A
PWRPWRDATADATA
BBAA
OR
Quickconnectors:
Connectorblocks:
presswire into terminal
usescrew terminals
Remove resistor to connect
another Access Point in series.
INOUT
-
A
B
+
PWRPWRDATADATA
BBAA
Quick connect
terminals
Terminal
block
120Ω
resistor
Connect multiple TAP units in series and leave terminating resistor only
in final TAP.
If using the quick connectors, remove the terminal block from the TAP
and strip approximately 3cm of insulation from the end of the cable.
Use a small flathead screwdriver to press the conductors into the quick
connectors. The individual conductors do not require stripped ends.
Connect all communication cables before powering on CCA.
• Up to 32 Modbus RS-485 devices can be
connected to a single Cloud Connect/CCA
• All devices must have a unique Modbus address
• All devices connected in series must have the same
baud rate, parity, and stop bit settings
• Check device manual for Modbus settings
Cloud Connect Advanced
(CCA)
AUX RS485-1RS485-2GATEWAYPOWER
B AB AB A
B A
To Modbus
Device(s)
B A
To TAP(s)/
Gateway(s)
Modbus Device #1
Manufacturer:
Model:
Type of Device:
Electrical Voltage:
Single or 3 Phase:
CT Rating:
Modbus Address:
Baud Rate:
Parity:
Stop Bits:
RS-485 Modbus terminalRS-485 Modbus terminal
GG++
--
Modbus Device #2
Manufacturer:
Model:
Type of Device:
Electrical Voltage:
Single or 3 Phase:
CT Rating:
Modbus Address:
Baud Rate:
Parity:
Stop Bits:
120Ω resistor across + and - terminals
on the last Modbus device in series
RS-485 communication cable with shield
Click here for more info about setting up inverters, meters, & sensors
23
Page 24
CONFIGURATION, REGISTRATION,
& COMMISSIONING
• Residential systems can perform configuration,
registration, and commissioning via the Tigo SMART App.
• Non-residential systems should perform site configuration
online at https://smart.tigoenergy.com.
Recommended procedure:
Enter site layout online
Type or scan TS4 barcodes
into online layout
Use Tigo SMART app to run
Discovery while on site
OR
Enter site layout online
Type or scan TS4 barcodes
into Excel .csv template*
Upload Excel .csv
template to layout
TS4 - O
4-1234T
4-1234T
Use Tigo SMART app to run
Discovery while on site
* Download the pre-formatted .csv template from the Layout step of the site builder
24
Page 25
TIGO SMART APP
Commissioning a new system using the Tigo App 3.0
Use the Tigo SMART app to:
• Create a system
• Input owner info
• Enter inverter & module types
• Congure layout and scan barcodes
• Congure network
• Commission Tigo hardware
• Monitor production
Install ‘Tigo SMART’ from the App Store or
Google Play
25
Page 26
GETTING STARTED
Requires active mobile data connection
If you do not have an installer account, tap
‘Enroll’ to create a new account. All system
data can also be accessed and edited
here: smart.tigoenergy.com
To proceed with a new installation, tap ‘+’
at the top right of the display
To service or monitor an existing system that
has already been congured, tap on that
system in your list
26
Page 27
SELECT EQUIPMENT
Requires active mobile data connection
• Go to ‘Select Equipment’
• Tap ‘+’ at the top right of the
display to add equipment
• Choose the inverter model,
the number of MPPTs, and the
associated CCA
• Select the manufacturer and
model of the PV modules
• Note: If using an inverter or
module not in the list, click the
‘+’ sign at the top right corner
• Place the CCA by tapping on
a position on the Layout grid
• Tap ‘Place’ next to an
equipment type to place it on
the grid
• Repeat for all CCAs and
inverters
27
Page 28
CONFIGURE MODULE LAYOUT
Requires active mobile data connection
• Place modules in the Layout
grid according to their
physical placement on site
• Note: Matching the physical
map of the system is optional
but improves its appearance
in the monitoring portal and
makes maintenance easier
• Tap and drag to change the
position of a placed item
• Tap ‘Register’ to begin
entering the TS4 barcodes
• Place the CCA by tapping on
a position on the Layout grid
• Tap ‘Place’ next to an
equipment type to place it on
the grid
• Repeat for all CCAs and
inverters
28
Page 29
CONNECT CCA TO SMARTPHONE
No mobile data connection required
•To connect the Smartphone to
the CCA via Bluetooth, tap the
serial number of the CCA you
wish to connect with
•Note: Use the Tigo Smart App to
pair with the CCA, instead of the
phone’s Bluetooth pairing screen
•Once connected to the CCA,
tap ‘Next’ to continue
• To connect the smartphone to
the CCA via Wi-Fi, choose the
CCA’s Wi-Fi connection in the
phone’s settings
• Note: Using the Wi-Fi connection
disconnects the smartphone
from the local Wi-Fi
• Once connected to the CCA,
tap ‘Next’ to continue
29
Page 30
CONFIGURE NETWORK SETTINGS –
CONNECT CCA TO INTERNET
Requires smartphone – CCA connection
• The Network Test checks the
Internet connection of the
CCA
• The test performs a series of
checks that can be used for
troubleshooting the network
connection
• Tap ‘Done’ to continue
COMMISSION THE TS4 UNITS –
RUN DISCOVERY
Requires smartphone – CCA connection
• Tap ‘Next’ in the ‘CCA
Network Settings’ to go to
‘Discovery’
• Note: Before starting
Discovery, all site equipment
and TS4 barcodes should be
input into the app. Begin the
process no later than an hour
before sunset.
• Tap ‘Start’ to run Discovery
• When Discovery is complete,
system production data can be
viewed online and in the app
30
Page 31
STRING DESIGN WITH TS4
TS4-M: MONITORING:
Standard rules for string length and design.
Requires CCA and TAP for monitoring.
Diodes
Monitoring
TS4-S: SAFETY:
Standard rules for string length and design.
Requires CCA and TAP for monitoring and rapid shutdown.
Diodes
MonitoringSafety
TS4-O: OPTIMIZATION:
Standard rules for string length
Flexible design (mixed orientations, unequal length strings in parallel)
Tolerant of shade and mismatch
Diodes
Monitoring
Safety
Optimization
TS4-L: LONG STRINGS:
Increased maximum string length, no derating for cold temperature
Flexible design (mixed orientations, unequal length strings in parallel)
Tolerant of shade and mismatch
Diodes
Monitoring
Safety
Optimization
Long Strings
Click here for TS4-L string sizing rules
31
Page 32
Appendix
Product Specications, Rapid Shutdown,
String Sizing with TS4-L
Page 33
TECHNICAL SPECIFICATIONS –
SMART MODULE WITH TS4-B
Electrical Ratings
DIODES
TS4-D
MONITORING
TS4-M
SAFETY
TS4-S
OPTIMIZATION
TS4-O
LONG STRINGS
TS4-L
Input
Rated DC Input Power-475W475W475W475W
Input Voltage-16 - 90V16 - 90V16 - 90V16 - 90V
Max Continuous
Input Current (I
MAX
)
12.5A12A12A12A12A
Output
Output Power Range0 – P
Output Voltage Range
Communication TypeN/AWirelessWirelessWirelessWireless
Rapid Shutdown UL Listed
(NEC 2014 & 2017 690.12)
Impedance MatchingNoNoNoYesYes
Output Voltage LimitNoNoNoNoYes
Maximum System Voltage1500V1500V1500V1500V1500V
1
Output voltage limit of TS4-L is factory-set.
2
Cloud Connect Advanced (CCA) and TAP/Gateway required for rapid shutdown compliance with TS4-S, TS4-O, & TS4-L. TS4-F requires
RSS Transmitter.
1
2
MAX
0 – V
OC
Need additional RS
device
0 - 475W0 - 475W0 - 475W0 - 475W
0 – V
OC
Need additional RS
device
0 – V
OC
YesYesYes
0 – V
OC
0 – V
MAX
Mechanical
Operating Temperature Range -40°C to +85°C (-40°F to +185°F), RH < 85%
Storage Temperature Range-40°C to +85°C (-40°F to +185°F), RH < 60%
Cooling Method)Natural Convection
Dimensions (with cover)152.5mm x 108mm x 25.3mm
Weight270g (base), 180g to 240g (cover)
Outdoor RatingIP67/IP68, NEMA 3R
Cabling
TypeH1Z2Z2-K
Output Cable Length1.2m (standard)
Rating Options
Cable Cross-Section6.3 ± 0.3mm
ConnectorsMC4 (standard), MC4 comparable, EVO2
UV Resistance500hr with UV light between 300-400nm @65°C
3
1 All TS4 covers are 1500V compatible. Specify max system voltage when ordering modules with TS4 bases for appropriate cables
& connectors.
3
1000V, 1500V
33
Page 34
TECHNICAL SPECIFICATIONS – TS4-R
Electrical Ratings
MONITORING
TS4-R-M
SAFETY
TS4-R-S
OPTIMIZATION
TS4-R-O
Input
Rated DC Input Power475W475W475W
Input Voltage16 - 90V16 - 90V16 - 90V
Max Continuous
Input Current (I
MAX
)
12A12A12A
Output
Output Power Range0 - 475W0 - 475W0 - 475W
Output Voltage Range0 – V
Communication TypeWirelessWirelessWireless
Rapid Shutdown UL Listed
(NEC 2014 & 2017 690.12)
Impedance MatchingNoNoYes
Output Voltage LimitNoNoNo
Maximum System Voltage1500V1500V1500V
1
Cloud Connect Advanced (CCA) and TAP/Gateway required for rapid shutdown compliance with TS4-R-S & TS4-R-O.
1
OC
Need additional
RS device
0 – V
OC
YesYes
0 – V
OC
Mechanical
Operating Temperature Range -40°C to +85°C (-40°F to +185°F), RH < 85%
Storage Temperature Range-40°C to +85°C (-40°F to +185°F), RH < 60%
Cooling Method)Natural Convection
Dimensions (with cover)178.5mm x 134mm x 25.5mm
Weight (base and cover)610g (M or S cover), 670g (O cover)
Outdoor RatingIP67/IP68, NEMA 3R
Cabling
TypeH1Z2Z2-K
Output Cable Length1m (standard)
Rating Options
Cable Cross-Section6.3 ± 0.3mm
ConnectorsMC4, MC4 comparable, EVO2
UV Resistance500hr with UV light between 300-400nm @65°C
3
1000V, 1500V
34
Page 35
TECHNICAL SPECIFICATIONS – TS4-A
Electrical Ratings
MONITORING
TS4-A-M
SAFETY
TS4-A-S
OPTIMIZATION
TS4-A-O
Input
Rated DC Input Power500W500W500W
Input Voltage16 - 90V16 - 90V16 - 90V
Max Continuous
Input Current (I
MAX
)
15A15A12A
Output
Output Power Range0 - 500W0 - 500W0 - 500W
Output Voltage Range0 – V
OC
Communication TypeWirelessWirelessWireless
Rapid Shutdown UL Listed
(NEC 2014 & 2017 690.12)
1
Need additional
RS device
Impedance MatchingNoNoYes
Output Voltage LimitNoNoNo
Maximum System Voltage1500V1500V1500V
1
Cloud Connect Advanced (CCA) and TAP/Gateway required for rapid shutdown compliance with TS4-A-S & TS4-A-O.
0 – V
OC
0 – V
YesYes
OC
Mechanical
Operating Temperature Range -40°C to +85°C (-40°F to +185°F), RH < 85%
Storage Temperature Range-40°C to +85°C (-40°F to +185°F), RH < 60%
Cooling Method)Natural Convection
Dimensions138.4mm x 139.7mm x 22.9mm
Weight490g
Outdoor RatingIP68
Cabling
TypeH1Z2Z2-K
Output Cable Length1.2m
Rating Options
Cable Cross-Section6.3 ± 0.3mm
ConnectorsMC4 (standard), MC4 comparable, EVO2
UV Resistance500hr with UV light between 300-400nm @65°C
Cloud Connect Advanced (CCA) and TAP/Gateway required for rapid shutdown activation with and TS4-A-O-Duo.
OC
Yes
Mechanical
Operating Temperature Range -40°C to +85°C (-40°F to +185°F), RH < 85%
Storage Temperature Range-40°C to +85°C (-40°F to +185°F), RH < 60%
Cooling Method)Natural Convection
Dimensions138.4mm x 139.7mm x 22.9mm
Weight560g
Outdoor RatingIP68
Cabling
TypeH1Z2Z2-K
Output Cable Length1.8m
Rating Options
Cable Cross-Section6.3 ± 0.3mm
ConnectorsMC4 (standard), MC4 comparable, EVO2
UV Resistance500hr with UV light between 300-400nm @65°C
3
1000V, 1500V
1800
139.7
138.4
30
120
±10
22.9
8
±10
37
Page 38
TECHNICAL SPECIFICATIONS –
CCA & TAP
Electrical
CCA
Input Voltage10VDC- 25V
Power Consumption3W - 7W
Power Supply138.4mm x 139.7mm x 22.9mm
Input Voltage100VAC- 240V
Mechanical
DIN rail mountable enclosure
Dimensions (CCA only)31mm x 115.51mm x 71.54mm
Weight (CCA only)126g
Operating Temperature Range-20°C to +70°C (-4°F to +158°F)
CoolingNatural Convection
Capacity
Mesh CongurationEach CCA supports up to 900 TS4 units and up to 7 TAPs
Legacy CongurationEach CCA supports up to 360 TS4 units and up to 7 TAPs
User Interface
Mobile App: Tigo SMART App for Android and iOS
Multi-function LED status indicator
AUX RS485-1RS485-2GATEWAYPOWER
14.96
B AB A B A
7.02108.87
105.10
70.70
31 30
4 - 103A4543R
Ethernet
Cellular
1 2
80.33
USB
Wi-Fi
115.5
DC
AC
126.2
access point
100.7
Power Supply
(Optional)
+
LL
TAPCCA
3.7
17.5
-
90
NN
All dimensions i n mm.
Electrical
TAP
Input Voltage24V
DC
Mechanical
Dimensions126.2mm x 130.0mm x 26.8mm (with bracket)
Weight227g
Operating Temperature Range-20°C to +85°C (-4°F to 185°F)
Environmental RatingIP68, Type 4R
CoolingNatural Convection
Capacity
Mesh Conguration300 TS4 units up to 115ft (35m) away
Legacy Conguration120 TS4 units up to 50ft (15m) away
38
Page 39
TESTING RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT
DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN
ARRAY
SOLAR ELECTRIC
PV PANELS
TS4-L, TS4-O, and TS4-S (includes TS4-R and TS4-A add-on versions)
with Cloud Connect Advanced and TAP are a solution to meet the
NEC 2014 & 2017 690.12 Rapid Shutdown requirements.
TS4 units with the safety feature automatically enter rapid shutdown
mode when the CCA is switched off and resume energy production
when power is restored to the CCA.
Wait 30 seconds after rapid shutdown activation before disconnecting
DC cables or turning off DC disconnect.
Test your rapid shutdown system by switching off the AC power to the CCA.
TS4 units with the safety feature will reduce their output to 0V when the CCA
is powered off.
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
Photovoltaic Rapid
Shutdown System, QIJS
E469960
WHEN USED WITH
Place safety labels in proper location
TS4
The CCA power supply MUST be on the same AC branch circuit as the
inverter to meet rapid shutdown requirements.
Click here for more info about Rapid Shutdown
39
Page 40
STRING SIZING WITH TS4-L
TS4-L has a state of the art technology designed to reduce balance of system
costs by allowing longer strings. This can reduce the number of strings by up
to 30%, which directly correlates to a 30% reduction in combiner boxes, wiring,
Verify string VMPlimits by dividing inverter max MPP voltage range by the Smart Module's VMP.
From the example above: 510V ÷ 30.6V = 16 modules per string by inverter
In case of discrepancy between the code requirement and the inverter voltage
requirement pick the lower number of the two. Therefore, this example results in a maximum
of 16 panels per string, a 33% increase in string power, with a corresponding reduction in
electrical BOS costs.
40
Page 41
TAP PLACEMENT - LEGACY(PRE-MESH
PWRDATA
B A
access point
accesspoint
50ft (15m)
)
Place TAP near center of array or each
sub-array.
AUX RS485-1RS485-2GATEWAYPOWER
B AB AB A
access pointaccess point
TAP attaches to module frame using
built-in bracket. Mounting holes are also
available in case of frameless modules.
OR
Quickconnectors:
Connectorblocks:
presswireinto terminal
usescrewterminals
Removeresistor to connect
anotherAccess Point in series.
INOUT
-
A
B
+
PWRPWRDATADATA
BBAA
Connect multiple TAP units in series and leave terminating resistor in final TAP only.
Use 4-conductor RS485 (18-22 AWG) cable between TAP and CCA.
Legacy conguration (same as Gateway):
•120 TS4 units per TAP
•360 TS4 units per CCA
•7 TAPs per CCA
•50ft (15m) radius with line of sight between TAP & all TS4 units
41
Page 42
INSTALLATION COMPLETE
For more details on designing and
installing solutions powered by Tigo,
please visit: