TIF MINIMAX-KT User Manual

MINIMAX
REFRIGERANT RECOVERY SYSTEM
USER’S OPERATING MANUAL
Telephone: (954) 499-5400 • Fax: (954) 499-5454 • Toll Free: (800) 327-5060
ADVANCED TEST PRODUCTS. INC • Miramar, FL
www.amprobe.com
TABLE OF CONTENTS
CARE AND MAINTENANCE OF YOUR MINIMAX 6 ADDITIONAL RECOVERY TANK INFORMATION 7
PURGING NON-CONDENSABLE GASES 8
HELPFUL HINTS FOR REFRIGERANT RECOVERY 9-10
OPERATING YOUR MINIMAX 11
DIAGRAM FOR REFRIGERANT RECOVERY 11 SELF PURGING YOUR MINIMAX 12 SELF PURGE/AUTO EVACUATE 12 DIAGRAM FOR “PUSH/PULL” METHOD 13
SET-UP DIAGRAM FOR TANK PRE OR SUB COOLING PROCEDURE 13 OPTIONAL RECOVERY / TANK PRE OR SUB 14
COOLING FOR FIXED HOSE SET-UP REFRIGERANT FLOW DIAGRAM 15
MINIMAX PARTS DIAGRAM/PARTS AND ACCESSORIES LIST 16 MINIMAX AND MINIMAX-KT WIRING DIAGRAMS 17
INSTALLATION OF OPTIONAL80% TANK 18 CAPACITYSENSING COMPONENTS (KIT KT-5001)
MINIMAX-KT MODEL 18 TROUBLESHOOTING YOUR MINIMAX 19 FULL ONE YEAR WARRANTY 20 ENVIRONMENTALPROTECTION AGENCY (EPA) INSTRUCTIONS 21
EPA REGIONAL OFFICES 22
3
m IMPORTANT SAFETY INFORMATION m
SAFETY COMES FIRST! Read all safety, operating guidelines and instructions before operating your Minimax.
1. CAUTION: ONLY A QUALIFIED TECHNICIAN SHOULD OPERATE THIS RECOVERY UNIT.
The operator must be familiar with air conditioning
and refrigeration systems, refrigerants and the dangers of pressurized components.
2. Always think before acting, familiarity breeds care-
lessness and carelessness can be harmful to your
health or, worse, result in death.
3. m WARNING Always wear safety goggles and protective gloves when working with refrigerants. Contact with refrigerant may cause injury. Disconnect hoses with extreme caution! All hoses may contain liquid refrigerant under pressure.
4. m PRESSURIZED TANK CONTAINS LIQUID REFRIGERANT. NEVER OVERFILLSTORAGE TANKS. OVERFILLING OF THE TANK MAY
CAUSE AVIOLENT EXPLOSIONAND POSSIBLE INJURY OR DEATH.DO NOT: Exceed theworking
pressure of Recovery Tank cylinder.
5.m Warning: DO NOT: Exceed the working pres-
sure of each cylinder. Recovery cylinders are designed for different pressures. Your MINIMAX is not supplied with a recovery tank, it requires the use of tanks with a minimum of 350 psi working pressure and PROMAX strongly recommends the use of 400 psi tanks.
NOTE: The use of a 400 psi tank is mandatory when recovering R-410A. See PROMAX Recovery Tanks under Parts and Accessories section on Page 16.
5. m A scale must be used to avoid overfilling the storage tank. DO NOT OVERFILL. Tank is full at
80% volume. Tank may explode if filled more than
80% due to liquid expansion.
7.Read all safety information regarding the safe handling of refrigerant and refrigerant oil, includ- ing the Material Safety Data Sheet. MSDS sheets can be obtained from your refrigerant supplier.
8. If you expect temperatures in excess of 135° F, contact the refrigerant supplier.
9. Be sure that any room where you are working is thoroughly ventilated, especially if a leak is sus pected. Refrigerant vapor is hazardous to your health and can cause death.
10. m Avoid breathingA/C refrigerant and lubrica-
tion vapor or mist. Exposure may irritate eyes, nose and throat. If accidental system discharge occurs,ventilateworkareabefore resumingserv­ice.
11. iWARNING:TOREDUCE THE RISKOFFIRE:
• Never operate unit in an explosiveenvironment!
Do not use this equipment in the vicinity of
spilled or open containers of gasoline or any
other flammable liquid.
• When using an extension cord it should be a
3-wire, 14 AWG minimum and no longer than 25
feet.
• Use this equipment in locations with mechani-
cal ventilation that provides at least four air
changes per hour or locate the equipment at
least 18 inches above the floor.
• Never use oxygen when testing for leaks. Any
oil in contact with oxygen under pressure will
form an explosive mixture.
12. c High voltage electricity inside panels. Risk of electrical shock. Be sure to disconnect
theunitfrom thepowersourcebeforeservicing it.
13. To reduce the risk of injury, care should be taken when moving this equipment.
6. Use ONLY authorized refillable refrigerant tanks. NEVER use a standard disposable 30lb. tank (the
type of container in which virgin refrigerant is sold) to recover refrigerant.
4
OPERATING GUIDELINES
m Before operating the Minimax recovery unit, read
the following m
1. MINIMAX IS APPROVED FOR USE WITH THE
FOLLOWING CATEGORY III, IV and V REFRIG­ERANTS (Per ARI 740):
R-12, R-22, R-134A, R-401A, R-401B, R-401C, R-402A,R-402-B,R-404A,R-406A,R-407A,R-407-B, R-407C, R-407D, R-408A, R-409A, R-410A,R-411A, R-411B, R-412A, R-500, R-502, R-507 and R-509
2. A FILTER must always be used and should
replaced frequently. We recommend that a clean filter be used for every service job. Failure to use a filter will invalidate your warranty.
The use of a filter will greatly reduce the risk of damage to your Minimax, by preventing foreign material from entering the unit.
2. Each filter should be labeled and used exclusively
for one type of refrigerant only.
3. Always open service and cylinder valves slowly.
This allows rapid control of the flow of gases if there is any danger. Once it is determined that there is no danger, the valves can be opened fully.
NEVER use a standarddisposable30lb.tank (the typeofcontainer in which virgin refrigerant is sold) to recover refrigerant.
9. m A scale must be used to avoid overfilling the storage tank. DO NOT OVERFILL. Tank is full at
80% volume. Tank may explode if filled more than 80%duetoliquid expansion. Below is a represen-
tative sample for R-22 refrigerant:
TANK SIZE MAX NET WEIGHT
30 lb. Tank 24 lbs. 50 lb. Tank 40 lbs.
Note: Promax strongly recommends the use of the ADS-100 Refrigerant Scale for monitoring tank
capacity.
10. Your Minimax has an Internal Pressure Shut Off
Switch. If the pressure inside the system should go above 550 psi, the system will automatically
shut itself off. Theshutoffswitch will automatically
reset itself again after the pressure drops below 300 psi.
4. Always isolate large amounts of refrigerant and close off valves after use, so if a leak should develop anywhere in the system, the refrigerant will not escape.
5. Always isolate large amounts of refrigerant and close off valves after use, so if a leak should develop anywhere in the system, the refrigerant will not escape.
6. Keep all connections to the refrigeration system thoroughly dry and clean. If moisture enters the refrigeration system, it is likely to cause consider­able damage.
7. Promax strongly recommends the use of the optional 80% Capacity Shutoff Kit (p/n KT-5001). When installed and used with a recovery tank that has an internal float switch, the Minimax will shut
down automatically when the tank is 80% full. Your
Minimax is pre-wired from the factory for this kit.
N o t e : The Minimax is also available in model Minimax-KT, with the 80% Shutoff Kit installed direct from the factory.
8. m CAUTION: Use only authorized refillable refrigerant recovery tanks. Federal regulations require refrigerant to be transported only in con­tainers meeting DOT spec. 4BA or 4BW.
m WARNING: The Internal Pressure Shut Off
Switch does not prevent tank overfill. If your system shuts off on high pressure and is connected to your tank, you may have overfilled your tank and created a very dangerous situation! Take immediate meas­ures to relieve any high pressure and/or tank overfill.
11. When recovering large amounts of liquid, use the "Push/Pull method (see diagram on page 13).
m CAUTION: When using the "Push/Pull" method,
once the "Push/Pull" siphon is started, it can contin­ue and overfill the storage tank even if the tank is equipped with a "shut off" float sensor. The siphon can continue even after the machine is turned off. You must manually close the valves on the tank and the unit to prevent overfilling of the recovery tank.
12. Always operate the unit on a flat level surface
13. To achieve the deepest final vacuum, use the tank cooling method to lower the head pressure on the recovery tank. (See Pages 13 &14). Repeat as necessary to achieve the desired vac­uum level.
5
OPERATING GUIDELINES - cont.
NOTE: If there is no liquid in the recovery tank, then the cooling method will not work. In this case, use an empty tank that has been fully evacuated to achieve the final vacuum level required.
14. If the tank pressure exceeds 300 psi, use the tank cooling procedure to reduce the tank pressure. (See Pages 13 & 14)
CARE AND MAINTENANCE OF YOUR MINIMAX
1. USE of a filter/dryer at the inlet is mandatory. A fil-
ter/dryer must always be used between the recov­ery machine and the inlet hose.
2. Special care should be taken when recovering
from a "burned-out" system. Use two high acid capacity filters, in series. (Alco type EK-162-F or Sporlan type C-162-F are recommended )When you have finished recovering from the system, flush your Minimax with a small amount of clean refrigerant and refrigerant oil to purge off any for­eign substances left in the unit.
3. Always empty refrigerant from the MINIMAX into a
storage tank; see Self-Purge/Auto Evacuate pro-
15.To maximize recovery rates, use the shortest possible length of 3/8" or larger hose. Ahose no longer than 3 feet is recommended.
16.For maximum throughput, always remove all unnecessary hose core depressors and the Schrader valves from port connections.
17.Deformed rubber seals and core depressors in hoses and faulty or unnecessary Schrader valves can restrict flow up to 90%.
cedure on Page 12. Liquid refrigerant left in the MINIMAX’s condenser may expand, causing dam­age to components.
4. c Warning! Whenever you perform any type of
maintenance work on your Minimax, insure that it is disconnected from the power supply before you begin.
5. If the unit is to be stored or not used for any length of time, we recommend that it be com­pletely evacuated of any residual refrigerant and purged with dry nitrogen.
6
ADDITIONAL RECOVERY TANK INFORMATION
m Warning: Also read the information pertain-
ing to recovery tanks, previously listed under Safety Information and Operating Guidelines.
1. CAUTION: NEVER use a standard disposable 30lb. tank (the type of container in which virgin refrigerant is sold) to recover refrigerant. Use ONLY authorized refillable refrigerant tanks. Federal regulations require refrigerant to be trans ported only in containers meeting DOT specs. 4BW or 4BA.
2.m Warning: DO NOT: Exceed the working pres-
sure of each cylinder. Recovery cylinders are designed for different pressures. Your MINIMAX is not supplied with a recovery tank, it requires the use of tanks with a minimum of 350 psi working pressure and PROMAX strongly recommends the
use of 400 psi tanks. NOTE: The use of a 400 psi tank is mandatory when recovering R-410A. See PROMAX Recovery Tanks under Parts and Accessories section on Page 16.
3. Tanks and filters should be designated for one
refrigerant only. Before using a tank previously
used for another refrigerant, completely empty the
tank, evacuate it and purge the tank using dry nitrogen, and then re-evacuate it.
3. Always store refrigerant containers in a cool dry place.
5. Do not mix refrigerants in a system, a tank or any where else. Each type of refrigerant must have its own tank, filter, etc.
6. Storage cylinders sometimes have valves that are not properly seated when manufactured. Keeping caps on these valves will guard against refrigerant leakage.
7. Do not exceed 80% of tank capacity. PROMAX strongly recommends the use of the Promax ADS­100 Refrigerant Scale for monitoring tank capacity. Safety codes recommend that closed tanks not be filled over 80% of volume with liquid. The remain­ing 20% is called head pressure room.
8. If you expect temperatures in excess of 135° F, contact the refrigerant supplier.
m NEVER TRANSPORT AN OVERFILLED CYLINDER m
Refrigerant expands when it gets warm and may cause a tank to explode if overfilled.
CYLINDER TEMPERATURE 60°F 70°F 100°F 130°F 150°F
STARTING WITH CYLINDER
80% BY VOLUME
SPACE OCCUPIED BY LIQUID 80% 81% 83% 90% 94%
STARTING WITH CYLINDER
90% BY VOLUME
SPACE OCCUPIED BY LIQUID 90% 92% 96% 100%
7
PURGING NON-CONDENSABLE GASES
FROM REFRIGERANT TANK
1. Allow the tank to sit undisturbed for 24 hours. This allows the air to rise to the top.
2. Connect a manifold to the tank and read the amount of pressure in the tank by looking at the output pressure gauge.
3. Determine the ambient temperature in the room.
4. Refer to a Refrigerant pressure/temperature chart. Find the temperature on the chart and look across to the corresponding pressure for the type of refrigerant in the tank. Determine how that
5. If the pressure reading is higher than the pressure shown on the chart, very slowly (so as not to cause turbulence inside the tank) crack open the vapor port valve. Watch the pressure on the gauge decrease. To prevent venting, add 4-5 psi to the pressure shown on the chart. when the gauge corresponds to that pressure, close the vapor port valve.
6. Allow the tank to sit for 10 minutes and check the pressure again.
7. Repeat the process again if necessary.
8
HELPFUL HINTS FOR
REFRIGERANT RECOVERY
Refrigerant recovery has come a long way in a few short years. On the surface it's simply the process of taking refriger­ant out of a system and putting it into a tank. However, this simple process can quickly become problematic if a few items are overlooked. The following are some tips and pointers we've accumulated over the last few years that can save you time and make the process go smoother.
First you need to identify the refrigerant type and quantity in the system you are servicing. If you determine it"s a burnout, you need a special tank (a tank that's identified as containing burnout or other unidentified gases), and you need to use extra filtration prior to recovery. (See item #2 on page 6)
If, on the other hand, you know the gas in the system is relatively clean or new, then a new tank should be used. If you're planning on putting the refrigerant back into the same system after you have finished the service or if the refrig­erant is going to be reclaimed, then use a tank that has the same refrigerant in it. A word of caution about the Environmental Protection Agency (EPA): If you use a variety of refrigerant gasses in your service work - as evidenced by your refrigerant purchases - and you only own one tank, you are asking for trouble. You would be well advised to own at least one tank for every refrigerant type serviced, plus an extra for burnouts and other unknowns.
Results of Liquid Refrigerant
PLANNING AHEAD
Knowing the quantity of refrigerant is important for plan­ning storage requirements, as well as planning for the actual recovery. For instance, any system with more than 5lbs. of refrigerant is likely to have areas where the liquid can get trapped.
The key to a quick recovery procedure is to get the liquid out first, and then get the remaining vapor out. However most systems are not "recovery friendly." That is they don't have access ports at their lowest points. If some units you're servicing are on maintenance contracts, you would save significant time by installing access ports at all of the lowest points in the system, where liquid is likely to accumulate.
Since most systems don't have these ports you need to be prepared to boil off the trapped liquid with a heat gun, when ever it's found. An indicator of trapped liquid in a system is frost or condensation forming on the plumbing or components where the liquid is trapped. The trapped liquid may be in an area that is not visible. In all cases trapped liquid in a system during recovery causes the recovery process to slow down, regardless of the size or type of machine (see diagram).
If you are unable to locate the trapped liquid, but you know it'sthere,becausetherecoveryjobistaking "forever". Turn on the system compressor (if it's operable) for a few seconds, this will get the refrigerant moving to another part of the system and in the process pick up enough heat to boil off.
Pstart
Pe
10” Hg
HOSES AND VALVES
Hoses and Schraeder valves have a large impact on recov­ery speed. In general, the larger the hose, the less friction on the flow of refrigerant, the quicker the recovery time. Many contractors are now using 3/8' lines for the input to the recovery machine, even those lines originating out of 1/4" fittings.
Schraeder valves must be removed from the connection prior to an expedient recovery. Most wholesalers sell a tool for removing these cores, while keeping the connection sealed. The core depressor, in the end of the hose, should also be removed. These two items can turn a 20 minute job into one that goes on for hours. So, be sure to remove the Schraeder valves and core depressors before every recovery job.
Another hose consideration is the little rubber grommet at the end of the hose that makes a seal with the flare fitting. We've seen these seals so worn and deformed that when the hose is connected to the flare fitting the grommet vir­tually seals off the connection.
Trapped in a System
Forever
0
Tstart Time Tfinish
9
HELPFUL HINTS FOR
REFRIGERANT RECOVERY - cont.
This is probably never noticed in charging, because the pressure opens the grommet, but during recovery (or with suction) the deformed grommet severely restricts the flow of refrigerant.
REFRIGERANT RECYCLING
Current regulations state that used refrigerant shall not be sold, or used in a different owner's equipment, unless the refrigerant has been laboratory analyzed and found to meet the requirements of ARI 700 (latest edition). As a result, recycling and verifying ARI 700 conformance isn't economically justified in most cases. It's still a great idea to do as much cleaning of refrigerant going back into the same system (or owners system) as possible. We recom­mend using the largest, high-acid capacity filter, that are economically feasible. Put these filters on the suction or inlet side of the recovery unit. Change filters often.
The recovery of large amounts of liquid refrigerant can sometimes carry with it large quantities of oil, if the sys­tem being serviced doesn't have an adequate oil separator installed. If this recovered refrigerant isn't going to be liq­uid charged back into the same system, you might want to separate the refrigerant from the oil in order to measure the oil (to know how much oil to charge back into the sys­tem). Refrigerant sent back for reclaim does not need to have the oil removed. One of the simplest and most cost effective ways to achieve this is to use a 30 or 50 lb. tank in line with your recovery machine. Connect the system to the liquid port of the tank, then from the vapor port of the tank connect to the input of your recovery machine. A sec­ond tank, for storing refrigerant, should then be connected to the output of the recovery machine. If you encounter large amounts of liquid you will need to put a band heater around the first tank. When the recovery job is complete the oil can be removed, from the first tank, by applying a small amount of pressure, using nitrogen, to one of the ports and extracting the oil from the other. If you are going to remove the oil from the vapor port you will need to turn the tank upside down. Always wear safety glasses when performing this operation as the oil may be acidic and could cause severe burning.
KEEPING THE DIRT OUT
During the recovery process your recovery machine can be exposed to debris that can, potentially, damage it. This includes brazing spatter and copper/ brass slithers. Further contamination can be introduced from the refrigerant stor­age tanks. To prolong the life of your recovery machine,
always use an inline filter at the inlet Port.
Whenever you are charging a system from a recovery cylinder it is a good idea to use an in-line filter to protect the system from contamination. Again, change your in-line filters often.
GETTING THE LIQUID OUT
See diagram on page 13 of this manual Push/pull is a method of removing bulk liquid from a sys-
tem using the pressure differential created by the recovery machine. Push-pull will generally not work on smaller sys­tems because there is no bulk liquid reservoir to create a siphon from.
Push-pull is mostly used on systems with a receiver tank or those with greater than 20 lbs. of refrigerant, or when transferring from one tank to another. The rate of liquid transfer is very much dependent on hose size, with larger hoses providing much better throughput.
Another trick is to cool the tank, if it's partially filled, prior to or during recovery. This operation will lower the pres­sure in the storage tank and therefore speed up recovery. There must be a minimum of 5 lbs of liquid refrigerant in the tank you wish to chill. This operation can be performed prior to or during the recovery. See the two set up dia­grams and procedures on page 13-14 of this manual.
There is nothing magic here, you are simply using your recovery machine to make a refrigerator where the tank is the evaporator. By throttling the output valve, you're effec­tively creating a capillary tube or an expansion device, but you need to adjust the back pressure to suit the conditions and the refrigerant. Five to ten minutes of chilling can pro­duce some very dramatic tank cooling, depending on the conditions. If there are any non condensables in the tank this process will not work. The greater the quantity of refrigerant in the tank the longer the process will take.
10
OPERATING YOUR MINIMAX
PROCEDURE FOR NORMAL SYSTEM RECOVERY
1. Inspect the Minimax thoroughly to insure that it is in good operating condition.
2. Make sure all connections are correct and tight (see set-up diagram below).
3. Open the liquid port of the recovery cylinder (always open valves slowly to check hoses and connections for leaks).
4. Make sure the Recover/Purge valve is set on Recover.
5. Open the output port of the Minimax
6. Open the liquid port on your manifold gauge set; opening the liquid port will remove the liquid from the system first, greatly reducing the recovery time. (after the liquid has been removed, open the manifold vapor port to finish evacuating the system).
7. Connect your Minimax to a 115V outlet.
a. Switch the main power switch to the ON position.
You should hear the fan running.
b. Press the compressor start switch. This “momen-
tary” switch will start the compressor. It may be
necessary, under certain circumstances, to press this switch more than once to start the compres­sor.
8. Slowly open the input port on the Minimax. a. If the compressor starts to knock, slowly throttle
back the input valve until the knocking stops.
b. If the input valve was throttled back, it should be
fully opened once the liquid has been removed from the system (the manifold gauge set vapor port should also be opened at this time).
9. Run until desired vacuum is achieved. a. Close the manifold gauge sets vapor and liquid
ports. b. Close the Minimax input port. c. Shut off and proceed with the Self Purge
procedure on the next page. Note: Always purge the Minimax after each use (see
Self Purge procedure on page 12). Failure to purge the remaining refrigerant from the Minimax could result in the acidic degradation of internal compo­nents, ultimately causing premature failure of the unit.
DIAGRAM FOR REFRIGERATION RECOVER Y
THIS IS THE FASTEST METHOD FOR RECOVERING VAPOR REFRIGERANT
OPTIONALMOISTURE
SIGHTGLASS
MANIFOLD
GAUGE
SET
SYSTEM BEING
SERVICED
LIQUID
A SCALE MUST BE USED TO AVOID OVER FILLING THE STORAGE TANK
m
INPUT
OUTPUT
VAPOR LIQUID
11
First turn knob to liquid port. When liquid is removed, move to full open for vapor
SELF PURGING YOUR MINIMAX
PROCEDURE FOR PURGING REMAINING REFRIGERANT FROM THE MINIMAX
1. Close the ports of the system being serviced that are connected to the input port of the Minimax.
2. Close the input port on the Minimax.
3. Turn off the Minimax.
4. Turn the Recover/Purge valve to the Purge posi­tion.
5. Restart the Minimax.
6. Run until desired vacuum is achieved.
SELF PURGE/ AUTO EVACUATE
To change from Recovery mode to Purge follow the steps below:
1. Close the Input port
7. Close the ports on the recovery tank and the Minimax.
8. Turn the Minimax off.
9. Return the Recover/Purge valve to the Recover position.
10.Disconnect and store all hoses.
11.Replace the in-line filter on your Minimax after every job.
2. Turn the unit off (to prevent high pressure shutoff).
3. Switch to Purge position.
4. Restart the unit.
12
DIAGRAM FOR “PUSH/PULL” METHOD
Push/pull method only works with large systems where the liquid is readily accessible. Do not use this method on systems that contain less than 15 lbs. as it may not work.
The sight glass is used to provide a method of determining the moisture content and quality of a system’s refrigerant.
m CAUTION: When using the “Push/Pull” method, once the siphon is started, it can continue and overfill
the storage tank even if the tank is equipped with a float level sensor. The siphon can continue even when the machine is turned off. You must manually close the valves on the tank and the unit to prevent overfill­ing of the recovery tank.
VAPOR
SYSTEM BEING
S E RV I C E D
LIQUID
m A scale must be used to avoid over filling
the storage tank.
OPTIONAL MOISTURE
SIGHT GLASS
INPUT
OUTPUT
LIQUID
SET-UP DIAGRAM FOR TANK
PRE OR SUB COOLING PROCEDURE
See page 10 of this manual for more information.
INPUT
1. To start you must have a minimum of 5 lbs. of liquid refrigerant in the tank.
VAPOR
OUTPUT
LIQUID
2. Throttle the output valve so that the output pres­sure is 100 psi greater than the input pressure, but never more than 300psi.
3. Run until the tank is cold.
13
OPTIONAL RECOVERY/TANK PRE OR SUB
COOLING FOR FIXED HOSE SET-UP
m A scale must be used to avoid over filling the storage tank.
NORMAL RECOVERY:
Tank Vapor valve is closed
TANK PRE OR SUB COOLING:
Tank Vapor valve is open and both manifold gauge set valves are closed.
14
REFRIGERANT FLOW DIAGRAM
15
MINIMAX PARTS DIAGRAM
29
26
25
2
3
4
5
6
27
1
13
14
15
23
28
12
7
22
8
9
10
11
30
16
17
18
19
20
21
24
MINIMAX PARTS LIST
ITEM DESCRIPTION PA RT #
1 PLASTIC CASE ( 1 0 0 11 8 )
2 FAN GRILL, OUTLET ( 1 0 0 1 7 9 ) 3 A X I A LFAN ( 1 0 0 11 9 ) 4 C O N D E N S E R ( 1 0 0 1 3 9 ) 5 C O M P R E S S O R ( C P 1 3 2 0 ) 6 COMPRESSOR BRACKET ( 1 0 0 2 0 7 ) 7 C O U P L E R ( C P 1 3 1 5 ) 8 B E L LHOUSING ( C P 1 0 0 1 ) 9 M O TOR BRACKET ( 1 0 0 2 0 9 )
1 0 M O TOR ( E L 1 8 2 1 )
*OPTIONAL COMPONENTS FOR 80% CAPACITY TANK SENSING KIT
11 FRONTPA N E L ( 1 0 0 1 2 1 ) 12 MANIFOLD ( 7 0 0 0 0 9 )
13 I N P U TGAUGE ( G A 1 5 0 0 ) 14 O U T P U T GAUGE ( G A 0 8 0 0 )
1 5 GAUGE LENS ( G A 1 0 0 0 )
16 ON/OFF SWITCH ( E L 1 3 1 0 )
1 7 S TA RTSWITCH ( E L 1 3 0 9 ) 1 8 RED KNOB ( 1 0 0 1 2 4 ) 19 BLACK KNOB ( 1 0 0 1 2 2 ) 2 0 BLUE KNOB ( 1 0 0 1 2 3 ) 2 1 FLARE CAP ( N B 6 5 0 1 )
2 2 F I LT E R ( 1 0 0 3 4 3 ) 2 3 * R E L AY ( E L 1 5 0 0 ) 2 4 *SENSOR CORD ( E L 1 4 2 0 ) 2 5 C A PA C I TOR ( E L 1 4 1 2 ) 2 6 REAR PA N E L ( 1 0 0 2 2 1 )
2 7 CORD SET ( 1 0 0 1 6 2 ) 28 PRESSURE SWITCH( E L 2 8 0 2 ) 29 FA NGRILL, INLET ( 1 0 0 1 8 0 )
30 H O S EA S S Y ( 1 0 0 3 4 5 )
REPLACEMENT KITS & ACCESSORIES
PART# DESCRIPTION
KT3302 PISTON SEAL REPLACEMENT (middle section of compressor) KT3303 VALVE REPLACEMENT KIT (top section of compressor) KT3307 COMPRESSOR REPAIR KIT (all three sections of compressor) KT3308 SHAFT REPLACEMENT KIT (bottom section of compressor) KT5001 80% CAPACITY TANK SENSING KIT RGT30 30 LB RECOVERY TANK (350 psi working pressure) with capacity sensor RGT30NS SAME AS RGT30, WITHOUT SENSOR RGT50 50 LB RECOVERY TANK (350 psi working pressure) with capacity sensor RGT50NS SAME AS RGT50, WITHOUT SENSOR RGT50HP 50 LB RECOVERY TANK, HIGH PRESSURE(400 psi working pressure) with capacity sensor ADS-100 REFRIGERANT SCALE, 200LB CAPACITY, WITH REMOVABLE PLATFORM
16
MINIMAX WIRING DIAGRAM
MINIMAX-KT WIRING DIAGRAM
INCLUDING OPTIONAL TANK CAPACITY SENSING CIRCUITRY (KIT:KT5001)
17
INSTALLATION OF OPTIONAL 80% TANK
CAPACITY SENSING COMPONENTS (KIT:KT5001)
Note: PROMAX also offers the model, Minimax-KT, with the 80% Capacity Shut Off Kit installed at the factory.
c Warning: Prior to performing any type of mainte-
nance work on your Minimax, insure that it is discon­nected from the power supply before you begin.
NOTE: Refer to the wiring diagram at the bottom of page 17 during installation of your kit.
1. Disconnect your Minimax from the power source
2. Remove the fasteners from each side of the Minimax and separate both halves of the plastic case.
Note: You may find it more convenient to disconnect the two wires to the fan, if so remember to reconnect them prior to re-installing the case.
3. Place the metal frame of the Minimax in the upright position
4. Remove the "pry out plug" from the hole located at the lower right of the front panel, and pass the tank sensor cord (p/n EL1420) through it.
5. Visually identify the two studs located on the base, directly behind the lower front panel. (this will be the location for the relay, p/n EL1500, all your electrical connections are made.)
6. Disconnect a red wire from the high-pressure switch (located under the start switch) Note: There are two red wires on the high-pressure switch, disconnect the one that originates from the Power Switch.
7. Ensure that the terminal multiplier (p/n EL1221) is placed on terminal #4 of the relay and then place the red wire removed from the high pressure switch on that terminal.
8. Place the black wire from the sensor cord on the other side of the terminal multiplier, on the same terminal #4 of the relay.
after
10. Connect the white wire from the male side of the 3 pin connector (p/n EL1215) to terminal #1 of the relay.
Note: Ensure that the green wire from the sensor cord is connected to the center of the 3-pin connec­tor. (Note: only two wires are used in this connector).
11. Connect the 3-pin connector to its female coun-
terpart, already pre wired on your Minimax.
Note: make sure the two wires, (1) green and (1) white, are in the proper position (directly across) from their mating wires.
12. Connect one end of the red wire (p/n WR1403), supplied with your kit, to terminal #2 of the relay and the other end to the high pressure switch.
13. Secure the relay onto the two studs mentioned in
Step 5, using the hardware already installed on
the studs.
14. Secure the tank sensor into the hole in the front
panel with the strain relief grommet provided.
15. Replace the fan wires, if removed in step # 2.
16. Secure any loose wiring with the wire ties pro-
vided.
17. Replace the plastic case halves and fasteners.
18. Test the installation by momentarily attempting
to start the Minimax without the sensor cord con- nected to a tank sensor. The unit’s compressor should not start up. Turn the Minimax off and re­attempt to start the unit with the sensor cord con nected to a tank with a tank capacity sensor. The unit should function normally. Disconnecting the sensor cord while the unit is running should cause the unit to shut down.
19. If your unit does not function per above, DIS-
CONNECT the Minimax from the Power Supply, and re-check your connections per the above steps and the wiring diagram at the bottom of page 17.
9. Place the white wire from the sensor cord on terminal #0 of the relay.
MINIMAX-KT MODEL
PROMAX offers the model, Minimax-KT, with the 80% Capacity Shut Off Kit (p/n KT-5001) installed at the factory. On this model, when used with a recovery tank that has an internal float switch, the recovery unit will automatically shut off when the recovery tank is 80% full.
18
TROUBLESHOOTING YOUR MINIMAX
Read and understand all safety information contained
CONNECT UNIT TO
115V OUTLET
SAFETY FIRST
in this manual before servicing the unit.
FAN IS RUNNING
WHEN POWER SWITCH
IS IN “ON” POSITION
YES
COMPRESSOR STARTS
WHEN START SWITCH
IS PRESSED
YES
UNIT PUMPS INTO
HIGH PRESSURE SHUT
OFF
YES YES YES
NO NO
NO NO
NO NO NO
CHECK POWER
SUPPLY
YES
IS UNIT IN HIGH
PRESSURE SHUT OFF?
YES
ARE VALVES OPEN?
CHECK
FOR SCHRADER
VALVES
DO YOU HAVE 115V SUPPLY?
YES
IS THE TANK
CORD ATTACHED
TO THE TANK
YES
DOES TANK FLOAT
SWITCH WORK
PROPERLY?
UNIT PULLS
INTO A VACUUM
YES
ARE YOUR HOSES
TIGHT? DO YOU
HAVE LEAKS?
DOES UNIT PULL A
VACUUM WHEN INPUT
VALVE IS CLOSED?
TROUBLESHOOTING ENDS
19
NONONO
FULL ONE YEAR WARRANTY
MFG #
Promax products are warranted to be free from defects in workmanship and materials for a period of one year from date of purchase.
THE FOLLOWING RESTRICTIONS APPLY:
1. The warranty applies to products in normal use only, as described in the operating manual. The product must also be serviced and maintained as described therein.
2. If the product fails, it will be replaced at the option of Advanced Test Products, Inc. (ATP)
3. Warranty service claims are subject to factory inspection for product defect(s). If during the warranty eval­uation it is determined that a filter has not been used or that the filter was not properly maintained or that the machine has been used in any way other than the purpose for which it was designed, ATP, reserves the right to void the warranty.
4. All warranty claims must be made within the warranty period. Proof of purchase must be supplied . This warranty is non-transferable.
5. Please note that the warranty does not apply if the product or product part is damaged by accident, mis­use, tampered with or modified in any way.
6. Normal wear items (seals, filters, etc.) are specifically excluded from warranty, unless found by Promax to be defective.
WARRANTY SERVICE
This warranty is given by ADVANCED TEST PRODUCTS, INC. Service under this warranty must be obtained by the following steps:
1. Outside the U.S.A. contact your local Promax Distributor.
2. Inside the U.S.A. call 1.800.327.5060 or 954-499-5400 for a return material authorization (RMA) number.
20
THE UNITED STATES ENVIRONMENTAL PROTECTION
AGENCY (EPA) REFRIGERANT RECOVERY AND RECYCLING DEVICE
ACQUISITION CERTIFICATION FORM
EPAregulations have required establishments that service or dispose of refrigerant or air conditioning equipment to certify that they have acquired recovery and recycling devices that meet the EPA standards for such devices since August 12. 1993. To certify that you have acquired equipment, please complete this form according to the instructions and mail it to the appropriate EPA Regional Office. BOTH THE INSTRUCTIONS AND MAILING ADDRESS CAN BE FOUND ON THE NEXT PAGE OF THIS MANUAL.
Part 1: ESTABLISHMENT INFORMATION
Name of Establishment
Street
City
Zip Code
State County
(Area Code)
Telephone Number
Name of Establishment
Street
City
Zip Code
UNIT STORAGE ADDRESS
NUMBER OF SERVICE VEHICLES BASED ATESTABLISHMENT
Part 2: REGULATORY CLASSIFICATION
Identify the type of work performed at your establishment. Check all boxes that apply.
Type A - Service small appliances. Type B - Service refrigeration or air conditioning equipment other than small appliances. Type C - Dispose of small appliances Type D - Dispose of refrigeration or air conditioning equipment other than small appliances.
Part 3: DEVICE IDENTIFICATION
Name of Device Manufacturer
Model #
Month/Year
Mfg# (if any)
State County
(Area Code)
Telephone Number
Self Contained
Part 4: SIGNATURE
I certify that the establishment named in part 1. has acquired the refrigerant recovery or recycling devices listed in part 3. and that this equipment will be properly used in service (and/or) disposing of appliances. I also certify that the information supplied herein is correct and true.
Signature of owner / Responsible Officer
Public reporting burden for this collection of information is estimated to vary from 20-60 minutes per response with an average of 40 minutes per response including time for reviewing instructions, searching existing data sources, gathering and maintaining the data needed and completing the collection of information. Send comments regarding the burden estimate or any other aspect of this collec­tion of information, including suggestions for reducing the burden to: Chief information Policy Branch EPA, 401 M St. S.W. (PM223Y), Washington, DC 20460 and to the Office of information and Regulatory A ffairs, Office of Management and Budget, Washington, DC 20503 marked Attention, Desk Officer for EP A .
DO NOT SEND THIS FORM TO THE ABOVE ADDRESSES. ONLY SEND COMMENTS TO THESE ADDRESSES
Date Name (please print) Title
21
INSTRUCTIONS EPA REGIONAL OFFICES
Part 1. Please provide the name, address and telephone number of the establishment where the refrigerant recov­ery or recycling device(s) is (are) located. Please com­plete one form for each location. State the number of vehicles based at this location that are used to transport technicians and equipment to and from service sites.
Part 2. Check the appropriate box for the type of work performed by technicians who are employees of the establishment. The term "small appliance" refers to any of the following products that are fully manufactured, charged and hermetically sealed in a factory with five or less pounds of refrigerant:
Refrigerators or freezers designed for home use, room air conditioners (including window air conditioners and pack­aged thermal air conditioners), packaged thermal heat pumps, dehumidifiers, under-the-counter ice makers, vending machines and drinking water coolers.
Part 3. For each recovery or recycling device acquired, please list the name of the manufacturer of the device and (if applicable) its model number and manufacturer number. If more than 8 devices have been acquired please fill out an additional form and attach it to the first one.
Recovery devices that are self-contained should be listed first and should be identified by checking the box in the last column on the right. Aself-contained device is one that uses it's own pump or compressor to remove refriger­ant from refrigeration or air conditioning equipment. On the other hand, system dependent recovery devices rely solely upon the compressor in the refrigeration or air con­ditioning equipment and/or upon the pressure of the refrigerant inside the equipment to remove the refrigerant.
If the establishment has been listed as Type B and/or Type D in Part 2, then the first device listed in Part 3 must be a self-contained device and identified as such by checking the box in the last column on the right.
If any of the devices are homemade, they should be iden­tified by writing "homemade" in the column provided for listing the name of the device manufacturer. Homemade devices can be certified for establishments that are listed as Type A or Type B in Part 2 until (six months after prom­ulgation of the rule). If a Type C or Type D establishment is certifying equipment after (six months after promulga­tion of the rule), then it must not use these devices for service jobs classified as Type A or Type B.
Part 4. This form must be signed by either the owner of the establishment or another responsible officer. The per­son who signs is certifying that the establishment has acquired the equipment, that the establishment is comply­ing with Section 608 regulations and that the information provided is true and correct.
Send your form to the EPA office listed under the state or territory in which your establishment is located.
CONNECTICUT, MAINE, MASSACHUSETTS, NEW HAMPSHIRE, RHODE ISLAND,VERMONT
CAA 608 Enforcement Contact: EPA Region 1. Mail Code APC, One Congress Street, John F. Kennedy Federal Building, Boston, MA 02203-0001 Phone: (617) 565-3420
NEW YORK, NEW JERSEY, PUERTO RICO,VIRGIN ISLANDS CAA 608 Enforcement Contact: EPA Region 2.
290 Broadway, New York, NY 10007-1866 Phone: (212) 637-3000
DELAWARE, DISTRICT OF COLOMBIA, MARYLAND, PENNSYLVANIA,VIRGINIA,WEST VIRGINIA
CAA 608Enforcement Contact: EPARegion 3. Mail Code 3AT21, 1650 Arch Street, Philadelphia, PA19103-2029 Phone: (215) 566-5000
ALABAMA, FLORIDA, GEORGIA,KENTUCKY, MISSIS­SIPPI, NORTH CAROLINA, SOUTH CAROLINA,TEN­NESSEE
CAA 608 Enforcement Contact: EPA Region 4. Mail Code APT-AE, 100 Alabama Street, SW, Atlanta, GA 30303 Phone: (404) 562-8357
ILLINOIS, INDIANA, MICHIGAN, MINNESOTA, OHIO, WISCONSIN
CAA 608 Enforcement Contact: EPA Region 5. Mail Code AT18J, 77 West Jackson Blvd., Chicago, IL60604-3507 Phone: (312) 353-2000
ARKANSAS, LOUISIANA, NEW MEXICO, OKLAHOMA, TEXAS
CAA 608 Enforcement Contact: EPA Region 6. Mail Code 6T-EC, Fountain Place, 12th Floor, Suite 1200 1445 Ross Avenue, Dallas, TX 75202-2733 Phone: (214) 665-6444
IOWA, KANSAS, MISSOURI, NEBRASKA
CAA 608 Enforcement Contact: EPA Region 7. Mail Code ARTX/ARBR, 901 N. 5th Street, Kansas City, KS 66101 Phone: (800) 223-0425
COLORADO, MONTANA, NORTH DAKOTA, SOUTH DAKOTA, UTAH,WYOMING
CAA 608Enforcement Contact: EPARegion 8. Mail Code 8AT-AP, 999 18th Street, Suite 500 Denver, CO 80202-2466 Phone: (303) 312-6312
AMERICA SAMOA, ARIZONA, CALIFORNIA, GUAM, HAWAII, NEVADA
CAA 608 Enforcement Contact: EPA Region 9. Mail Code A-3, 75 Hawthorne Street, San Francisco, CA 94105 Phone: (415) 744-1305
ALASKA, IDAHO, OREGON, WASHINGTON
CAA 608Enforcement contact: EPA Region 10. Mail Code AT-082, 1200 Sixth Ave. Seattle, WA 98101 Phone: (206) 553-1200
22
ADVANCED TEST PRODUCTS. INC • Miramar, FL
Telephone: (954) 499-5400 • Fax: (954) 499-5454
Toll Free: (800) 327-5060
www.PromaxRecovery.com
Designed & Engineered in the USA
Manufactured in China
PN/ 100116 Rev.B
Loading...