• A direct-buried mechanical splice with a cable
range of 250 to 750 Kcmil.
• Insulated in a “Flood-Seal” EPDM cover.
Select the correct cut-off ring for the cable being used.
1
2 1/0
2/0 350
350 500
500 750
750 1000
1000 1500
#2 to 1/0 (.37-.54)
#2/0 to 350 *(.53-.91)
350 to 500 *(.83-1.09)
500 to 750 *(.96-1.19)
750 to 1000 *(1.183-1.4)
1000 to 1500 *(1.3-1.6)
Danger of Electric Shock! Installation of this product must be performed
by trained installers in accordance with all applicable local, state and
national electrical codes, installation standards and safety rules.
INSTALLATION INSTRUCTIONS
for USK 750
"Flood-Seal"® Mechanical Splice Kit
Cut off the rocket at
2 1/0
2/0 350
350 500
500 750
750 1000
1000 1500
* Decimal range
2
tip of the arrow,
leaving the correct
cable size showing
on the opened
rocket.
Wipe the cable clean.
3
Bevel the end of
the cable
insulation for
ease of
installation.
Apply silicone grease to the end of
4
the cable and the cut opening
of the rocket. Slide the rocket
over the prepared cable.
Repeat steps 2, 3 and
4 on the cap.
5
7
WARNING
Strip the cable insulation for
installation of the connector,
baring approximately 3-1/4”
of cable.
3¼”
WIRE SIZE TORQUE
250 - 350 Kcmil 240 in-lbs (20 ft-lbs)
400 - 750 Kcmil 360 in-lbs (30 ft-lbs)
Apply silicone grease to the open edge of the
rocket. Center the connector
between the cap and rocket.
Slide the covers together.
6
Install the
connector to the
suggested torque
using a 3/8” hex
wrench.
Limited Warranty Applies. Refer to:
www.tnb.com/ecpwarranty for full warranty terms.
© 2012 Thomas & Betts. All Rights Reserved.
INSTALLATION INSTRUCTIONS
"Flood-Seal"® Mechanical Splice Kit
• A direct-buried mechanical splice with a cable
range of 250 to 750 Kcmil.
• Insulated in a “Flood-Seal” EPDM cover.
Select the correct cut-off ring for the cable being used.
1
2 1/0
2/0 350
350 500
500 750
750 1000
1000 1500
#2 to 1/0 (.37-.54)
#2/0 to 350 *(.53-.91)
350 to 500 *(.83-1.09)
500 to 750 *(.96-1.19)
750 to 1000 *(1.183-1.4)
1000 to 1500 *(1.3-1.6)
2 1/0
2/0 350
350 500
500 750
750 1000
1000 1500
Thomas & Betts Corporation
for USK 750
Cut off the rocket at
2
tip of the arrow,
leaving the correct
cable size showing
on the opened
rocket.
Wipe the cable clean.
3
Bevel the end of
the cable
insulation for
ease of
installation.
Apply silicone grease to the end of
4
the cable and the cut opening
of the rocket. Slide the rocket
over the prepared cable.
Repeat steps 2, 3 and
4 on the cap.
Memphis, Tennessee
www.tnb.com
WARNING
Danger of Electric Shock! Installation of this product must be performed
by trained installers in accordance with all applicable local, state and
national electrical codes, installation standards and safety rules.
Strip the cable insulation for
5
installation of the connector,
baring approximately 3-1/4”
of cable.
3¼”
WIRE SIZE TORQUE
250 - 350 Kcmil 240 in-lbs (20 ft-lbs)
400 - 750 Kcmil 360 in-lbs (30 ft-lbs)
Apply silicone grease to the open edge of the
7
rocket. Center the connector
between the cap and rocket.
Slide the covers together.
Install the
6
connector to the
suggested torque
using a 3/8” hex
wrench.
0014647 A
103_R3
Page 1 of 1
* Decimal range