Danger of Electric Shock! Installation of this product must be performed
by trained installers in accordance with all applicable local, state and
national electrical codes, installation standards and safety rules.
INSTALLATION INSTRUCTIONS
for UH1000 Connector
WARNING
#2 to 2/0 CUT HERE *(.380-.580)
3/0 to 250 CUT HERE *(.580-.765)
300 to 500 CUT HERE *(.760-1.003)
500 to 750 CUT HERE *(.926-.1.218)
750 to 1000 CUT HERE *(1.128-1.372)
1000 CUT HERE *(1.280-1.662)
* DECIMAL RANGE
Remove insulating sleeve
1.
from the outlet. Select
2 2/0
3/0 250
300 500
500 750
750 1000
1000
3.
correct cut-off ring for cable being used.
Cut off rocket sleeve at the
2.
tip of arrow, leaving correct cable size showing on opened rocket.
0
/
2
2
0
5
2
3
/
0
3
0
0
0
0
5
0
5
5
0
7
0
0
7
0
5
0
0
1
1
0
0
0
5.
Limited Warranty Applies. Refer to: www.tnb.com/ecpwarranty for full warranty terms.
© 2012 Thomas & Betts. All Rights Reserved.
Strip the insulation from the cable end baring approx. 3” of conductor. Pencilling is preferred although not necessary.
Thoroughly wire brush bare conductor with compound to break up oxides.
Insert conductor into the
4.
Apply silicone grease. Slide cut rocket over
6.
outlet barrel. Tighten set screws down on the conductor, starting with the outermost screw.
prepared cable.
WIRE SIZE #14 to #3 #2 to 350 MCM 400 MCM to 750 MCM 800 MCM to 1000 MCM
Slide rocket sleeve over
7.
outlet and onto PVC shoulder until rocket butts against connector bar.
Thomas & Betts Corporation
www.tnb.com
INCH POUNDS
120 240 360 500
FOOT POUNDS
10 20 30 42
0507285 A
192_R1
Page 1 of 1
#2 to 2/0 CUT HERE *(.380-.580)
3/0 to 250 CUT HERE *(.580-.765)
300 to 500 CUT HERE *(.760-1.003)
500 to 750 CUT HERE *(.926-.1.218)
750 to 1000 CUT HERE *(1.128-1.372)
1000 CUT HERE *(1.280-1.662)
* DECIMAL RANGE
Remove insulating sleeve
1.
from the outlet. Select correct cut-off ring for cable being used.
Cut off rocket sleeve at the
2.
tip of arrow, leaving correct cable size showing on opened rocket.
INSTALLATION INSTRUCTIONS
for UH1000 Connectors
Strip the insulation from
2 2/0
3/0 250
300 500
500 750
750 1000
1000
3
5
7
1
0
0
0
/
2
2
0
5
2
3
/
0
0
0
0
0
5
0
5
0
7
0
0
0
5
0
0
1
0
3.
the cable end baring approx. 3” of conductor. Pencilling is preferred although not necessary.
Thoroughly wire
5.
brush bare conductor with compound to break up oxides.
Danger of Electric Shock! Installation of this product must be performed
WARNING
by trained installers in accordance with all applicable local, state and
national electrical codes, installation standards and safety rules.
Insert conductor into the
4.
Apply silicone grease. Slide cut rocket over prepared cable.
6.
outlet barrel. Tighten set screws down on the conductor, starting with the outermost screw.
WIRE SIZE #14 to #3 #2 to 350 MCM 400 MCM to 750 MCM 800 MCM to 1000 MCM
Slide rocket sleeve over
7.
outlet and onto PVC shoulder until rocket butts against connector bar.
INCH POUNDS
120 240 360 500
FOOT POUNDS
10 20 30 42
Limited Warranty Applies. Refer to: www.tnb.com/ecpwarranty for full warranty terms.