–WARNING–
LUMINAIRE MUST BE GROUNDED AS REQUIRED PER PA RAGRAPH 410.44 AND ARTICLE 250 OF THE NATIONAL ELECTRIC
CODE AND/OR SECTION 10 AND RULE 30-500 OF CANADIAN ELECTRIC CODE. FAILURE TO PROPERLY GROUND THIS
LUMINAIRE WILL CREATE AN ELECTRICAL SHOCK HAZARD WHICH CAN CAUSE SERIOUS INJURY OR DEATH.
INSTALLATION INSTRUCTIONS FOR LUMINAIRE MOUNTS
DO NOT ATTEMPT INSTALLATION UNTIL YOU ARE FAMILIAR WITH ALL PRECAUTIONS AND PROCEDURES OUTLINED WITHIN
THIS INSTRUCTION SHEET.
WARNING:
Risk of Shock.
Disconnect Power before Installation.
1. PENDANT AND STANCHION TYPE MOUNTS
Screw the luminaire mount onto previously inst all conduit, a minimum of 3 threads must be engaged between the conduit and luminaire mount.
Tighten the conduit locking screw (A) to 30 inch pounds (figure.1).
2. CEILING AND WALL TYPE MOUNTS
Install the luminaire mount to the appropriate mounting surface by means of the external mounting lugs (B).
The bolt positions are as follows:
a. Ceiling:
12-3/4” bolt circle for std - 3 or 9-5/8” bolt circle for mini - M3
b. Wall:
3-3/4” X 3-3/4” bolt pattern
Install conduits plug in any unused con duit entries with the supplied close-up plugs (C), minimum of 3 threads must be engaged between the
conduit or close-up plug and luminaire mount.
3. 4 INCH OUTLET BOX TYPE MOUNTS
Install the luminaire mount to previously installed 4 inch outlet box using supplied gasket and screws tighten mounting screws (d) to 30
inch- pounds.
Always inspect gasket joints before closing the luminaire, if gasket shows any indication of deterioration, replace the luminaire.
Tel: (888) 552-6467 Fax: (800) 316-4515 www.tnb.com
03/15 750.1843_ Rev. A
1/1