Tigo TS4-F, TS4-R-F, TS4-A-F, RSS Transmitter Installation Manual

Installation Manual
TS4-F, TS4-R-F, TS4-A-F, RSS Transmitter
IMPORTANT SAFETY INSTRUCTIONS
LETHAL VOLTAGE MAY BE PRESENT IN ANY PV INSTALLATION
SAVE THESE INSTRUCTIONS
This manual contains important instructions for installation and maintenance of the Tigo product models TS4-F, TS4-R-F, TS4-A-F, and the RSS Transmitter.
Risk of electric shock, do not remove cover, disassemble, or repair, no user serviceable parts inside. Refer servicing to qualied service personnel.
Failure to adhere to these instructions may result in injury or death, damage to the system or voiding the factory warranty.
Installation must be performed by trained professionals only. Tigo does not assume liability for loss or damage resulting from improper handling, installation, or misuse of products.
Do not operate the Tigo TS4 units if they have been physically damaged. Check existing cables and connectors, ensuring they are in good condition and appropriate in rating. Do not operate Tigo TS4 units with damaged or substandard wiring or connectors. Tigo TS4 units must be mounted on the high end of the PV module backsheet or racking system, and in any case above ground.
Do not connect or disconnect under load. Turning off the Inverter and/or the Tigo products may not reduce this risk. Internal capacitors within the inverter can remain charged for several minutes after disconnecting all power sources. Verify capacitors have discharged by measuring voltage across inverter terminals prior to disconnecting wiring if service is required. Wait 30 seconds after rapid shutdown activation before disconnecting DC cables or turning off DC disconnect.
Always assume TS4 units are in “ON” state, or may turn on when restarting.
The transmitter control power supply MUST be on the same AC branch circuit as the inverter to meet rapid shutdown requirements.
05/21/2019
2
TABLE OF CONTENTS
TS4-F Rapid Shutdown System 4
TS4 Fire Safety Products 5
System Overview: TS4-F 6
System Overview: TS4-R-F 7
System Overview: TS4-A-F 8
Installation Notes 9
TS4-F Installation 10
TS4-R-F Installation 11
TS4-A-F Installation 12
RSS Transmitter Installation – Single RSS Core 13
RSS Transmitter Wiring – Single RSS Core 14
RSS Transmitter Grounding – Single RSS Core 15
Technical Specications – RSS Transmitter Commercial Kit 26
Technical Specications – RSS Transmitter Outdoor Kit 27
Testing Rapid Shutdown 28
Conduit Drilling Guide 29
Installation Complete 30
Ordering Information 31
RSS Transmitter Installation – Dual RSS Core 16
RSS Transmitter Wiring – Dual RSS Core 17
RSS Transmitter Grounding – Dual RSS Core 18
RSS Transmitter Commercial Installation 19
RSS Transmitter Commercial Wiring 20
Technical Specications – TS4-F / TS4-R-F 22
Mechanical Specications – TS4-F / TS4-R-F 23
Technical Specications – TS4-A-F 24
Technical Specications – RSS Transmitter 25
3
TS4-F RAPID SHUTDOWN SYSTEM
Module-Level Power Electronics:
TS4-F, TS4-R-F, TS4-A-F
• NEC 2017 690.12 Rapid shutdown compliant
• Module-level deactivation
• PLC communication
• Plug & play, no conguration required
Transmitter:
RSS Transmitter
• Rapid Shutdown System Transmitter for rapid shutdown activation of TS4-F, TS4-R-F, or TS4-A-F units
• The external device that provides a keep­alive signal to the TS4-F via Power Line Communication
4
TS4 FIRE SAFETY PRODUCTS
Module-Integrated:
TS4-F
• Module electronics are contained in the junction box, installed at the PV module factory.
• Connected in series like regular modules
• No additional wiring connections to make
Add-on/Retrot:
TS4-R-F, TS4-A-F
• Bracket clips to module frame without tools
• TS4-R-F or TS4-A-F outputs are connected in series to form a string
• No additional grounding required
5
SYSTEM OVERVIEW: TS4-F
1 2 3
RSS
Transmitter
1. Modules with integrated TS4-F
2. RSS Transmitter and RSS Core
3. Inverter
The TS4-F requires a Tigo RSS Transmitter or inverter with built-in transmitter for operation. The Tigo RSS Transmitter is installed in line with a solar PV inverter, as shown, and can be installed inside the inverter or external to it.
Method of Operation
All TS4-F units start in the OFF position and measure 0.6V at the output. When power is supplied to the RSS Transmitter, the TS4-F units turn ON and allow full PV module voltage.
The units constantly receive a “keep-alive” signal from the transmitter over PLC. When power to the transmitter is cut, this keep-alive signal ceases, sending every TS4-F into shutdown mode with output reduced to 0.6V.
6
SYSTEM OVERVIEW: TS4-R-F
1 2 3
TS4-R-F
4-123A
RSS
Transmitter
Note: connect modules to TS4-R inputs before connecting outputs
The TS4-R-F requires a Tigo RSS Transmitter or inverter with built-in transmitter for operation.
• TS4-R-F mounting is recommended on the upper right as shown, but can be placed elsewhere on the frame or bolted to the racking if needed.
• TS4-R-F cable glands must not be facing up.
• Allow clearance between PV module and mounting surface for air circulation around TS4-R-F.
• Do not drill additional mounting holes in the frame or metal bracket.
7
SYSTEM OVERVIEW: TS4-A-F
1 2 3
TigoRapidShutdown
NEC690.12-2017andC22.1-2015Rule64.218
DONOTDISCONNECT
TS4-A-F
UNDERLOAD
4-123A
RSS
Transmitter
Note: connect modules to TS4-A inputs before connecting outputs
The TS4-A-F requires a Tigo RSS Transmitter or inverter with built-in transmitter for operation.
• TS4-A-F mounting is recommended on the upper right as shown, but can be placed elsewhere on the frame or bolted to the racking if needed.
• TS4-A-F cable glands must not be facing up.
• Allow clearance between PV module and mounting surface for air circulation around TS4-A-F.
• Do not drill additional mounting holes in the frame or metal bracket.
8
INSTALLATION NOTES
• TS4-F, TS4-R-F, and TS4-A-F are shipped in the OFF position and will measure 0.6V at the output when the keep-alive signal is not present.
• Failing to follow the sequence of installation steps may result in TS4 damage not covered under warranty.
• Connect all TS4-R-F or TS4-A-F units to their respective modules before connecting their outputs in series.
• Install all TS4-F, TS4-R-F, or TS4-A-F units before powering on the RSS Transmitter.
• Never apply an external voltage source to a module or string equipped with TS4-F, TS4-R-F, or TS4-A-F units.
• If parallel string connections are needed, rst connect the TS4-F, TS4-R-F,
or TS4-A-F to the PV modules, then connect all TS4-F, TS4-R-F, or TS4-A-F outputs in series, and nally pass one side (+ or -) of the homeruns through the PLC transmitter to turn the system ON.
• Place rapid shutdown system label no more than 1m (3ft) from initiator (AC disconnect) or service panel containing means of disconnection if not at same location.
Place safety labels in proper location
9
TS4-F INSTALLATION
Smart modules with an integrated TS4 Junction box are installed and connected in series just like standard PV modules.
Connect modules with TS4-F in series before powering on the RSS Transmitter.
1
TS4-F
4-123A
TS4-F
4-123A
2
TS4-F
4-123A
TS4-F
4-123A
10
TS4-R-F INSTALLATION
Standard modules can be equipped with TS4-R-F add-on/retrot units as shown below.
Always connect modules to TS4-R inputs before connecting outputs.
Each TS4-R-F must have a PV module connected to its input before connecting the outputs of TS4-R-F units in series.
To disconnect TS4-R-F from a module, disconnect the TS4-R-F outputs from the string before disconnecting the TS4-R-F inputs from the module junction box.
1
3
TS4-R-F
4- 123A
TS4-R-F
2
TS4-R-F
4- 123A
4-123A
TS4-R-F
4-123A
11
TS4-A-F INSTALLATION
Standard modules can be equipped with TS4-A-F add-on/retrot units as shown below.
Always connect modules to TS4-A inputs before connecting outputs.
Each TS4-A-F must have a PV module connected to its input before connecting the outputs of TS4-A-F units in series.
To disconnect TS4-A-F from a module, disconnect the TS4-A-F outputs from the string before disconnecting the TS4-A-F inputs from the module junction box.
1
3
TS4-A-F
4- 123A
TigoRapid Shutdown
NEC690.12-2017andC22.1-2015Rule64.218
DONOTDISCONNECT
UNDERLOAD
TS4-A-F
4- 123A
TigoRapidShutdown
NEC690.12-2017andC22.1-2015Rule64.218
2
TigoRapid Shutdown
NEC690.12-2017andC22.1-2015Rule64.218
TS4-A-F
4- 123A
DONOTDISCONNECT
UNDERLOAD
TigoRapidShutdown
NEC690.12-2017andC22.1-2015Rule64.218
DONOTDISCONNECT
UNDERLOAD
TS4-A-F
4- 123A
DONOTDISCONNECT
UNDERLOAD
12
RSS TRANSMITTER INSTALLATION – SINGLE RSS CORE
LED (Power) +V
GND
AC
85-264V
PSU
1 2
-
+
RSS
NN
LL
Transmitter
LED (Signal)
IN
*
RSS Core inputs
3
1 DIN Rail PSU
2 RSS Transmitter
3 RSS Core (CT)
* *
Suggested locations for conduit
*
Transmitter power supply must be on same AC branch circuit as inverter to meet rapid shutdown requirements.
Note: Install TS4-F before powering on RSS Transmitter
· Drill holes in enclosure for conduit (see drilling guide for placement)
· Mount RSS Transmitter and power supply on DIN rail
· Connect DC leads from power supply (1) to transmitter (2)
· Connect RSS Core (3) to transmitter
Place rapid shutdown system label no more than 1m (3ft) from RSS Transmitter or AC disconnect if not at same location.
3
1 2
RSS TRANSMITTER WIRING – SINGLE RSS CORE
-
+
RSS
Transmitter
AC Wires for Power Supply
NN
LL
Homerun
Only (+) or (-)
through RSS Core
Note: Install TS4-F before powering on RSS Transmitter
· Pass either positive or negative homerun through RSS Core
· Connect wires to AC side of power supply
Max number of strings per RSS Core: 10 Max string length: 30 modules Max current per RSS Core: 100A Max cable length from inverter (+) to inverter (-): 1000ft (300m)
RSS TRANSMITTER GROUNDING – SINGLE RSS CORE
DC Ground
-
+
RSS
AC Ground
NN
LL
Transmitter
Conduit Ground
Note: Install TS4-F before powering on RSS Transmitter
· Connect AC and DC ground wires to DIN rail
· Ground all conduit connections
· Turn on AC power to Transmitter power supply to activate keep-alive signal and energize PV array
Warning: nonmetallic enclosure does not provide bonding between conduit connections. Use grounding type bushings and jumper wires.
RSS TRANSMITTER INSTALLATION – DUAL RSS CORE
LED (Power) +V
GND
1 2
-
+
RSS
NN
LL
Transmitter
RSS Core inputs LED (Signal)
IN
RSS Core inputs
Suggested locations for conduit
1 DIN Rail PSU
2 RSS Transmitter
34RSS Core (CT)
RSS Core (CT)
* *
*
3
4
* *
*
Transmitter power supply must be on same AC branch circuit as inverter to meet rapid shutdown requirements.
Note: Install TS4-F before powering on RSS Transmitter
· Drill holes in enclosure for conduit (see drilling guide for placement)
· Mount RSS Transmitter and power supply on DIN rail
· Connect DC leads from power supply (1) to transmitter (2)
· Connect RSS Core (3) and (4) to transmitter
Place rapid shutdown system label no more than 1m (3ft) from RSS Transmitter or AC disconnect if not at same location.
3 4
1 2
RSS TRANSMITTER WIRING – DUAL RSS CORE
-
+
RSS
Transmitter
AC Wires for Power Supply
NN
LL
Homerun
Only (+) or (-)
through RSS Core
Homerun
Note: Install TS4-F before powering on RSS Transmitter
· Pass either positive or negative homerun through RSS Cores
· Connect wires to AC side of power supply
Max number of strings per RSS Core: 10 Max string length: 30 modules Max current per RSS Core: 100A Max cable length from inverter (+) to inverter (-): 1000ft (300m)
RSS TRANSMITTER GROUNDING – DUAL RSS CORE
DC Ground
-
+
RSS
AC Ground
NN
LL
Transmitter
Conduit Ground
Note: Install TS4-F before powering on RSS Transmitter
· Connect AC and DC ground wires to DIN rail
· Ground all conduit connections
· Turn on AC power to Transmitter power supply to activate keep-alive signal
Warning: nonmetallic enclosure does not provide bonding between conduit connections. Use grounding type bushings and jumper wires.
RSS TRANSMITTER COMMERCIAL INSTALLATION
200-500V
DC
+12V
DC
-12V
Ground
Neutral
Line
AC
Power Supply
+V
-V
+ V ADJ
+
LL
G L2L1
1 2
-
NN
RSS
Transmitter
4
LED (Power)
IN
+V
GND
RSS Core inputs LED (Signal) RSS Core inputs
1 DIN Rail PSU
3
2 RSS Transmitter
34RSS Core (CT)
RSS Core (CT)
Transmitter power supply must be on same AC branch circuit as inverter to meet rapid shutdown requirements.
Note: Install TS4-F before powering on RSS Transmitter
· Mount RSS Transmitter and power supply on DIN rail
· Connect DC leads from power supply (1) to transmitter (2)
· Connect RSS Core (3) and (4) to transmitter
3 4
1 2
Place rapid shutdown system label no more than 1m (3ft) from RSS Transmitter or AC disconnect if not at same location.
RSS TRANSMITTER COMMERCIAL WIRING
+V
-V
+ V ADJ
G L2L1
-
+
RSS
NN
LL
Transmitter
Homerun
Only (+) or (-)
through RSS Core
Homerun
Only (+) or (-)
through RSS Core
Note: Install TS4-F before powering on RSS Transmitter
· Pass either positive or negative homerun through RSS Cores
· Connect wires to AC side of power supply
· Turn on AC power to Transmitter power supply to activate keep-alive signal
Max number of strings per RSS Core: 10 Max string length: 30 modules Max current per RSS Core: 150A Max cable length from inverter (+) to inverter (-): 1000ft (300m)
Appendix
TS4-F, TS4-R-F, TS4-A-F, RSS Transmitter
TECHNICAL SPECIFICATIONS – TS4-F / TS4-R-F
Electrical Ratings TS4-F / TS4-R-F Fire Safety
Input
Rated DC Input Power 475W
Input Voltage 16 - 90V
Max Continuous Input Current (I
Output
Output Power Range 0 - 475W
Output Voltage Range 0 – V
Communication Type Power Line Communication (PLC)
Rapid Shutdown UL Listed (NEC 2014 & 2017 690.12) Yes
Impedance Matching Capability No
Output Voltage Limit No
Maximum System Voltage 1500V
Fuse Rating 20A
) 12.5A
MAX
OC
Specify system voltage when ordering (1000V / 1500V) for appropriate cables & connectors.
Rapid shutdown activation requires RSS Transmitter.
22
MECHANICAL SPECIFICATIONS – TS4-F / TS4-R-F
Specications TS4-F / TS4-R-F Fire Safety
Mechanical
Operating Temperature Range: -40°C to +70°C (-40°F to +158°F), RH < 85%
Storage Temperature Range: -40°C to +70°C (-40°F to +158°F), RH < 60%
Cooling Method Natural Convection
Dimensions (with cover) 178.5mm x 134mm x 25.5mm
Weight (base and cover) 670g
Outdoor Rating IP68, NEMA 3R
Cabling
Type H1Z2Z2-K
Output Length 1.2m standard, other lengths available
Cable Options 1000V rated, 1500V rated
Cable Cross-Section 6.3 ± 0.3mm
Connectors MC4, MC4 compatible
UV Resistance 500hr with UV light between 300-400nm @65C
Maximum System Voltage 1500V
23
TECHNICAL SPECIFICATIONS – TS4-A-F
Specications TS4-A-F Fire Safety
Environmental
Operating Temperature Range -40°C to +85°C (-40°F to +185°F)
Outdoor Rating IP68, NEMA 3R
Mechanical
Dimensions 138.4mm x 139.7mm x 22.9mm
Weight 490g
Electrical
Input Voltage 16 - 90V
Maximum Continuous Input Current (I
) 12.5A
MAX
Maximum Power 500W
Output Cable Length 1.2m (standard), other lengths available
Connectors MC4 compatible (standard)
Communication Type PLC
Maximum System Voltage 1500V
Rapid Shutdown UL Listed (NEC 2014 & 2017 690.12) Yes
22.9
8
120
±10
1200
139.7
138.4 30
±10
Specify system voltage when ordering (1000V / 1500V) for appropriate cables & connectors.
Rapid shutdown activation requires RSS Transmitter.
24
TECHNICAL SPECIFICATIONS – RSS TRANSMITTER
Electrical Ratings RSS Transmitter
Input
Input Voltage
12V
DC
Input Current 1A
Average Supply Power 0.85W
Dimensions(Transmitter only) 90.2mm x 36.3mm x 57.7mm
RSS Core
Maximum Current
Maximum MPPT String Voltage 1500V
150A per Core (Single Core: 150A, Dual Core: 300A)
DC
Internal Opening for Wires ~25mm
Outside Dimensions 59mm
Maximum Number of Strings per Core 10
Maximum String Length 30 modules
Environmental
Temperature -40°C to 85°C
Recommended max. torque 0.79 N/m for wiring
36.3 17.5
-
+
Rapid
Shutdown
System
Transmitter
RSS Transmitter RSS CoreOptional Power Supply
90.2
NN
LL
90
610
18 AWG
25.0 min
73 max
All dimensions in mm.
25
TECHNICAL SPECIFICATIONS – RSS TRANSMITTER COMMERCIAL KIT
Electrical Ratings RSS Transmitter
Input
Input Voltage
12V
DC
Input Current 1A
Average Supply Power 0.85W
Included Power Supply Rating
480/277VACinput, 12VDCoutput
Dimensions(Transmitter only) 90.2mm x 36.3mm x 57.7mm
RSS Core
Maximum Current 150A per Core (includes 2 Cores for 300A)
Maximum MPPT String Voltage 1500V
DC
Internal Opening for Wires ~25mm
Outside Dimensions 59mm
Maximum Number of Strings per Core 10
Maximum String Length 30 modules
Environmental
Temperature -40°C to 85°C
Recommended max. torque 0.79 N/m for wiring
40
36.3
610
+V
-V
+ V ADJ
Rapid
Shutdown
System
Transmitter
RSS Transmitter RSS Core
90.2
G L2L1
Power Supply
125.2
18 AWG
25.0 min
73 max
All dimensions in mm.
26
TECHNICAL SPECIFICATIONS – RSS TRANSMITTER OUTDOOR KIT
Electrical Ratings RSS Transmitter
Input
Input Voltage
12V
DC
Input Current 1A
Average Supply Power 0.85W
Dimensions(Transmitter only) 90.2mm x 36.3mm x 57.7mm
RSS Core
Maximum Current
Maximum MPPT String Voltage 1500V
100A per Core (Single Core: 100A, Dual Core: 200A)
DC
Internal Opening for Wires ~25mm
Outside Dimensions 59mm
Maximum Number of Strings per Core 10
Maximum String Length 30 modules
Environmental
Temperature -40°C to 85°C
Recommended max. torque 0.79 N/m for wiring
36.3
Rapid
Shutdown
System
Transmitter
90.2
110
RSS Transmitter Outdoor Enclosure RSS Core Installation Example
170
18 AWG
270
610
-
+
Rapid
Shutdown
System
Transmitter
NN
LL
73
25.0 min
max
All dimensions in mm.
27
TESTING RAPID SHUTDOWN
TS4-F (or TS4-R-F / TS4-A-F) and an RSS Transmitter are a solution to meet NEC 2014 & 2017 690.12 Rapid Shutdown requirements.
TS4-F, TS4-R-F, and TS4-A-F units automatically enter rapid shutdown mode when the RSS Transmitter is switched off and resume energy production when power is restored to the RSS Transmitter.
Wait 30 seconds after rapid shutdown activation before disconnecting DC cables or turning off DC disconnect.
Test your rapid shutdown system by switching off the AC power to the RSS Transmitter or inverter with built-in transmitter.
TS4-F, TS4-R-F, and TS4-A-F units will reduce their output to 0.6V when the Transmitter is powered off.
Place safety labels in proper location
The RSS Transmitter control power supply MUST be on the same AC branch circuit as the inverter to meet rapid shutdown requirements.
Click here for more info about Rapid Shutdown
28
CONDUIT DRILLING GUIDE
Enclosure Drilling Guide for .75" Conduit
Single Core Dual Core
108
47.1
2X Ø 28
41.6
41.6
68
41.6
47.1
Ø 28
40
47.1
3X Ø 28
Enclosure Drilling Guide for 1" Conduit
Single Core Dual Core
41.6
40
47.1
2X Ø 28
104.5
50.6
2X Ø 35
41.6
41.6
41.6
41.6
52.3
52.3 52.3
50.6
Ø 35
50.6 50.6
3X Ø 35 2X Ø 35
*all dimensions in mm
INSTALLATION COMPLETE
Problems?
TS4-F Troubleshooting Guide
For more details on designing and installing solutions powered by Tigo, please visit:
Tigo Academy Resource Center
Or contact us at:
training@tigoenergy.com
ORDERING INFORMATION
Part # Description
Transmitter
490-00000-10 Single Core (150A) RSS DIN Rail Transmitter (no power supply)
490-00000-20 Dual Core (300A) RSS DIN Rail Transmitter (no power supply)
493-00000-20 Commercial Dual Core RSS DIN Rail Transmitter, 480/277VACPower Supply
492-00000-10 Single Core RSS DIN Rail Transmitter Kit, 120/240VACPower Supply, Outdoor Enclosure
492-00000-20 Dual Core RSS DIN Rail Transmitter Kit, 120/240VACPower Supply, Outdoor Enclosure
490-00100-10 Single RSS Core, RSS Transmitter PCBA
490-00100-20 Dual RSS Core, RSS Transmitter PCBA
983-01512-00 DIN Rail Power Supply, 12VDC, 1.25A
TS4-A-F
Standard
458-00257-12 1000V UL / TÜV, 1.2m cable, MC4 compatible
Options
458-00252-32 1000V UL / TÜV, 1.2m cable, MC4
458-00257-00 1000V UL / TÜV, 1m cable, MC4 compatible
458-00252-12 1000V UL / TÜV, 1m cable, MC4
458-00261-32 1500V UL / TÜV, 1.2m cable, EVO2
458-00261-12 1500V UL / TÜV, 1m cable, EVO2
For sales info:
sales@tigoenergy.com or 1.408.402.0802
For technical information:
http://support.tigoenergy.com
For product info:
Visit www.tigoenergy.com/products
For technical info:
http://support.tigoenergy.com
For additional info and product selection assistance, use Tigo’s online design tool at
www.tigoenergy.com/design
Tigo Energy, Inc. 420 Blossom Hill Rd, Los Gatos, California 95032 USA | www.tigoenergy.com
P: +1.408.402.0802 F: +1.408.358.6279 | sales@tigoenergy.com