IMPORTANT SAFETY INFORMATION4
OPERATING GUIDELINES5-6
CARE AND MAINTENANCE OF YOUR RG5410A6
ADDITIONAL RECOVERY TANK INFORMATION7
PURGING NON-CONDENSABLE GASES 8
HELPFUL HINTS FOR REFRIGERANT RECOVERY9-10
OPERATING YOUR RG5410A11
DIAGRAM FOR REFRIGERANT RECOVERY11
SELF PURGING YOUR RG5410A12
SELF PURGE/AUTO EVACUATE12
DIAGRAM FOR “PUSH/PULL” METHOD13
SET-UP DIAGRAM FOR TANK PRE OR SUB COOLING PROCEDURE13
OPTIONAL RECOVERY / TANK PRE OR SUB14
COOLING FOR FIXED HOSE SET-UP
REFRIGERANT FLOW DIAGRAM15
RG5410A PARTS DIAGRAM/PARTS AND ACCESSORIES LIST16
RG5410A WIRING DIAGRAM17
INSTALLATION OF OPTIONAL80% TANK
CAPACITYSENSING COMPONENTS (KIT KT-50001)
RG5410A-KT MODEL18
TROUBLESHOOTING YOUR RG5410A19
FULL ONE YEAR WARRANTY20
SAFETY COMES FIRST! Read all safety, operating
guidelines and instructions before operating your
RG5410A.
1. CAUTION: ONLY A QUALIFIED TECHNICIAN
SHOULD OPERATE THIS RECOVERY UNIT.
The operator must be familiar with air conditioning
and refrigeration systems, refrigerants and the
dangers of pressurized components.
2. Always think before acting, familiarity breeds care-
lessness and carelessness can be harmful to your
health or, worse, result in death.
3. m WARNING Always wear safety goggles and
protective gloves when working with refrigerants.
Contact with refrigerant may cause injury.
Disconnect hoses with extreme caution! All hoses
may contain liquid refrigerant under pressure.
4. m PRESSURIZED TANK CONTAINS LIQUID
REFRIGERANT. NEVER OVERFILLSTORAGE
TANKS. OVERFILLING OF THE TANK MAY
CAUSE AVIOLENTEXPLOSIONANDPOSSIBLE
INJURY OR DEATH.DONOT: Exceedthe working
pressure of Recovery Tank cylinder.
5. m Warning: DO NOT: Exceed the working pres-
sure of each cylinder. Recovery cylinders are
designed for different pressures.Your RG5410A
is not supplied with a recovery tank, it requires the
use of tanks with a minimum of 350 psi working
pressure and PROMAX strongly recom-
mends the use of 400 psi tanks.
NOTE: The use of a 400 psi tank is mandatory when recovering R-410A.
See PROMAX Recovery Tanks under Parts and
Accessories section on Page 16.
5. m A scale must be used to avoid overfilling the
storage tank. DO NOT OVERFILL. Tank is full at
80% volume. Tank may explode if filled more than
80% due to liquid expansion.
7.Read all safety information regarding the safe
handling of refrigerant and refrigerant oil, includ-
ing the Material Safety Data Sheet. MSDS
sheets can be obtained from your refrigerant
supplier.
8. If you expect temperatures in excess of 135° F,
contact the refrigerant supplier.
9. Be sure that any room where you are working is
thoroughly ventilated, especially if a leak is suspected. Refrigerant vapor is hazardous to your
health and can cause death.
10. m Avoid breathingA/Crefrigerantand lubrica-
tion vapor or mist. Exposure may irritate eyes,
nose and throat. If accidental system discharge
occurs,ventilateworkareabeforeresuming service.
11. i WARNING:TOREDUCE THE RISKOF FIRE:
• Never operate unit inanexplosiveenvironment!
Do not use this equipment in the vicinity of
spilled or open containers of gasoline or any
other flammable liquid.
• When using an extension cord it should be a
3-wire, 14 AWG minimum and no longer than
25 feet.
• Usethisequipment in locationswithmechanical
ventilation that provides at least four air
changes per hour or locate the equipment at
least 18 inches above the floor.
• Never use oxygen when testing for leaks. Any
oil in contact with oxygen under pressure will
form an explosive mixture.
12. c High voltage electricity inside panels. Risk of electrical shock. Be sure to disconnect
theunitfrom thepowersource before servicing it.
13. To reduce the risk of injury, care should be
taken when moving this equipment.
6. Use ONLY authorized refillable refrigerant tanks.
NEVER use a standard disposable 30 lb. tank
(the typeofcontainerinwhichvirginrefrigerant
is sold) to recover refrigerant.
4
Page 5
OPERATING GUIDELINES
m Before operating the RG5410A recovery unit,
read the following m
1. RG5410A IS APPROVED FOR USE WITH THE
FOLLOWING CATEGORY III, IV and V REFRIGERANTS (Per ARI 740):
2. A FILTER must always be used and should
replaced frequently. We recommend that a clean
filter be used for every service job.
Failure to use a filter will invalidate your warranty.
The use of a filter will greatly reduce the risk of
damage to your RG5410A, by preventing
foreign material from entering the unit.
3. Each filter should be labeled and used exclusively
for one type of refrigerant only.
4. Always open service and cylinder valves slowly.
This allows rapid control of the flow of gases if
there is any danger. Once it is determined that
there is no danger, the valves can be opened
fully.
5. Always isolate large amounts of refrigerant and
close off valves after use, so if a leak should
develop anywhere in the system, the refrigerant
will not escape.
6. Keep all connections to the refrigeration system
thoroughly dry and clean. If moisture enters the
refrigeration system, it is likely to cause considerable damage.
7. Promax strongly recommends the use of the
optional 80% Capacity Shutoff Kit (p/n KT-5001).
When installed and used with a recovery tank that
has an internal float switch, the RG5410A will
shut down automatically when the tank is 80% full.
Your RG5410A is pre-wired from the factory for
this kit. Note: The RG5410A is also available in
model RG541OA-KT, with the 80% Shutoff Kit
installed direct from the factory.
8. m A CAUTION: Use only authorized refillable
refrigerant recovery tanks. Federal regulations
require refrigerant to be transported only in
containers meeting DOT spec. 4BA or 4BW.
NEVER use a standard disposable 301b. ta, .1% (the
type of container in which virgin refrigerant is sold) to
recover refrigerant.
9. m A scale must be used to avoid overfilling the
storage tank. DO NOT OVERFILL. Tank is full at
80% volume. Tank may explode if filled more than
80% due to liquid expansion. Below is a repre-
sentative sample for R-22 refrigerant:
TANK SIZE MAX NETWEIGHT
30 lb. Tank24 lbs.
50 lb. Tank40 lbs.
Note: Promax strongly recommends the use of the
ADS-100 Refrigerant Scale for monitoring tank
capacity.
10. Your RG5410A has two Internal Pressure
Shut Off switches, a standard 400psi and
a 550psi (when the High Pressure (R410A)
switch is engaged). The shut off switches will
automatically reset after the pressure drops
below 200 psi.
m WARNING: The Internal Pressure Shut Off
Switches do not prevent tank overfill. If your system
shuts off on high pressure and is connected to your
tank, you may have overfilled your tank and created
a very dangerous situation! Take immediate measures to relieve any high pressure and/or tank overfill.
11. When recovering large amounts of liquid, use the
"Push/Pull method (see diagram on page 13).
m CAUTION: When using the "Push/Pull" method,
once the "Push/Pull" siphon is started, it can continue and overfill the storage tank even if the tank is
equipped with a "shut off" float sensor. The siphon
can continue even after the machine is turned off.
You must manually close the valves on the tank and
the unit to prevent overfilling of the recovery tank.
12. Always operate the unit on a flat level surface.
13. To achieve the deepest final vacuum, use the
tank cooling method to lower the head pressure
on the recovery tank. (See Pages 13 & 14).
Repeat as necessary to achieve the desired
vacuum level.
5
Page 6
OPERATING GUIDELINES - cont.
NOTE: If there is no liquid in the recovery tank, then
the cooling method will not work. In this case, use an
empty tank that has been fully evacuated to achieve
the final vacuum level required.
14. If the tank pressure exceeds 300 psi, use the tank
cooling procedure to reduce the tank pressure.
(See Pages 13 & 14)
CARE AND MAINTENANCE OF YOUR RG5410A
1. USE of a filter/dryer at the inlet is mandatory. A fil-
ter/dryer must always be used between the recovery machine and the inlet hose.
2. Special care should be taken when recovering
from a "burned-out" system. Use two high acid
capacity filters, in series. (Alco type EK-162-F or
Sporlan type C-162-F are recommended )When
you have finished recovering from the system,
flush your RG5410A with a small amount of
clean refrigerant and refrigerant oil to purge off
any foreign substances left in the unit.
3. Always empty refrigerant from the RG5410A
into a storage tank; see Self-Purge/Auto Evacuate
15.To maximize recovery rates, use the shortest
possible length of 3/8" or larger hose.
A hose no longer than 3 feet is recom-
mended.
16.For maximum throughput, always remove all
unnecessary hose core depressors and the
Schrader valves from port connections.
17.Deformed rubber seals and core depressors in
hoses and faulty or unnecessary Schrader
valves can restrict flow up to 90%.
procedure on Page 12. Liquid refrigerant left in
theRG5410A’s condenser may expand,causing
damage to components.
4. c Warning! Whenever you perform any type of
maintenance work on your RG5410A, insure
that it is disconnected from the power supply
before you begin.
5. If the unit is to be stored or not used for any
length of time, we recommend that it be complenty evacuated of any residual refrigerant and
purged with dry nitrogen.
6
Page 7
ADDITIONAL RECOVERY TANK INFORMATION
m Warning: Also read the information pertain-
ing to recovery tanks, previously listed under
Safety Information and Operating Guidelines.
1. CAUTION: NEVER use a standard disposable
30 lb. (the type of container in which virgin refrigerant is sold) to recover refrigerant.
Use ONLY authorized refillable refrigerant tanks.
Federal regulations require refrigerant to be trans
ported only in containers meeting DOT specs.
4BW or 4BA.
2.m Warning: DO NOT: Exceed the working pres-
sure of each cylinder. Recovery cylinders are
designed for different pressures. Your RG5410A
is not supplied with a recovery tank, it requires the
use of tanks with a minimum of 350 psi
working pressure and PROMAX strongly recom-mends the use of 400 psi tanks.
NOTE: The use of a 400 psi tank is mandatory
when recovering R-410A.
See PROMAX Recovery Tanks under Parts and
Accessories section on Page 16.
tank, evacuate it and purge the tank using dry
nitrogen, and then re-evacuate it.
3. Always store refrigerant containers in a cool dry
place.
5. Do not mix refrigerants in a system, a tank or any
where else. Each type of refrigerant must have its
own tank, filter, etc.
6. Storage cylinders sometimes have valves that are
not properly seated when manufactured. Keeping
caps on these valves will guard against refrigerant
leakage.
7. Do not exceed 80% of tank capacity. PROMAX
strongly recommends the use of the Promax ADS100 Refrigerant Scale for monitoring tank capacity.
Safety codes recommend that closed tanks not be
filled over 80% of volume with liquid. The remaining 20% is called head pressure room.
8. If you expect temperatures in excess of 135º F
contact the refrigerant supplier.
3. Tanks and filters should be designated for one
refrigerant only. Before using a tank previously
used for another refrigerant, completely empty the
m NEVER TRANSPORT AN OVERFILLED CYLINDER m
Refrigerant expands when it gets warm and may cause a tank to explode if overfilled.
CYLINDER TEMPERATURE60°F70°F100°F130°F150°F
STARTING WITH CYLINDER
80% BY VOLUME
SPACE OCCUPIED BY LIQUID80%81%83%90%94%
STARTING WITH CYLINDER
90% BY VOLUME
SPACE OCCUPIED BY LIQUID90%92%96%100%
7
Page 8
PURGING NON-CONDENSABLE GASES
FROM REFRIGERANT TANK
1. Allow the tank to sit undisturbed for 24 hours. This
allows the air to rise to the top.
2. Connect a manifold to the tank and read the
amount of pressure in the tank by looking at the
output pressure gauge.
3. Determine the ambient temperature in the room.
4. Refer to a Refrigerant pressure/temperature chart.
Find the temperature on the chart and look across
to the corresponding pressure for the type of
refrigerant in the tank. Determine how that relates
to the reading on the gauge.
5. If the pressure reading is higher than the pressure
shown on the chart, very slowly (so as not to
cause turbulence inside the tank) crack open the
vapor port valve. Watch the pressure on the
gauge decrease. To prevent venting, add 4-5 psi
to the pressure shown on the chart.
when the gauge corresponds to that pressure,
close the vapor port valve.
6. Allow the tank to sit for 10 minutes and check the
pressure again.
7. Repeat the process again if necessary.
8
Page 9
HELPFUL HINTS FOR
REFRIGERANT RECOVERY
Refrigerant recovery has come a long way in a few short years. On the surface it's simply the process of taking refrigerant out of a system and putting it into a tank. However, this simple process can quickly become problematic if a few
items are overlooked. The following are some tips and pointers we've accumulated over the last few years that can save
you time and make the process go smoother.
First you need to identify the refrigerant type and quantity in the system you are servicing. If you determine it’s a
burnout, you need a special tank (a tank that's identified as containing burnout or other unidentified gases), and you
need to use extra filtration prior to recovery. (See item #2 on page 6)
If, on the other hand, you know the gas in the system is relatively clean or new, then a new tank should be used. If
you're planning on putting the refrigerant back into the same system after you have finished the service or if the refrigerant is going to be reclaimed, then use a tank that has the same refrigerant in it. A word of caution about the
Environmental Protection Agency (EPA): If you use a variety of refrigerant gasses in your service work - as evidenced by
your refrigerant purchases - and you only own one tank, you are asking for trouble. You would be well advised to own at
least one tank for every refrigerant type serviced, plus an extra for burnouts and other unknowns.
Results of Liquid Refrigerant
PLANNING AHEAD
Knowing the quantity of refrigerant is important for planning storage requirements, as well as planning for the
actual recovery. For instance, any system with more than
5lbs. of refrigerant is likely to have areas where the liquid
can get trapped.
The key to a quick recovery procedure is to get the liquid
out first, and then get the remaining vapor out. However
most systems are not "recovery friendly." That is they
don't have access ports at their lowest points. If some
units you're servicing are on maintenance contracts, you
would save significant time by installing access ports at all
of the lowest points in the system, where liquid is likely to
accumulate.
Since most systems don't have these ports you need to
be prepared to boil off the trapped liquid with a heat gun,
when ever it's found. An indicator of trapped liquid in a
system is frost or condensation forming on the plumbing
or components where the liquid is trapped. The trapped
liquid may be in an area that is not visible. In all cases
trapped liquid in a system during recovery causes the
recovery process to slow down, regardless of the size or
type of machine (see diagram).
If you are unable to locate the trapped liquid, but you
know it's there, because the recovery job is taking "forev -er". Turn on the system compressor (if it's operable) for a
few seconds, this will get the refrigerant moving to another part of the system and in the process pick up enough
heat to boil off.
Pstart
Pe
10” Hg
HOSES AND VALVES
Hoses and Schraeder valves have a large impact on recovery speed. In general, the larger the hose, the less friction
on the flow of refrigerant, the quicker the recovery time.
Many contractors are now using 3/8' lines for the input to
the recovery machine, even those lines originating out of
1/4" fittings.
Schraeder valves must be removed from the connection
prior to an expedient recovery. Most wholesalers sell a
tool for removing these cores, while keeping the connection sealed. The core depressor, in the end of the hose,
should also be removed. These two items can turn a 20
minute job into one that goes on for hours. So, be sure to
remove the Schraeder valves and core depressors before
every recovery job.
Another hose consideration is the little rubber grommet at
the end of the hose that makes a seal with the flare fitting.
We've seen these seals so worn and deformed that when
the hose is connected to the flare fitting the grommet virtually seals off the connection.
Trapped in a System
Forever
0
TstartTimeTfinish
9
Page 10
HELPFUL HINTS FOR
REFRIGERANT RECOVERY - cont.
This is probably never noticed in charging, because the
pressure opens the grommet, but during recovery (or with
suction) the deformed grommet severely restricts the flow
of refrigerant.
REFRIGERANT RECYCLING
Current regulations state that used refrigerant shall not be
sold, or used in a different owner's equipment, unless the
refrigerant has been laboratory analyzed and found to meet
the requirements of ARI 700 (latest edition). As a result,
recycling and verifying ARI 700 conformance isn't economically justified in most cases. It's still a great idea to do as
much cleaning of refrigerant going back into the same system (or owners system) as possible. We recommend using
the largest, high-acid capacity filter, that are economically
feasible. Put these filters on the suction or inlet side of the
recovery unit. Change filters often.
The recovery of large amounts of liquid refrigerant can
sometimes carry with it large quantities of oil, if the system
being serviced doesn't have an adequate oil separator
installed. If this recovered refrigerant isn't going to be liquid
charged back into the same system, you might want to separate the refrigerant from the oil in order to measure the oil
(to know how much oil to charge back into the system).
Refrigerant sent back for reclaim does not need to have the
oil removed. One of the simplest and most cost effective
ways to achieve this is to use a (30 or 50 lb.) tank in line
with your recovery machine. Connect the system to the liquid port of the tank, then from the vapor port of the tank
connect to the input of your recovery machine. A second
tank, for storing refrigerant, should then be connected to
the output of the recovery machine. If you encounter large
amounts of liquid you will need to put a band heater around
the first tank. When the recovery job is complete the oil can
be removed, from the first tank, by applying a small amount
of pressure, using nitrogen, to one of the ports and extracting the oil from the other. If you are going to remove the oil
from the vapor port you will need to turn the tank upside
down. Always wear safety glasses when performing this
operation as the oil may be acidic and could cause severe
burning.
KEEPING THE DIRT OUT
During the recovery process your recovery machine can be
exposed to debris that can, potentially, damage it. This
includes brazing spatter and copper/ brass slithers. Further
contamination can be introduced from the refrigerant storage tanks. To prolong the life of your recovery machine,
always use an inline filter at the inlet Port.
Whenever you are charging a system from a recovery cylinder it is a good idea to use an in-line filter to protect the system from contamination. Again, change your in-line filters
often.
GETTING THE LIQUID OUT
See diagram on page 13 of this manual
Push/pull is a method of removing bulk liquid from a sys-
tem using the pressure differential created by the recovery
machine. Push-pull will generally not work on smaller systems because there is no bulk liquid reservoir to create a
siphon from.
Push-pull is mostly used on systems with a receiver tank or
those with greater than 20 lbs. of refrigerant, or when transferring from one tank to another. The rate of liquid transfer
is very much dependent on hose size, with larger hoses providing much better throughput.
Another trick is to cool the tank, if it's partially filled, prior
to or during recovery. This operation will lower the pressure
in the storage tank and therefore speed up recovery. There
must be a minimum of 5 lbs of liquid refrigerant in the tank
you wish to chill. This operation can be performed prior to
or during the recovery. See the two set updiagramsand procedures on page 13-14 of this manual.
There is nothing magic here, you are simply using your
recovery machine to make a refrigerator where the tank is
the evaporator. By throttling the output valve, you're effectively creating a capillary tube or an expansion device, but
you need to adjust the back pressure to suit the conditions
and the refrigerant. Five to ten minutes of chilling can produce some very dramatic tank cooling, depending on the
conditions. If there are any non condensables in the tank
this process will not work. The greater the quantity of refrigerant in the tank the longer the process will take.
10
Page 11
OPERATING YOUR RG5410A
PROCEDURE FOR NORMAL SYSTEM RECOVERY
1. Inspect the RG5410A thoroughly to insure that
it is in good operating condition.
2. Make sure all connections are correct and tight
(see set-up diagram below).
3. Open the liquid port of the recovery cylinder
(always open valves slowly to check hoses and
connections for leaks).
4. Make sure the Recover/Purge valve is set on
Recover.
5. Open the output port of the RG5410A.
6. Open the liquid port on your manifold gauge set;
opening the liquid port will remove the liquid from
the system first, greatly reducing the recovery
time. (after the liquid has been removed, open
the manifold vapor port to finish evacuating the
system).
7. Connect your RG5410A to a 115V outlet.
a. Switch the main power switch to the ON position.
You should hear the fan running.
b. Press the compressor start switch. This “momen-
tary” switch will start the compressor. It may be
necessary, under certain circumstances, to press
thisswitchmore than once tostart thecompressor.
8. Slowly open the input port on the RG5410A.
a. If the compressor starts to knock, slowly
throttle back the input valve until the knock-
ing stops.
b. If the input valve was throttled back, it should
be fully opened once the liquid has been
removed from the system (the manifold gauge
set vapor port should also be opened at this
time).
9. Run until desired vacuum is achieved.
a. Close the manifold gauge sets vapor and
liquid ports.
b. Close the RG5410A-E input port.
c. Shut off and proceed with the Self Purge
procedure on the next page.
Note: Always purge the RG5410A after each
use (see Self Purge procedure on page 12).
Failure to purge the remaining refrigerant from
theRG5410A could result in the acidic degradation
of internal components, ultimately causing
premature failure of the unit.
10. High Pressure Select (R410A) Switch:
When the High Pressure Select (R410A) Switch
is in the on position, the unit will shut off at 550
PSI. In the off position it will shut of at 400 PSI.
DIAGRAM FOR REFRIGERATION RECOVER Y
THIS IS THE FASTEST METHOD FOR RECOVERING VAPOR REFRIGERANT
RECOVER
PURGE
OUT
SYSTEM BEING
SERVICED
A SCALE MUST BE USED TO AVOID
OVER FILLING THE STORAGE TANK
m
OPTIONALMOISTURE
SIGHTGLASS
MANIFOLD
GAUGE
SET
VAPOR
LIQUID
INPUT
OUTPUT
LIQUID
11
First turn knob to liquid
port. When liquid is
removed, move to full
open for vapor
IN
CLOSED
Page 12
SELF PURGING YOUR RG5410A
PROCEDURE FOR PURGING REMAINING REFRIGERANT FROM THE RG5410A
1. Close the ports of the system being serviced that
are connected to the input port of the RG5410A.
2. Close the input port on the RG5410A.
3. Turn off the RG5410A.
4. Turn the Recover/Purge valve to the Purge position.
5. Restart the RG5410A.
6. Run until desired vacuum is achieved.
SELF PURGE / AUTO EVACUATE
To change from Recovery mode to Purge follow the steps below:
1. Close the Input port
7. Close the ports on the recovery tank and the
RG5410A.
8. Turn the RG5410A off.
9. Return the Recover/Purge valve to the Recover
position.
10.Disconnect and store all hoses.
11.Replace the in-line filter on your RG5410A
after every job.
2. Turn the unit off (to prevent high pressure shutoff).
3. Switch to Purge position.
4. Restart the unit.
RECOVER
IN
CLOSED
PURGE
OUT
12
Page 13
DIAGRAM FOR “PUSH/PULL” METHOD
Push/pull method only works with large systems where the liquid is readily accessible. Do not use this
method on systems that contain less than 15 lbs. as it may not work.
The sight glass is used to provide a method of determining the moisture content and quality of a system’s
refrigerant.
m CAUTION: When using the “Push/Pull” method, once the siphon is started, it can continue and overfill
the storage tank even if the tank is equipped with a float level sensor. The siphon can continue even when
the machine is turned off. You must manually close the valves on the tank and the unit to prevent overfilling of the recovery tank.
1. Close INPUT and OUTPUT valves
2. Put RECOVER/PURGE knob on RECOVER
3. Start machine
4. Open INPUT and OUPUT valves
5. When the scale stops rising close all ports
CAUTION: Do not overfill tank
6. Switch off the machine
SET-UP DIAGRAM FOR TANK
PRE OR SUB COOLING PROCEDURE
INPUT
OUTPUT
VAPOR
INPUT
SYSTEM BEING
S E RV I C E D
m A scale must be used to avoid over filling
the storage tank.
See page 10 of this manual for more information.
1. To start you must have a minimum of
5 lbs.of liquid refrigerant in the tank
2. Close INPUT and OUTPUT valves
3. Put RECOVER/PURGE knob on RECOVER
4. Start machine
5. Open INPUT valve to liquid
6. Throttle the output valve so that the output pres-
sure is 100 psi greater than the input pressure,
but never more than 300psi
7. Run until tank is cold
VAPOR
LIQUID
OPTIONAL MOISTURE
SIGHT GLASS
OUTPUT
LIQUID
LIQUID
13
Page 14
OPTIONAL RECOVERY/TANK PRE OR SUB
COOLING FOR FIXED HOSE SET-UP
MANIFOLD
GAUGE
SET
SYSTEM BEING
SERVICED
INPUT
OUTPUT
LIQUID
VAPOR
LIQUID
m A scale must be used to avoid over filling the storage tank.
NORMAL RECOVERY:
Tank Vapor valve is closed
TANK PRE OR SUB COOLING:
Tank Vapor valve is open and both manifold gauge set valves are closed.
14
Page 15
REFRIGERANT FLOW DIAGRAM
15
Page 16
23
RG5410A DIAGRAM
1
2
3
4
ITEM DESCRIPTION PA RT #
1 PLASTIC CASE 100134 (L&R)
2 FAN GRILL 100505
3AXIAL FAN EL1817
4 CONDENSER CD1201
5 MOTOREL1821
6COUPLER CP1315
7 BELL HOUSING CP1001
8 COMPRESSOR CP1320
9 PRESSURE SWEL2800
24
5
6
7
25
11
10
22
18
9
26
27
8
19
20
RG5410A PARTS LIST
ITEM DESCRIPTION PA RT #
10 INPUT GAUGE GA1500
11 OUTPUT GAUGE GA0800
12 GAUGE LENS GA1000
13 ON/OFF SWITCH EL1310
14 START SWITCH EL1309
15 BLUE KNOB 100123
16 RED KNOB 100124
17 BLACK KNOB 100122
1 8 FRONT PANEL 100137
IITEM DESCRIPTION PA RT#
19 FILTER100343
20 FLARE CAP NB6501
21 CORD SET 100162
22 HIGH PRESSURE SW EL2802
23 BACK PLATE 100318
24 CAPACITOR EL1412
25 COMPRESSOR BRACKET 100351
26 MANIFOLD 700133
27 HOSE 4” 100345
21
15
16
12
14
13
17
REPLACEMENT KITS & ACCESSORIES
PART#DESCRIPTION
KT3302 PISTON SEAL REPLACEMENT (middle section of compressor)
KT3303 VALVE REPLACEMENT KIT (top section of compressor)
KT3307 COMPRESSOR REPAIR KIT (all three sections of compressor)
KT3308 SHAFT REPLACEMENT KIT (bottom section of compressor)
KT5001 80% CAPACITY TANK SENSING KIT
RGT30 30 LB RECOVERY TANK (350 psi working pressure) with capacity sensor
RGT30NS SAME AS RGT30, WITHOUT SENSOR
RGT50 50 LB RECOVERY TANK (350 psi working pressure) with capacity sensor
RGT50NS SAME AS RGT50, WITHOUT SENSOR
RGT50HP 50 LB RECOVERY TANK, HIGH PRESSURE(400 psi working pressure) with capacity sensor
ADS-100 REFRIGERANT SCALE, 200LB CAPACITY, WITH REMOVABLE PLATFORM
16
Page 17
RG5410A WIRING DIAGRAM
17
Page 18
INSTALLATION OF OPTIONAL 80% TANK
CAPACITY SENSING COMPONENTS (KIT:KT5001)
Note: PROMAX also offers the model, RG5410A-KT,
with the 80% Capacity Shut Off Kit installed at the
factory.
c Warning: Prior to performing any type of mainte-
nance work on your RG5410A, insure that it is disconnected from the power supply before you begin.
NOTE: Refer to the wiring diagram on page 17
during installation of your kit.
1. Disconnect your RG5410A from the power source
2. Remove the fasteners from each side of the
RG5410A and separate both halves of the plastic
case.
3. Place the metal frame of the RG5410A in the
upright position
4. Remove the "pry out plug" from the hole located
at the lower right of the front panel, and pass the
tank sensor cord (p/n EL1420) through it.
5. Visually identify the two studs located on the
base, directly behind the lower front panel. (this
will be the location for the relay, p/n EL1500,
all your electrical connections are made.)
6. Disconnect a red wire from the high-pressure
switch (located under the start switch) Note:
There are two red wires on the high-pressure
switch, disconnect the one that originates from the
Power Switch.
7. Ensure that the terminal multiplier (p/n EL1221) is
placed on terminal #4 of the relay and then place
the red wire removed from the high pressure
switch on that terminal.
8. Place the black wire from the sensor cord on the
other side of the terminal multiplier, on the same
terminal #4 of the relay.
after
Note: Ensure that the green wire from the sensor
cord is connected to the center of the 3-pin connector. (Note: only two wires are used in this connector).
11. Connect the 3-pin connector to its female counterpart, already pre wired on your RG5410A.
Note: make sure the two wires, (1) green and (1)
white, are in the proper position (directly across)
from their mating wires.
12. Connect one end of the red wire (p/n WR1403),
supplied with your kit, to terminal #2 of the relay
and the other end to the high pressure switch.
13. Secure the relay onto the two studs mentioned in
Step 5, using the hardware already installed on
the studs.
14. Secure the tank sensor into the hole in the front
panel with the strain relief grommet provided.
15. Secure any loose wiring with the wire ties provided.
16. Replace the plastic case halves and fasteners.
17. Test the installation by momentarily attempting
to start the RG5410A without thesensor cord
connectedtoatank sensor.The unit’s compressor
should not start up. Turn the RG5410Aoff and
reattempt to start the unit with the sensor cord
connected to a tank with a tank capacity sensor.
The unit should function normally. Disconnecting
the sensor cord while the unit is running should
cause the unit to shut down.
18. If your unit does not function per above,
DISCONNECT the RG5410A from the Power
Supply, and re-check your connections per the
above steps and the wiring diagram on page 17.
9. Place the white wire from the sensor cord on
terminal #0 of the relay.
10. Connect the white wire from the male side of the
3 pin connector (p/n EL1215) to terminal #1 of
the relay.
18
Page 19
TROUBLESHOOTING YOUR RG5410A
CONNECT UNIT
TO 115V
SAFETY FIRST
Read and understand all safety information contained
in this manual before servicing the unit.
FAN IS RUNNING
WHEN POWER SWITCH
IS IN “ON” POSITION
YES
COMPRESSOR STARTS
WHEN START SWITCH
IS PRESSED
YES
UNIT PUMPS INTO
HIGH PRESSURE SHUT
OFF
YESYESYES
NONO
NONO
NONONO
CHECK POWER
SUPPLY
YES
IS UNIT IN HIGH
PRESSURE
SHUT OFF?
YES
ARE VALVES OPEN?
CHECK
FOR SCHRADER
VALVES
DO YOU
HAVE 115V
YES
IS THE TANK
CORD ATTACHED
TO THE TANK
YES
DOES TANK FLOAT
SWITCH WORK
PROPERLY?
UNIT PULLS
INTO A VACUUM
YES
ARE YOUR
HOSES TIGHT?
DOES UNIT PULL A
VACUUM WHEN INPUT
VALVE IS CLOSED?
YES
TROUBLESHOOTING ENDS
19
NONONO
YES
Page 20
FULL ONE YEAR WARRANTY
Note: First 2 digits represent the
MFG #
Promax products are warranted to be free from defects in workmanship and materials for a period of one
year from date of purchase.
THE FOLLOWING RESTRICTIONS APPLY:
1. The warranty applies to products in normal use only, as described in the operating manual. The product
must also be serviced and maintained as described therein.
2. If the product fails, it will be replaced at the option of Advanced Test Products, Inc. (ATP)
3. Warranty service claims are subject to factory inspection for product defect(s). If during the warranty evaluation it is determined that a filter has not been used or that the filter was not properly maintained or that
the machine has been used in any way other than the purpose for which it was designed, ATP, reserves
the right to void the warranty.
4. All warranty claims must be made within the warranty period. Proof of purchase must be supplied .
This warranty is non-transferable.
5. Please note that the warranty does not apply if the product or product part is damaged by accident, misuse, tampered with or modified in any way.
year and the 3
rd
digit the quarter
6. Normal wear items (seals, filters, etc.) are specifically excluded from warranty, unless found by Promax
to be defective.
WARRANTY SERVICE
This warranty is given by ADVANCED TEST PRODUCTS, INC.
Service under this warranty must be obtained by the following steps:
1. Outside the U.S.A. contact your local Promax Distributor.
2. Inside the U.S.A. call 1.800.327.5060 or 954-499-5400
for a return material authorization (RMA) number.
20
Page 21
THE UNITED STATES ENVIRONMENTAL PROTECTION
AGENCY (EPA) REFRIGERANT RECOVERY AND RECYCLING DEVICE
ACQUISITION CERTIFICATION FORM
EPA regulations have required establishments that service or dispose of refrigerant or air conditioning
equipment to certify that they have acquired recovery and recycling devices that meet the EPA standards
for such devices since August 12. 1993. To certify that you have acquired equipment, please complete this
form according to the instructions and mail it to the appropriate EPA Regional Office. BOTH THE
INSTRUCTIONS AND MAILING ADDRESS CAN BE FOUND ON THE NEXT PAGE OF THIS MANUAL.
Part 1: ESTABLISHMENT INFORMATION
Name of Establishment
Street
City
Zip Code
StateCounty
(Area Code)
Telephone Number
Name of Establishment
Street
City
Zip Code
UNIT STORAGE ADDRESS
NUMBER OF SERVICE VEHICLES BASED AT ESTABLISHMENT
Part 2: REGULATORY CLASSIFICATION
Identify the type of work performed at your establishment. Check all boxes that apply.
Type A - Service small appliances.
Type B - Service refrigeration or air conditioning equipment other than small appliances.
Type C - Dispose of small appliances
Type D - Dispose of refrigeration or air conditioning equipment other than small appliances.
Part 3: DEVICE IDENTIFICATION
Name of Device Manufacturer
Model #
Month/Year
Mfg# (if any)
StateCounty
(Area Code)
Telephone Number
Self Contained
Part 4: SIGNATURE
I certify that the establishment named in part 1. has acquired the refrigerant recovery or recycling
devices listed in part 3. and that this equipment will be properly used in service (and/or) disposing
of appliances. I also certify that the information supplied herein is correct and true.
Signature of owner / Responsible Officer
Public reporting burden for this collection of information is estimated to vary from 20-60 minutes per response with an average of 40
minutes per response including time for reviewing instructions, searching existing data sources, gathering and maintaining the data
needed and completing the collection of information. Send comments regarding the burden estimate or any other aspect of this collection of information, including suggestions for reducing the burden to: Chief information Policy Branch EPA, 401 M St. S.W. (PM223Y),
Washington, DC 20460 and to the Office of information and Regulatory A ffairs, Office of Management and Budget, Washington, DC
20503 marked Attention, Desk Officer for EPA .
DO NOT SEND THIS FORM TO THE ABOVE ADDRESSES. ONLY SEND COMMENTS TO THESE ADDRESSES
DateName (please print)Title
21
Page 22
INSTRUCTIONS EPA REGIONAL OFFICES
Part 1. Please provide the name, address and telephone
number of the establishment where the refrigerant recovery or recycling device(s) is (are) located. Please complete one form for each location. State the number of
vehicles based at this location that are used to transport
technicians and equipment to and from service sites.
Part 2. Check the appropriate box for the type of work
performed by technicians who are employees of the
establishment. The term "small appliance" refers to any of
the following products that are fully manufactured,
charged and hermetically sealed in a factory with five or
less pounds of refrigerant:
Refrigerators or freezers designed for home use, room air
conditioners (including window air conditioners and packaged thermal air conditioners), packaged thermal heat
pumps, dehumidifiers, under-the-counter ice makers,
vending machines and drinking water coolers.
Part 3. For each recovery or recycling device acquired,
please list the name of the manufacturer of the device
and (if applicable) its model number and manufacturer
number. If more than 8 devices have been acquired
please fill out an additional form and attach it to the first
one.
Recovery devices that are self-contained should be listed
first and should be identified by checking the box in the
last column on the right. Aself-contained device is one
that uses it's own pump or compressor to remove refrigerant from refrigeration or air conditioning equipment. On
the other hand, system dependent recovery devices rely
solely upon the compressor in the refrigeration or air conditioning equipment and/or upon the pressure of the
refrigerant inside the equipment to remove the refrigerant.
If the establishment has been listed as Type B and/or
Type D in Part 2, then the first device listed in Part 3 must
be a self-contained device and identified as such by
checking the box in the last column on the right.
If any of the devices are homemade, they should be identified by writing "homemade" in the column provided for
listing the name of the device manufacturer. Homemade
devices can be certified for establishments that are listed
as Type A or Type B in Part 2 until (six months after promulgation of the rule). If a Type C or Type D establishment
is certifying equipment after (six months after promulgation of the rule), then it must not use these devices for
service jobs classified as Type A or Type B.
Part 4. This form must be signed by either the owner of
the establishment or another responsible officer. The person who signs is certifying that the establishment has
acquired the equipment, that the establishment is complying with Section 608 regulations and that the information
provided is true and correct.
Send your form to the EPA office listed under the state or
territory in which your establishment is located.
CONNECTICUT, MAINE, MASSACHUSETTS, NEW
HAMPSHIRE, RHODE ISLAND, VERMONT
CAA 608 Enforcement Contact: EPA Region 1.
Mail Code APC, One Congress Street, John F. Kennedy
Federal Building, Boston, MA 02203-0001
Phone: (617) 565-3420
NEW YORK,NEW JERSEY, PUERTO RICO,VIRGIN
ISLANDS CAA 608 Enforcement Contact: EPA Region 2.
290 Broadway, New York, NY 10007-1866
Phone: (212) 637-3000
DELAWARE, DISTRICT OF COLOMBIA, MARYLAND,
PENNSYLVANIA,VIRGINIA,WEST VIRGINIA
CAA 608Enforcement Contact: EPA Region 3. Mail Code
3AT21, 1650 Arch Street, Philadelphia, PA 19103-2029
Phone: (215) 566-5000
ALABAMA, FLORIDA, GEORGIA, KENTUCKY, MISSISSIPPI, NORTH CAROLINA, SOUTH CAROLINA,TENNESSEE
CAA 608 Enforcement Contact: EPA Region 4. Mail Code
APT-AE, 100 Alabama Street, SW, Atlanta, GA 30303
Phone: (404) 562-8357