Thomas & Betts UH-11-L Installation Manual

Page 1
Danger of Electric Shock! Installation of this product must be performed
by trained installers in accordance with all applicable local, state and
national electrical codes, installation standards and safety rules.
INSTALLATION INSTRUCTIONS
for "Flood-Seal"® Insulated Mechanical Splice
Cat. No. UH 11 & UH 11 L
WARNING
14 10
8 4
2 1/0
2/0 250
300 400
500
Apply silicone grease. Slide cut
4
rocket over prepared cable.
#8 to #4 cut here *(.24-.38)
#2 to 1/0 cut here *(.38-.54)
2/0 to 250 cut here *(.53-.78) 300 to 400 cut here *(.74-.98)
500 *(.94-1.175)
Select correct cut-off ring
1
for cable being used.
#14 to #10 cut here (SL)
* Decimal range
5 6
Insert conductors into the outlet barrels of
14 10
8 4
2 1/0
2/0 250
300 400
500
HOMAC FSS500-C
connector and tighten set screws to a torque of 240 inch-lbs.
Limited Warranty Applies. Refer to: www.tnb.com/ecpwarranty for full warranty terms.
© 2012 Thomas & Betts. All Rights Reserved.
• A direct buried mechanical splice with a
cable range of #6 to 350 MCM.
• Insulated in a “Flood-Seal” EPDM cover.
• Double set screws for lowest contact resistance.
• Testing: UH11 & UH11L mechanical splices are warranted to meet or exceed Class A
requirements of EEI NEMA STANDARD TDJ-162.
Cut off rocket sleeve at the
2
tip of arrow, leaving correct cable size showing on opened rocket.
0
1
4
1
4
8
0
/
2
1
2
0
5
/
0
2
3
0
0
0
0
4
500
Strip insulation from cable ends, baring
3
1-7/8” of conductor. Thoroughly wire brush bare conductor with compound to break up oxides.
Apply silicone to open edge of rocket. SLIDE TOGETHER.
Thomas & Betts Corporation
Memphis, Tennessee
www.tnb.com
0014720 A
Page 1 of 1
14 10
8 4
2 1/0
2/0 250
300 400
500
Apply silicone grease. Slide cut
4
rocket over prepared cable.
#8 to #4 cut here *(.24-.38)
#2 to 1/0 cut here *(.38-.54)
2/0 to 250 cut here *(.53-.78) 300 to 400 cut here *(.74-.98)
500 *(.94-1.175)
Select correct cut-off ring
1
for cable being used.
#14 to #10 cut here (SL)
* Decimal range
5 6
INSTALLATION INSTRUCTIONS
for "Flood-Seal"® Insulated Mechanical Splice
Cat. No. UH 11 & UH 11 L
14 10
8 4
2 1/0
2/0 250
300 400
500
HOMAC FSS500-C
Insert conductors into the outlet barrels of connector and tighten set screws to a torque of 240 inch-lbs.
• A direct buried mechanical splice with a
cable range of #6 to 350 MCM.
• Insulated in a “Flood-Seal” EPDM cover.
• Double set screws for lowest contact resistance.
• Testing: UH11 & UH11L mechanical splices are warranted to meet or exceed Class A
requirements of EEI NEMA STANDARD TDJ-162.
Cut off rocket sleeve at the
2
tip of arrow, leaving correct cable size showing on opened rocket.
Apply silicone to open edge of rocket. SLIDE TOGETHER.
Danger of Electric Shock! Installation of this product must be performed
WARNING
by trained installers in accordance with all applicable local, state and
national electrical codes, installation standards and safety rules.
0
1
4
1
4
8
0
/
2
1
2
0
5
/
0
2
3
0
0
0
0
4
500
Strip insulation from cable ends, baring
3
1-7/8” of conductor. Thoroughly wire brush bare conductor with compound to break up oxides.
Limited Warranty Applies. Refer to: www.tnb.com/ecpwarranty for full warranty terms.
© 2012 Thomas & Betts. All Rights Reserved.
Thomas & Betts Corporation
Memphis, Tennessee
www.tnb.com
0014720 A