Thorn SensaLite SLOCS, 96239753, SensaLite SLOCSP, 96239752 Installation And Commissioning Instructions

Installation and Commissioning
Instructions
SensaLite PIR Detector for Batten-style Luminaires
SENSALITE SLOCS - Switching
SENSALITE SLOCSP - Switching with photocell
SENSALITE SLOCS (96239752) SENSALITE SLOCSP (96239753)
If there is insufficient space for the locknut, the adaptor shown below (Fig. 3) can be used.
Fig. 3
Fig. 1
Fig. 2
SENSALINK SLOCS - Switching SENSALINK SLOCSP - Switching with photocell
Only suitably qualified personnel should install this equipment.
This passive infrared presence detector is designed to be fitted to a batten-style luminaire.
Installation
1. Remove the M20 knockout from the end cap of the luminaire.
2. Pass the sensor wires through from the outside and insert the threaded end of the sensor into the hole.
3. A polarising plate can be made in order to prevent rotation of the sensor - an example design is given below (Fig. 4).
4. If a polarising plate is to be used, pass the wires through the slot and position the polarising plate against the inside face of the end cap. Ensure that the tab is positioned correctly i.e. at the ceiling side, away from the lamp.
5. Fit and tighten the locknut.
6. Connect the wires in accordance with the wiring instructions.
Polarising Plate (not supplied)
The purpose of the polarising plate is to ensure that the sensor does not rotate from the correct position, i.e. pointing vertically downwards, during transport or installation.
The two overall dimensions marked ‘SEE TEXT’ need to be made such that when the plate is positioned against the inner face of the luminaire end cap, it cannot rotate.
The 3.5mm ‘tab’ should be located closest to the ceiling (away from the lamp). The 6.0mm slot is optional and is to allow the wires to pass through for ease of assembly.
Material can be plastic sheet, minimum thicknesss 1.0mm, recommended thickness 1.5-2.0mm, or mild/stainless steel sheet, minimum thickness 0.6mm, recommended thickness 1.0-1.6mm.
SEE TEXT
SEE TEXT
7.3
6.0
20
3.5
Fig. 4
- 2 -
20mm Female Adaptor MK part number EFA/2
Electrical Connections
LOAD
Blue Brown Black
Blue Brown Black
Multiple Detectors may be connected in parallel, as is shown above, to control the same Maximum Load
L N E
SUPPLY
Maximum Total Load not to exceed that specified for a Single Detector
LOAD
LOAD
L N E
Fig. 6
W5023A
L N E L N E
Always check product label before connecting.
Black
Blue
Brown - Live
- Neutral
- Switched live
Fig. 5
- 3 -
Loading...
+ 5 hidden pages