Thomas Scientific 5300A20/F48025-TS, 5300A25/F48025-80-TS Operation Manual And Parts List

Muffle Furnace
OPERATION MANUAL
AND PARTS LIST
Series 1285
Model Voltage Control Display
5300A20/F48025-TS 120V Single Setpoint Model °C
5300A25/F48025-80-TS 120V 8 Setpoint Programmable Model °C
with OTP
with OTP
Table of Contents
Safety Information ..............................................................................................................................................3
Alert Signals..................................................................................................................................................3
Warnings ......................................................................................................................................................3
Introduction..........................................................................................................................................................5
Intended Use ................................................................................................................................................5
General Usage..............................................................................................................................................5
Principles of Operation ................................................................................................................................5
General Specifications ........................................................................................................................................6
Models 5300A20/F48025-TS and 5300A25/F48025-80-TS ........................................................................6
Environmental Conditions ............................................................................................................................7
Unpacking ..........................................................................................................................................................8
Installation ..........................................................................................................................................................9
Site Selection................................................................................................................................................9
Electrical Connections ..................................................................................................................................9
Operation, All Models ........................................................................................................................................10
Power Switch ..............................................................................................................................................10
Cycle Light ..................................................................................................................................................10
Door Safety Switch ....................................................................................................................................10
Single Setpoint Model with OTP ......................................................................................................................11
Single Ramp & Dwell ........................................................................................................................................15
8 Segment Programmable Models with OTP....................................................................................................17
Furnace Loading ..............................................................................................................................................31
Preventative Maintenance ................................................................................................................................32
General Cleaning Instructions ....................................................................................................................32
Troubleshooting ................................................................................................................................................33
Maintenance and Servicing ..............................................................................................................................35
To Replace a Heating Element ..................................................................................................................35
To Replace a Chromel/Alumel Thermocouple ............................................................................................36
To Replace Door Switches (Micro-Switch) ................................................................................................37
To Realign Door Switches (Micro-Switch) ..................................................................................................37
To Replace the Controller ..........................................................................................................................38
Replacement Parts............................................................................................................................................39
Single Setpoint Models with OTP ..............................................................................................................39
8 Segment Programmable Models with OTP ............................................................................................39
Ordering Procedures ..................................................................................................................................39
Wiring Diagrams................................................................................................................................................40
Warranty Repair and Service ............................................................................................................................44
2
Alert Signals
Warning
Warnings alert you to a possibility of per­sonal injury.
Caution
Cautions alert you to a possibility of damage to the equipment.
Note
Notes alert you to pertinent facts and conditions.
Safety Information
This manual contains important operating and safety infor­mation. You must carefully read and understand the con­tents of this manual prior to the use of this furnace.
Your Thomas Scientific 5300A20/F48025-TS or 5300A25/F48025-80-TS Muffle Furnace has been designed with function, reliability and safety in mind. It is your responsibility to install it in conformance with local electrical codes. For safe operation, please pay attention to the alert signals throughout the manual.
Warnings
To avoid electrical shock, this furnace must:
1. Use a properly grounded electrical outlet of cor­rect voltage and current handling capacity.
2. Be disconnected from the power supply prior to maintenance and servicing.
Hot Surface
Hot surfaces alert you to a possibility of personal injury if you come in contact with a surface during use or for a period of time after use.
3. Have the door switch operating properly.
To avoid personal injury:
1. Do not use in the presence of flammable or com­bustible materials; fire or explosion may result. This device contains components which may ignite such material.
2. Caution: Hot Surface - Avoid Contact. To avoid burns, do not touch the exterior or interior sur­faces of this furnace during use or for a period of time after use.
3. Always wear safety glasses or a safety shield and high temperature gloves when loading or unload­ing the furnace. Long sleeved, fire retardant cloth­ing and a fire retardant apron is also recommend­ed.
4. Refer servicing to qualified personnel.
3
SAFETY INFORMATION
Warning
Refer servicing to qualified per­sonnel.
Warning
This warning is presented for compliance with California Proposition 65 and other regulatory agencies and only applies to the insulation in this product. This product contains refracto­ry ceramic, refractory ceramic fiber or fiberglass insulation, which can produce respirable dust or fibers during disassem­bly. Dust or fibers can cause irritation and can aggravate pre­existing respiratory diseases. Refractory ceramic and refractory ceramic fibers (after reaching 1000°C) contain crystalline silica, which can cause lung damage (silicosis). The International Agency for Research on Cancer (IARC) has classified refracto­ry ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to humans (Group 1).
The insulating materials can be located in the door, the hearth collar, in the chamber of the product or under the hot plate top. Tests performed by the manufacturer indicate that there is no risk of exposure to dust or respirable fibers resulting from oper­ation of this product under normal conditions. However, there may be a risk of exposure to respirable dust or fibers when repairing or maintaining the insulating materials, or when other­wise disturbing them in a manner which causes release of dust or fibers. By using proper handling procedures and protective equipment you can work safely with these insulating materials and minimize any exposure. Refer to the appropriate Material Safety Data Sheets (MSDS) for information regarding proper handling and recommended protective equipment. For addi­tional MSDS copies, or additional information concerning the handling of refractory ceramic products, please contact the Customer Service Department at Thomas Scientific at 1-800­345-2100.
4
Caution
Do not exceed operating temperatures shown in “General Specifications.” Exceeding these limits will result in severely reduced element life.
Introduction
Intended Use
The 5300A20/F48025-TS or 5300A25/F48025-80-TS furnace is a general purpose laboratory and heat treat­ing furnace. For optimum element life, Thomas Scientific recommends observing these temperature ranges: from 100°C (212°F) to 1093°C (2000°F) contin­uous use or from 1093°C (2000°F) to 1200C (2192°F) for intermittent use. Continuous use is operating the furnace for more than 3 hours and intermittent use is operating the furnace for less than 3 hours.
All furnaces consist of: 1) a vented heating chamber;
2) a temperature controller; and 3) a door safety switch for operator safety.
General Usage
Do not use this product for anything other than its intended usage.
Principles of Operation
The furnace chamber is heated by open coil electric resistance elements and is insulated with ceramic fiber insulation. The controller is located under the furnace chamber and is well insulated from the heat generated in the furnace chamber. A door safety switch removes power to the heating elements whenever the furnace door is opened. The temperature is controlled by one of three types of controllers.
5
General Specifications
Models 5300A20/F48025-TS and 5300A25/F48025-80-TS
Dimensions in Inches (cm):
Chamber: 7 (17.8) W x 5 (12.7) H x 10 (25.4) D Overall: 13.25 (33.7) W x 19 (48.3) H x 19.5 (49.5) D
Weight: 56 lb. (25.4 kg)
Electrical Ratings:
Volts: 120 Amps: 14.5 Watts: 1800 Frequency: 50/60 Phase: 1
Temperature:
Operating Range: 2000°F (1093°C) continuous
2192°F (1200°C) intermittent
6
GENERAL SPECIFICATIONS
Environmental Conditions
Operating: 17°C to 27°C; 20% to 80% relative humidity, non-condensing. Installation Category II
(overvoltage) in accordance with IEC 664. Pollution degree 2 in accordance with IEC 664. Altitude Limit: 2,000 meters.
Storage: -25°C to 65°C; 20% to 80% relative humidity
7
Unpacking
1. Visually check for any physical damage to the shipping container.
2. Inspect the equipment surfaces that are adjacent to any damaged area.
3. Open the furnace door and remove the packing material from inside the furnace chamber.
4. Vacuum the chamber prior to use to remove the insulation dust due to ship­ment. (The 5300A20/F48025-TS and 5300A25/F48025-80-TS furnaces are supplied with one ceramic shelf.)
5. Retain the original packaging material if reshipment is foreseen or required.
8
Caution
Be sure ambient temperature does not exceed 40°C (104°F). The recommended ambient temperature is 17°C - 27°C. Ambients above this level may result in damage to the controller.
Caution
Allow at least six inches of space between the furnace and any combustible surface. This permits the heat from the furnace case to escape so as not to cre­ate a possible fire hazard.
Installation
Site Selection
Install furnace on a sturdy surface and allow adequate space for ventilation.
Electrical Connections
The electrical ratings are located on the specification plate on the back of the furnace. Consult Thomas Scientific if your electrical service is different than those listed on the specification plate. Be sure the front power switch is in the OFF position before connecting the furnace to your electrical supply.The 5300A20/F48025-TS or 5300A25/F48025-80-TS fur­naces are supplied with a power cord rated at 120V, 15 amps.
Warning
To avoid electrical shock, this furnace must always use a properly grounded outlet of correct voltage and current han­dling capacity.
9
Operation, All Models
Warning
To avoid personal injury do not use in the presence of flammable or combustible chemicals; fire or explosion may result. This device contains components which may ignite such materials.
Hot Surface
Caution: Avoid Contact. To avoid burns, this furnace must not be touched on the exterior or interior surfaces during use or for a period of time after use.
Warning
Always wear safety glasses or a safety shield and high temperature gloves when loading or unloading the furnace. Long sleeved, fire retardant clothing and a fire retardant apron is also recommended.
Power Switch
Both the ON/OFF power switch and the digital display will illuminate when power is switched ON. The fur­nace will begin to heat to its controller's current set­point. (See the instructions for your type of controller for information on checking and setting the setpoint.)
Cycle Light
The amber cycle light will illuminate whenever the power is being applied to the heating elements. The cycle light will turn on and off as the furnace reaches the setpoint.
Door Safety Switch
The door safety switch removes power from the heat­ing elements when the door is opened. Open and close the door a few times; note that the amber CYCLE light will switch off when the door is opened. If this condition is not true, consult the Troubleshooting section before proceeding. This check must be done when the furnace is heating and the cycle light is illuminated.
Warning
To avoid electrical shock, the door safety switch must be operating properly.
10
Single Setpoint Model w/OTP
Output 1
Manual
AN
M
PAGE
Button
Single Setpoint Models
SCROLL
Button
Output 2
DOWN ARROW
Button
Temperature
Display
Display
Window
UP ARROW
Button
The single setpoint model w/ OTP furnace con­troller is a single setpoint controller which provides a single digital display to indicate the current chamber temperature or setpoint temperature. This tempera­ture controller features sensor break protection, self­tuning capability and over temperature protection (OTP) with an additional OTP relay device.
Basic Operation
When the controller is turned ON it will perform a short self-test and then display the measured value (process value) in the HOME DISPLAY.
Buttons and Indicators
OP1 (Output 1): Illuminates when the logic output is ON.
OP2 (Output 2): Illuminates when the relay output is ON (will go out during an alarm situation).
PAGE button: Allows you to select a new list of parameters.
Note
If at any time you want to return to the HOME DISPLAY, simultaneously press the PAGE and SCROLL buttons.
SCROLL button: Allows you to select a parameter within a list of parameters.
DOWN button: Allows you to decrease a value.
UP button: Allows you to increase a value.
To View or Change the Setpoint
To view the setpoint, press and release the UP or DOWN buttons. If you want to change the setpoint, continue pressing until the desired setpoint value is displayed and then release the button. A few seconds after the button is released, the controller will accept the new value and revert to the HOME DISPLAY.
11
SINGLE SETPOINT MODEL W/OTP
To View the Display Units
From the HOME DISPLAY press the SCROLL button. The display will show the temperature units in °C/F/K and then return to the HOME DISPLAY. (Call Customer Service if you require a different temperature unit.)
To View the % Output Power
From the HOME DISPLAY press the SCROLL button twice. Press and release the UP or DOWN button to view the % output power. This value is a read-only value and cannot be changed.
Controller Parameters
Home display
°C: Temperature units in Celsius. Temperature units can not be changed without entering the configuration. Contact Customer Service if a different temperature unit is required.
OP: % output power demand.
IdHi: Deviation high alarm. Factory preset to 50.
AL List (Alarm List)
IdHi: Deviation high alarm. Factory preset to 50.
3FSL: Full scale low alarm. Factory preset to -99°C.
Cannot be adjusted by end users.
Atun List (Autotune List)
tunE: One-shot autotune enable.
Pid List (Proportional, Integral, Derivative)
Pb: Proportional band (in display units). Factory preset to 5.
12
ti: Integral time in seconds. Factory preset to 0.48.
td: Derivative time in seconds. Factory preset to 0.8.
ACCS List Code: Access code (Code needed to enter or
change the other configuration parameters which are not normally accessible.) Not accessible.
SINGLE SETPOINT MODEL W/OTP
Note
The following alarm messages are fac­tory default settings and may vary if you have changed the configuration of your controller:
IDHi: = 50°C 2FSH = 1225°C
Alarms
The controller will flash an alarm message in the home display if an alarm condition is detected.
2FSH: Measured value full scale high alarm. The full scale high alarm is for furnace protection. It cannot be accessed from the user list.
IdHi: Measured value deviation high alarm. The devia­tion alarm is factory preset at 50°C. If the chamber tem­perature rises to 50°C above the setpoint temperature, this error condition will alert end users. The furnace will continue to control temperature at the alarm setpoint, which was defined as 50°C above the setpoint. End users must power off the furnace and contact Customer Service for troubleshooting assistance. Do not reset this alarm below 20°C at any time.
S.br: Sensor Break: check that sensor is connected cor­rectly.
L.br: Loop Break: check that the heating circuits are working properly.
Ld.F: Heater Circuit Fault: indication of either an open or short solid sate relay, a blown fuse, missing supply or open circuit heater.
Sensor Break Protection
This controller provides sensor break protection in the event the thermocouple opens. If an open thermocouple condition occurs, the digital display will blink “S.br” and the power to the heating element will be shut OFF (Cycle light will extinguish).
Over-Temperature Protection (OTP)
The OTP will be in effect during any alarm condition when the temperature of the furnace has deviated beyond the limit. The “Deviation High” alarm is the only alarm value which can be changed. To change it, press the SCROLL button until “IdHi” appears on the display.
13
SINGLE SETPOINT MODEL W/OTP
Note
Furnace must be at ambient temperature before starting a tune.
Press the UP or DOWN button to select the OTP value you desire. We recommend a value of 20° above your working temperature to provide protection for your workload.
In addition to over-temperature protection, units con­taining a single setpoint controller w/OTP feature a mechanical OTP relay device which disconnects power from the elements in an alarm condition (only in fur­naces with OTP relay).
Tuning
This controller incorporates a self-tuning feature which determines the optimum control parameters for the best temperature accuracy with your load and setpoint. Use this feature the first time you use your furnace and each time you change either your setpoint or the type of load you are heating. Thomas Scientific recom­mends you use this feature to provide the best temper­ature accuracy the controller can attain. To use the tun­ing feature:
1. Adjust the setpoint to your desired value.
14
Note
“Stat” and “Sp.rr” in Sp list must be set to OFF or “tunE” will not initiate.
Note
Tune has completed when “tunE” stops flashing on display.
2. Press the PAGE button until display reads, “Atun.”
3. Press the SCROLL button. Display will read, “tunE.”
4. Press the UP or DOWN button to select, “on.”
5. Simultaneously press the PAGE and SCROLL buttons to return to the HOME DIS­PLAY. The display will alternately flash between “tunE” and the HOME DISPLAY while tuning is in progress.
6. The controller will then turn the heating on and off to induce an oscillation. When the measured value reaches the required setpoint the first cycle will end.
7. Tuning will be complete after two oscillation cycles and then the tuner will turn itself off.
8. Normal control function will resume after the controller calculates tuning parameters.
Mode 1 (Opt. 1)
Single Ramp & Dwell
Functions
This type of controller has single ramp and dwell program­ming capabilities. The Ramp and Dwell can be configured to five different modes.
1. Mode 1 (Opt. 1) is a Ramp (if needed) to the Setpoint temperature, a Dwell, and then a cool down.
2. Mode 2 (Opt. 2) is the same as mode 1, except the controller continues to heat at the Setpoint after the Dwell has completed. (This mode does not cool down.)
3. Mode 3 (Opt. 3) is the same as mode 1, except the Dwell time includes the Ramp (if needed).
Mode 2 (Opt. 2)
Mode 3 (Opt. 3)
Mode 4 (Opt. 4)
4. Mode 4 (Opt. 4) is the same as mode 2, except the Dwell time includes the Ramp (if needed).
5. Mode 5 (Opt. 5) is a Dwell (delay time) before the controller Ramps (if needed) to the Setpoint tem­perature.
Program Overview
A program mode can be set by changing the “tm.OP” variable to “Opt. 1, Opt. 2, Opt. 3, Opt. 4, or Opt. 5.
A Ramp rate may be set by changing the “SPrr” variable to a value. The Ramp rate units are in degrees per minute.
The Dwell time can be set by changing the “dwEll” variable to the desired value. Dwell time units are in minutes.
The program Status can be set by changing the “StAt” variable to “run” or “oFF.” This variable will start or stop the program.
Mode 5 (Opt. 5)
15
SINGLE RAMP & DWELL
Note
The program must be stopped and the controller must be displaying the actual temperature before beginning the Setup.
Program Setup
1. Press the PAGE button until the “SP” is displayed.
2. Press the SCROLL button once, “SPrr” (Ramp Rate) will be displayed, set the desired Ramp rate with the UP or DOWN buttons, if the ramp to set­point feature is needed. If the Ramp rate is not needed, then set to “OFF” with the UP or DOWN buttons.
3. Press the SCROLL button once, “tm.OP” (Ramp & Dwell mode) will be displayed, select the desired mode with the UP or DOWN buttons. (Opt. 1, Opt. 2, Opt. 3, Opt. 4, Opt. 5)
4. Press the SCROLL button once, “dwEll” will be dis­played, set the desired Dwell time with the UP or DOWN buttons. (Dwell in minutes.)
5. Press the PAGE button until the Actual tempera­ture is displayed.
Running the Program
1. Press the SCROLL button until “StAt” is displayed, set to “run” with the UP or DOWN buttons.
2. Press the PAGE button to display Actual tempera­ture.
Stopping the Program
Press the SCROLL button until “StAt” is displayed, set to “oFF” with the UP or DOWN buttons.
Clearing the Flashing End
Press the PAGE and SCROLL buttons at the same time.
16
Verifying a Running Program
Press the SCROLL button until “StAt” is displayed. The dis­play will show “run” if the program is running, or “oFF” if it is not running. Press the PAGE button to display Actual tem­perature.
AUTO/MAN
Button
8 Segment Programmable
Model w/OTP
The 8 segment programmable controller consists of
Note
The controller will return to the HOME DISPLAY if left idle for more than a few seconds.
Note
Once the desired parameter has been selected, depressing either the UP or DOWN button will change the parameter value. In all cases, the value shown on the display is the current working value of that parameter.
Output 1
Display
Window
a microprocessor based three-mode PID (Proportional, Integral, Derivative), programmable temperature controller with over-temperature protec­tion and appropriate output switching devices to con­trol the furnace. The digital readout continuously dis­plays chamber (upper display) and setpoint (lower display) temperatures unless the SCROLL or PAGE button is depressed. The programmable controller can be used as a single setpoint controller or as a programmable controller. The 8 segment digital model enables eight segments of programming.
Basic Operation
When the controller is turned ON, it will perform a short self-test and then change to the HOME DIS­PLAY. The HOME DISPLAY shows the measured temperature (process value) in the upper display and the desired value (setpoint) in the lower display.
Upper
Display
Lower
Display
RUN/HOLD
UP ARROW
PAGE Button
8 Segment Programmable Model with OTP
SCROLL
Button
DOWN ARROW
Button
Button
Button
To Change the Setpoint
If you want to change the setpoint, press the UP or DOWN button until the desired setpoint value is dis­played in the lower display and then release the but­ton.
To View Display Units
From the HOME DISPLAY press the SCROLL button. The display will briefly show the temperature units in °C/F/K and then return to the HOME DISPLAY. (If you require a different temperature unit call Thomas Scientific Customer Service.)
To View the % Output Power
From the HOME DISPLAY press the SCROLL button twice. This value is a read-only value and cannot be changed.
17
8 SEGMENT PROGRAMMABLE MODEL W/OTP
Buttons and Indicators
OP1 (Output 1): illuminates when the heating output of the temperature controller is on.
AUTO/MAN: (Auto/Manual Mode): when the con­troller is in the automatic mode the output automatically adjusts to keep the temperature or process value at the setpoint. The “AUTO” light will illuminate. The manual mode has been disabled through factory configuration. Attempts to operate in manual mode are not recom­mended.
RUN/HOLD (Run/Hold button):
Starts a program when pressed once—RUN
light illuminates.
Holds a program when pressed again—
HOLD light illuminates.
Cancels hold and continues running when
pressed again—HOLD light is off and RUN light illuminates.
Exits a program when the button is held down
for two seconds—RUN and HOLD lights are off.
At the end of a program the RUN light will
flash.
During holdback the HOLD light will flash.
PAGE button: allows you to select a list in the user or configuration mode.
SCROLL button: allows you to select a parameter within a list in the user configuration mode.
UP button: allows you to increase the value in the lower display.
18
DOWN button: allows you to decrease the value in the lower display.
8 SEGMENT PROGRAMMABLE MODEL W/OTP
Controller Parameters
Home Display
°C: measured temperature in Celsius. Temperature units can not be changed without entering the configuration. Contact Customer Service if a different temperature unit is required.
OP: % output power demand; displayed in lower display (cannot be changed).
C.id: Controller identification number.
IdHi: Deviation High Alarm. Factory preset to 50.
tunE: One-shot autotune enable.
run LiSt (Program Run List)
PrG (Program): Currently running program (only used on 4x16 programmable models)
StAt (Status): Displays the program status [OFF, run (running active program), hoLd (program on hold), HbAc (waiting for process to catch up), End (program complet­ed)] in the lower display. The controller will default to “OFF.”
FASt (Fast): Fast run through program (no/YES). The controller will default to “no.”
SEG.d (Segment): Flash active segment type in the lower display of the home display (no/YES). The con­troller will default to “no.”
ProG LiSt (Program Edit List)
Hb (Holdback): Press the UP or DOWN ARROW to select the holdback type [OFF (disables holdback), Lo (deviation low holdback), Hi (deviation high holdback) or bAnd (deviation band holdback)] for the entire program. The controller will default to “OFF.”
Hb.U (Holdback Units): Press the UP or DOWN ARROW to select the holdback value (in display units).
19
8 SEGMENT PROGRAMMABLE MODEL W/OTP
rmP.U (Ramp Units): Press the UP or DOWN ARROW
to toggle between ramp units (SEc, min or Hour). Controller will default to “SEc.”
dwL.U (Dwell Units): Press the UP or DOWN ARROW to toggle between dwell units (SEc, min or Hour). Controller will default to “SEc.”
Cyc.n (Cycle Number): Press the UP or DOWN ARROW to set the number of program cycles (1 to 999 or cont). The controller will default to “cont.”
SEG.n (Segment Number): Press the UP or DOWN ARROW to select the segment number (1-8).
tYPE (Type of Segment): Press the UP or DOWN ARROW to select the segment type [End (end of pro­gram), rmP.r = ramp rate (ramp to a specified setpoint at a set rate), rmp.t = ramp time (ramp to a specified tem­perature in a set time), dwEll (to maintain a constant temperature for a set time), StEP (climb instantaneously from current to specified temperature). The controller will default to “End.” Other parameters used with tYPE include; tGt target setpoint), Rate (rate of temperature increase) and dur (time to target setpoint or time to dwell).
20
End.t (End Type): End segment type: dwELL (dwell con­tinuous), rSEt (reset) and S OP (End Segment Output power level.
AL LiSt (Alarm List)
IdHi: Deviation High Alarm. Factory preset to 50.
Atun LiSt (Autotune List)
tunE: One-shot autotune enable. Resets the PID values automatically.
drA: Adaptive tune enable. Monitors the process variable and resets the PID values if the process variable exceeds the trigger level.
drA.t: Adaptive tune trigger level in display units. Range = 1 9999.
8 SEGMENT PROGRAMMABLE MODEL W/OTP
Pid LiSt
G.SP (Gain Setpoint): Is the temperature at which the controller switches from the (SEt1) PID values to the (SEt 2) PID values.
Pb: Proportional band in display units. (SEt 1)
ti: Integral time in seconds. (SEt 1)
td: Derivative time in seconds. (SEt 1)
Pb2: Proportional band. (SEt 2)
ti2: Integral time in seconds. (SEt 2)
Note
The following alarm messages are factory default settings and may vary if you have changed the configuration of your controller:
IDHi: = 50°C 2FSH = 1225°C
td2: Derivative time in seconds. (SEt 2)
ACCS LiSt (Access List)
Access Code (Code needed to enter or change the other configuration parameters which are not normally accessible.) Not accessible.
Alarms
The controller will flash an alarm message in the home display if an alarm condition is detected.
IdHi: PV deviation high alarm. Factory preset at 50°C.
2FSH: PV full scale high alarm. Factory preset at 1225°C. The full scale high alarm is for furnace pro­tection. The parameter is not accessible from the user list.
S.br: Sensor break: check that sensor is connected correctly.
L.br: Loop Break: Check that the heating circuits are working properly.
21
8 SEGMENT PROGRAMMABLE MODEL W/OTP
Sensor Break Protection
This controller provides sensor break protection in the event the thermocouple opens. If an open thermocouple condition occurs, the digital display will Blink “S.br” and the power to the heating element will be shut OFF (Cycle light will extinguish).
Over-Temperature Protection (OTP)
The OTP will be in effect during any alarm condition when the temperature of the furnace has deviated beyond the limit. The “Deviation High” alarm is the only alarm value which can be changed. To change it, press the SCROLL button until “idHi” appears on the display. Press the UP or DOWN button to select the OTP value you desire. We recommend a value of 20° above your working temperature to provide protection for your work­load.
22
To Operate the Controller as a Single Setpoint Controller
1. Switch the power switch to the “ON” position. The setpoint temperature presently set in the controller will appear in the lower display. (The upper display indicates the actual chamber tem­perature.)
2. To change the setpoint, press the UP or DOWN button until the desired setpoint value is dis­played; then release the button.
3. From the home list, use the page key (press and release) to access the run list.
4. From the run list, use the scroll key (press and release) to view “StAt.” Ensure “StAt” is set to off. Use up or down arrow to select off if neces­sary.
5. The furnace will begin to heat if the new set­point temperature is higher than the present chamber temperature.
8 SEGMENT PROGRAMMABLE MODEL W/OTP
Programming the Controller
The controller is capable of varying temperature or process value with time through programming. A program is stored as a series of segments and can be run once, repeated a set number of times or run continuously. To create a cus­tomized program using the controller parameters listed under “Controller Parameters” at the beginning of this sec­tion, follow the procedures outlined in the proceeding sec­tions of this manual. All programming is accomplished in the ProG list.
Hb: Holdback
Step 1 in programming the controller is to set the holdback feature. Holdback consists of a value and a type. If the measured value lags behind the setpoint by an undesirable amount during a ramp or dwell, the holdback feature can be used to freeze the program at its current state (the HOLD light will flash). The program will resume when the meas­ured value comes within the holdback value.
Holdback can be set to 1 of 4 settings. They are as follows:
1) OFF: holdback is disabled.
2) Lo (Deviation Low Holdback): holds the program back
when process variable deviates below the setpoint by more than the holdback value.
3) Hi (Deviation High Holdback): holds the program back when process variable deviates above the setpoint by more than the holdback value.
4) bAnd (Deviation Band Holdback): combines the fea­tures of the high and low deviation holdback in that it holds the program back when the process variable deviates above or below the setpoint by more than the holdback value.
To set the holdback type when programming the con­troller:
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
2. Press the SCROLL button until display reads, “Hb.”
23
8 SEGMENT PROGRAMMABLE MODEL W/OTP
Note
The value set in this parameter is always for the entire program.
3. Press the UP or DOWN button to toggle between “bAnd, Hi, Lo and OFF.”
If you choose to activate the holdback feature for your pro­gram by selecting Lo, Hi or bAnd, you will also need to set the holdback value.
Hb U: Holdback Value
Step 2 in programming the controller is to set the Holdback Value. If you donʼt activate the holdback feature, move on to “mP.U: Setting Ramp Units”
To set the holdback value:
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
Note
The holdback value should never be set less than 10.
Note
The time units you set for the ramp and dwell apply for the entire program.
2. Press the SCROLL button until display reads, “Hb.U.”
3. Press the UP or DOWN button to enter a holdback value.
rmP.U: Setting Ramp Units
Step 3 in programming the controller is defining ramp rate units. Ramp units are time units which are used in “rmP.r” segments (ramp to a setpoint at degrees per second, minute or hour) and “rmP.t” segments (ramp to setpoint in a specific amount of time). See “Setting the Segment Type” for an explanation on how to set a ramp segment.
To set the ramp rate units:
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
2. Press the SCROLL button until display reads, “rmP.U.”
3. Press the UP or DOWN button to toggle between seconds, minutes and hours.
24
8 SEGMENT PROGRAMMABLE MODEL W/OTP
dwL.U: Setting Dwell Units
Step 4 in programming your controller is defining dwell units. Dwell units are time units which are used in “dwELL” segments (amount of time to remain at a specif­ic temperature ). See “Setting the Segment Type” for an explanation on how to set a dwell segment.
To set the dwell units:
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
2. Press the SCROLL button until display reads, “dwL.U.”
3. Press the UP or DOWN button to toggle between seconds, minutes and hours.
Note
The program ramp rate is designed to reduce the heatup rate or cooling rate that the furnace normally exhibits. When not using this feature, the fur­nace will operate at its maximum heating and cooling capability.
CYC.n: Setting the Number of Cycles
Step 5 in programming the controller is to define the cycle setting. Set the number of times a group of seg­ments or programs are to be repeated by following the steps listed below.
To set the cycle setting:
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
2. Press the SCROLL button until display reads,”CYC.n.”
3. Press the UP or DOWN button to select the number of cycles you want to run or, press the DOWN button to select “cont.” so the program will run continuously.
Setting the Segment Type
Step 6 in programming the controller is to define the first segment type. There are five segment types; “rmP.r,” “rmP.t,” “dwEll,” “StEP” or “End.” Proceed with the follow­ing steps according to the type of segment you have selected.
rmP.r (Ramp)
To ramp linearly at a set rate to a specified temperature:
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
25
8 SEGMENT PROGRAMMABLE MODEL W/OTP
Note
When the program ramp has ended or has been reset, the furnace will continue to maintain setpoint temper­ature. It will not cool to ambient tem­perature unless the setpoint is set to ambient temperature by the program or by the operator.
2. Press the SCROLL button until display reads, “tYPE.”
3. Press the UP or DOWN button until display reads, “rmP.r.”
Steps 4 and 5 are used in the 4 program model only. If you are using an 8 segment program, skip to step 6.
4. Press the SCROLL button until display reads “Hb.”
5. Press the UP or DOWN button to toggle between “bAnd, Hi, Lo and OFF.”
6. Press the SCROLL button until display reads, “tGt.”
7. Press the UP or DOWN button to set a target set­point.
8. Press the SCROLL button until display reads,”rAtE.”
9. Press the UP or DOWN button to select a value in ramp units (seconds, minutes or hours; set in the “rmP.U” parameter).
rmP.t
To ramp to a specified temperature at a set time:
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
2. Press the SCROLL button until display reads, “tYPE.”
3. Press the UP or DOWN button until display reads, “rmP.t.”
4. Press the SCROLL button until display reads, “tGt.”
5. Press the UP or DOWN button to set a target set­point.
26
6. Press the SCROLL button until display reads, “dur.”
8 SEGMENT PROGRAMMABLE MODEL W/OTP
7. Press the UP or DOWN button to select a time in ramp units (seconds, minutes or hours; set in the “rmP.U” parameter.
dwEll
To maintain a constant temperature for a specified time:
1. Press the PAGE button until you reach the program list (ProG LiSt).
2. Press the SCROLL button until display reads, “tYPE.”
3. Press the UP or DOWN button until display reads, “dwEll.”
4. Press the SCROLL button until display reads, “dur.”
5. Press the UP or DOWN button to select a time in dwell units (seconds, minutes or hours; set in the “dwL.U” parameter).
StEP
To climb instantaneously from the current temperature to a specified temperature.
1. Press the PAGE button until you reach the program list (ProG LiSt).
2. Press the SCROLL button until display reads, tYPE.”
3. Press the UP or DOWN button until the dis­play reads, “StEP.”
4. Press the SCROLL button until display reads, “tGt.”
5. Press the UP or DOWN button to set a target setpoint.
End
To end or repeat a program:
1. Press the PAGE button until you reach the program list (ProG LiSt).
2. Press the SCROLL button until display reads, “tYPE.”
27
Note
Do to the configuration of these con­trollers, it is advised NOT to end a program to the “S OP” type. This will put the furnace in manual mode. In manual mode, the output power is based on percentage. This will ulti­mately cause heating element fail­ure.
8 SEGMENT PROGRAMMABLE MODEL W/OTP
3. Press the UP or DOWN button until display reads, “End.”
4. Press the SCROLL button until display reads, “End.t.”
5. Press the UP or DOWN button to toggle between “dwEll” (an indefinite dwell), “S OP” (End Segment Output Power) and “rSET” (reset). When “dwEll” is selected, the controller will hold the program at the last setpoint in the program indefinitely. When “rSET” is selected, the con­troller will reset the program and control chamber temperature at the single setpoint temperature.
Make sure the single setpoint temperature is set to what temperature you want the controller to regulate, prior to beginning the program.
28
Note
Display will flash “tu.ER” if an error occurs during tuning. To clear the error and restart tuning, simultane­ously press the PAGE and SCROLL buttons and follow the steps outlined in “Autotuning.”
Running a Program
To run a program, press the RUN/HOLD button. (The RUN light will illuminate.)
Holding a Program
To put a running program on hold, press the RUN/HOLD button. (The HOLD light will illuminate.)
Cancelling a Program
To cancel a program, hold the RUN/HOLD button down until the RUN and HOLD lights go off.
Tuning your Furnace
The purpose of tuning your furnace is to match the charac­teristics of your controller to the characteristics of the process being controlled. Good control is evidenced by: stable, straight-line control of the setpoint temperature with no fluctuations; No overshoot or undershoot of the setpoint temperature; rapid restoration of the setpoint temperature when external disturbances cause deviations from the set­point.
Note
To stop the tuning function, simulta­neously press the PAGE and SCROLL buttons.
8 SEGMENT PROGRAMMABLE MODEL W/OTP
This controller has automatic tuning features which install optimum tuning parameters to give the best temperature accuracy. No manual loading of tuning parameters is needed. We recommend that you tune the furnace to your specific application to obtain the best results. To provide the best temperature accuracy possible, use these fea­tures when you install your furnace and whenever you change your application or procedure.
Tuning Error
The display will flash “tu.ER” if an error occurs during tun­ing. To clear the error and restart tuning, simultaneously press the PAGE and SCROLL buttons and follow the steps outlined in “Autotuning.”
Gain Scheduling
G.SP: Gain Scheduling
Gain scheduling is the automatic transfer of control between two sets of PID values. The 2416 controller does this at a presettable process value. Gain scheduling is used for difficult control processes which show large changes in their response time or sensitivity at high or low temperatures, or when heating or cooling.
The G.SP gain schedule setpoint is factory set at 700° C. The G.SP must be adjusted to 200°C from the desired setpoint temperature when tuning.
Setting the Transfer Point
If gain scheduling has been enabled, “G.SP will appear at the top of the PID list. This sets the value at which the transfer will occur. When the process value is below this level, PID1 will be active and when it is above, Pid2 will be active. Set a value between the control regions that show the greatest change to achieve the best point of transfer.
Tuning
The two sets of PID values can be manually set or auto­matically tuned. To tune automatically you must tune above and below the transfer point G.SP. If the process value is below the transfer point G.SP, the calculated val­ues will automatically be inserted into the (SEt 1) set and if the process value is above G.SP, the calculated values will automatically be inserted into the (SEt 2).
29
8 SEGMENT PROGRAMMABLE MODEL W/OTP
Autotuning
The Autotune feature automatically sets up the PID values in the control parameters to suit new process conditions.
To tune your furnace using autotuning:
1. Load your furnace with a load similar to your nor­mal load and close the door.
2. Set the setpoint temperature.
3. Press the PAGE button until the display reads, “Atun LiSt.”
4. Press the SCROLL button until “tunE OFF” is dis­played.
5. Press the UP or DOWN button to select “on.”
6. Simultaneously press the PAGE and SCROLL buttons to return to the HOME DISPLAY. The dis­play will flash “tunE” while tuning is in progress.
Adaptive Tuning
Adaptive tuning continuously evaluates tuning parameters. Adaptive tuning automatically installs new values if better accuracy is possible. Adaptive tuning should be used when the characteristics of a process change due to load or set­point changes or, in a process that can not handle the oscillation caused by a one-shot tune.
To tune your furnace using adaptive tuning:
1. Load your furnace with a load characteristic of those you intend to heat in it.
2. Press the PAGE button until display reads, “Atun LiSt.”
3. Press the SCROLL button until “drA OFF” is dis­played.
30
4. Press the UP or DOWN button to select “on.”
5. Press the SCROLL button until “drA.t” is dis­played.
6. Press the UP or DOWN button until the desired trigger value is achieved.
Caution
Do not overload your furnace chamber. If the load is to be heated uniformly, it should not occupy more than two-thirds of the furnace chamber. Maintain at least a 3/4” gap between the load and ele­ments. Failure to observe this caution could result in damage to the furnace components.
Note
This unit is equipped with a venting sys­tem on the top of the furnace. This is for the removal of fumes from the chamber of the unit.
Furnace Loading
For best results, use only the center two­thirds of the furnace chamber.
If you are heating a number of small parts, spread them throughout the center two-thirds of the furnace chamber.
Keep objects away from the thermocouple.
Use insulated tongs and mittens when load­ing and unloading the furnace.
Always wear safety glasses.
Never come into contact with the heating ele­ments. Hitting the elements with tongs or lay­ing the load against them will cause the ele­ments to burn out prematurely.
Thermocouple Sample Port
Heating Elements
Thermocouple
31
Preventive Maintenance
Contamination is a major cause of element failure, therefore, remove all fume forming material before heating. (e.g. clean cutting oil from tool steel).
Housekeeping is vital to your electric furnace – KEEP IT CLEAN. Run your furnace up to 871°C (1600°F) empty occasionally to burn off the contamination that may exist on the insulation and elements. Maintain 871°C (1600°F) for at least 4 hours to ensure complete ashing of foreign materials.
Element life is reduced somewhat by repeated heating and cooling. If the furnace is to be used again within a few hours, it is best to keep it at the operating tempera­ture or at a reduced level such as 260°C (500°F). We highly recommend that you replace the thermocouple periodically (once every six months) to ensure temper­ature accuracy.
General Cleaning Instructions
Wipe exterior surfaces with a lightly dampened cloth containing a mild soap solution.
32
Troubleshooting
The Troubleshooting section is intended to aid in defining and correcting possible service problems. When using the chart, select the problem category that resembles the malfunction. Then proceed to the possible causes category and take necessary corrective action.
Problem Possible Causes Corrective Action
Cycle light does not The furnace is not Reconnect furnace to power illuminate. connected to power supply. supply.
Incorrect power source. Connect to correct power
source.
ON and OFF power switch Replace power switch. defective.
Defective cycle light. Replace cycle light.
Door switch malfunction. Realign or replace furnace
door safety switch.
Furnace does not heat. No power. Check power source and
fuses or breakers.
Defective electrical hookup. Repair electrical hookup.
Thermocouple has oxidized and Replace thermocouple. opened the circuit.
Controller malfunction. Replace controller.
Heating elements Replace defective elements. burned out.
Door switch malfunction. Realign or replace door safety
switch.
Defective OTP relay. Replace relay.
Defective solid state relay. Replace relay.
Door switch does Door switch not functioning. Realign or replace door safety not cut power to switch. heating elements.
33
TROUBLESHOOTING
Problem (cont.) Possible Causes (cont.) Corrective Action (cont.)
Controller over-temp. Alarm output device malfunction. Replace controller. does not cut power to furnace chamber. OTP relay malfunction. Replace relay.
Element shorted to ground. Replace faulty element.
Slow heatup. Low line voltage. Install line of sufficient size
and voltage (isolate furnace from other electrical loads).
Heavy load in chamber. Lighten load in chamber to allow heat to circulate.
Wrong heating element. Install proper element.
Heating element burned Replace element. out.
Repeated element Overheating furnace. Keep furnace under maximum burnout. temperature. Closer supervision of
control setting.
Heating harmful materials. Enclose material in container.
Clean up spills in and on chamber. Ventilate chamber by leaving top vent slightly open when heating known harmful reagents.
Contamination from previous Replace insulation material. burnout.
Inaccurate temp. Oxidized or contaminated Replace thermocouple. readout. thermocouple.
Poor thermocouple connection. Tighten connections.
Improper loading procedures. Use proper loading
procedures.
Poor ventilation of control. Clear area around furnace control.
Thermocouple connections Reconnect thermocouple reversed. correctly.
34
Maintenance and Servicing
Warning
To avoid electrical shock, this furnace must always be disconnected from the power supply prior to maintenance and service.
Perform only maintenance described in this manual. Contact an authorized deal­er or our factory for parts and assistance.
Refer servicing to qualified personnel.
Note
The ceramic hearth collar may crack. This is a normal condition and will not affect the performance of the hearth col­lar.
To Replace a Heating Element
1. Disconnect the furnace from the power sup­ply.
2. Remove the back terminal cover of the fur­nace. (Note placement and connection of wires.)
3. Loosen the nuts on the terminal points of the four heating element lead wires and remove the element wires from the termi­nals.
4. Loosen the thermocouple hold-down clip and carefully remove the thermocouple from the rear of the furnace chamber.
5. Remove both the back of the furnace and the blanket insulation.
6. Grasp the element lead wires and pull out both elements and the back chamber insula­tion.
7. Replace the defective element.
8. Reverse the disassembly procedure, making sure you thread all element lead wires through the insulating porcelain bushings on the back of the furnace and cut off any excess element lead wire after securing the leads to the terminal points.
9. Reconnect the furnace to the power supply.
10. Test the operation of the furnace.
35
MAINTENANCE AND SERVICING
To Replace a Chromel/Alumel Thermocouple
1. Disconnect the furnace from the power sup­ply.
2. Remove both back covers. (Note placement and connection of wires.)
3. Remove the clip holding the thermocouple in place (1 screw), and remove the two screws on the thermocouple terminals.
4. Remove the thermocouple. (Note: first pull the thermocouple straight out of the hole in the chamber to avoid damage to the insula­tion.)
5. Guide the looped ends of the new thermo­couple through the plastic bushings with the red (-) lead to the right as you face the back of the furnace.
6. Insert the thermocouple straight through the hole in the chamber.
7. Secure the thermocouple with clip and screw. Connect the looped ends of the ther­mocouple to the terminals with “+” to “+” (yellow) and “-” to “-” (red) wires. A polarity test of the thermocouple and lead wire is easily made with the use of a magnet. On a Chromel/Alumel thermocouple and lead wire, the non-magnetic wire is positive (+) and the magnetic wire is negative (-).
8. Replace both back covers.
9. Reconnect to the power supply.
10. Test the operation of the furnace.
36
MAINTENANCE AND SERVICING
To Replace Door Switches (Micro-Switch)
1. Disconnect the furnace from the power sup­ply.
2. Remove the screws on the front dial and the screws and lock washers on the back cover.
3. Slide the control section forward. (Note: do not pull excessively on the internal wires.)
4. Disconnect the wires from the door switch. (Note the connection placement of the wires to the micro-switch.)
5. Remove the screws and nuts from the micro-switch.
6. Insert new micro-switches and secure with the screws and nuts removed in step 5.
7. Reconnect the wires to the new door switch.
8. To realign the door switches, see the follow­ing section, “To Realign Door Switches.”
9. Slide the control section back and replace the screws and lock washers described in step 2.
10. Reconnect to the power supply.
11. Test the operation of the door switches. (See next section, step 8.)
To Realign Door Switches
(Micro-Switch):
1. Disconnect the furnace from the power sup­ply.
2. Remove the lower rear cover.
37
MAINTENANCE AND SERVICING
3. With the door closed, loosen the screws on the micro-switch bracket and gently push the switch bracket forward until you hear a click.
4. Open and close the door; the switch should click when the door is opened approximately 3" and 1" to 2” before the door is closed. Slide the switches backward to increase the dis­tance, forward to decrease the distance.
5. Tighten the two screws to secure the switch­es. Check the operation of the switch as described in step 4 after tightening the screws.
6. Replace the back cover.
7. Reconnect to power supply.
8. To test the operation of the door switch: move the power switch on, set the control to a set­ting high enough to keep the control from cycling, open and close the door; the cycle light should turn OFF when the door is opened approximately 3" and turn back ON 1” to 2” before the door is closed.
To Replace the Controller
The controller plugs into a panel mounting sleeve which should be left permanently installed in the furnace housing. To remove the controller, release the side clips and slide the controller out. Do not attempt to dismantle this unit further; replace it with a Thomas Scientific loaner or a new unit.
38
Replacement Parts
Warning
Replace fuses with same type and rating.
Single Setpoint Models with OTP
5300A20/F48025-TS
Part number Description QTY.
0165A30 Controller 1 0165A47 Element 2 0165A51 Line Fuse 2 0165A68 Pilot Light 1 0165A71 S.S. Relay 1 0165A73 Mechanical Relay 1 0165A80 Door Switch 2 0165A78 Power Switch 1 0165A89 Terminal Block 1 0165A83 Thermocouple 1
8 Segment Programmable Models with OTP
5300A25/F48025-80-TS
Part number Description QTY.
0165A25 Controller 1 0165A51 Line Fuse 2 0165A68 Pilot Light 1 0165A71 S.S. Relay 1 0165A73 Mechanical Relay 1 0165A80 Door Switch 2 0165A78 Power Switch 1 0165A89 Terminal Block 1 0165A83 Thermocouple 1
Ordering Procedures
Please refer to the Specification Plate for the complete model number, serial number, and series number when requesting service, replacement parts or in any correspondence concerning this unit.
39
Wiring Diagrams
SINGLE SETPOINT CONTROL W/OTP
40
WIRING DIAGRAMS
8 SEGMENT PROGRAMMABLE CONTROL
41
42
43
Warranty Repair and Service
In addition to manufacturer warranties, Thomas Scientific (the Company) warrants all instruments and equip­ment (other than supplies, small items, reagents and chemicals) delivered to and retained by their original pur­chasers to be free from defect in material and workmanship for one year from the date of the Companyʼs invoice to the purchaser (Thomas Scientific makes no warranty with respect to consumable parts or supplies). For a period of one year from the date of such invoice, the Company will correct, either by repair or replace­ment at the Companyʼs sole election, any defect in material or workmanship (not including defects due to mis­use, abuse, abnormal conditions or operation, accident, alteration, improper installation, acts of God, or serv­ice or modification of the product without prior authorization of the Company) without charge for labor, parts or shipment of the product to and from the service facility designated by the Company. Manufacturer warranties that extend beyond this 1-year period are the sole responsibility of the manufacturer.
The determination of whether any product has been subject to misuse or abuse will be made solely by the Company. The Company shall not be liable for any delay in performance under this warranty caused by any contingency beyond the Companyʼs control, including war, government restrictions, strikes, acts of God, or reduced supply of materials. The Company shall not be liable for any special, incidental, or consequential damages, or any damage to plant, personnel, equipment or products, directly or indirectly resulting from the use or misuse of any product. Representations and warranties made by any person, including dealers and representatives of the Company which are inconsistent, in conflict with or in excess of the terms of this war­ranty shall not be binding upon the Company unless placed in writing and approved by an officer of the Company.
This warranty and all claims hereunder shall be governed by the laws of the State of New Jersey, United States of America.
The foregoing warranty is in lieu of all other warranties, guarantees, or representations, whether oral, written or implied, including any warranty of merchantability or fitness for use or purpose.
The Companyʼs liability under this warranty or otherwise with respect to products of their use (including liability for negligence or otherwise in tort) is limited exclusively to the remedies provided herein and no other right or remedy shall be available to any person.
Thomas Scientific P.O. Box 99 Swedesboro, NJ 08085 T: 800-345-2100 www.thomassci.com
Loading...