This document is meant for use with the Limitorque MX Installation and Operation Manual for MX-05
through MX-40. Information in this document is also applicable to MX-85 and MX-140. No part of
this book shall be reproduced, stored in a retrieval system, or transmitted by any means, electronic,
mechanical, photocopying, recording, or otherwise without the written permission of Limitorque. While
every precaution has been taken in the preparation of this book, the publisher assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the
information contained herein.
This document is the proprietary information of Flowserve, furnished for customer use ONLY. No other
uses are authorized without written permission from Limitorque.
Limitorque reserves the right to make changes, without notice, to this document and the products it
describes. Limitorque shall not be liable for technical or editorial errors or omissions made herein;
nor for incidental or consequential damages resulting from the furnishing, performance or use of this
document.
The choice of system components is the responsibility of the buyer, and how they are used cannot be
the liability of Limitorque. However, Flowserve Limitorque’s sales team and application engineers are
always available to assist you in making your decision.
This manual contains information that is correct to the best of Flowserve’s knowledge. It is intended
to be a guide and should not be considered as a sole source of technical instruction, replacing good
technical judgment, since all possible situations cannot be anticipated. If there is any doubt as to exact
installation, configuration, and/or use, call Flowserve Limitorque at (434) 528-4400. The latest revisions
to this document are available online at http://www.limitorque.com
2
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
ODVA hereby issues this Declaration of Conformity to the DeviceNet™ Specification for the product(s) described below. The Vendor
listed below (the "Vendor") has holds a valid the Terms of Usage Agreement for the DeviceNet Technology from ODVA, which is
incorporated herein by reference, thereby agreeing that it is the Vendor’s ultimate responsibility to assure that its DeviceNet
Compliant Products conform to the DeviceNet Specifications and that the DeviceNet Specifications are provided by ODVA to the
vendor on an AS IS basis without warranty. NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WITHOUT LIMITATION ANY
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE BEING PROVIDED BY ODVA.
In recognition of the below DeviceNet Compliant Product(s) having been DeviceNet Conformance Tested at ODVA-authorized Test
Service Provider and having received a passing result from ODVA at the Composite Test Revision Level specified below, this
Declaration of Conformity authorizes the Vendor to use the DeviceNet Certification Marks in conjunction with the specific DeviceNet
Compliant Product(s) described below, for so long as the Vendor's Terms of Usage Agreement for the DeviceNet Technology remains
valid.
DeviceNet CONFORMANCE TESTED ™
Certification Logo MarkCertification Word Mark
This Declaration of Conformity is issued on 27 February 2006
on behalf of ODVA by:
Katherine Voss
Executive Director
Vendor Information
Vendor Name Flowserve Corporation
Vendor Address 5114 Woodall Road
Lynchburg, VA 24506
USA
Test Information
Test Date 16-17 February 2006
Composite Test Revision 18
ODVA File Number 10331
Product Information
Identity Object Instance 1
Device(s) Under Test Value
Vendor ID (Identity Object Attribute 1) 966
Network Category Node
Device Type (Identity Object Attribute 2) 0
Device Profile Name Generic Device
Product Revision (Identity Object Attribute 4) 1.002
Products Covered Under This Declaration of Conformity
No. Product Code (Identity Object Attribute 3) Product Name (Identity Object Attribute 7) SOC File Name
119800 Flowserve MX DLI.stc
Declaration of DeviceNet Conformance –
ODVA Certification
5
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Abbreviations
CIP Common Industrial Protocol
CAN Controller Area Network
COS Change of State
ODVA Open DeviceNet Vendor Association
UCMM Unconnected Message Manager
NV-RO Non-Volatile Read Only. Data is stored in non-volatile memory and can only be read. Data is
stored during Power-Off. For DeviceNet Limitorque Interface this storage area is FLASH
NV-RW Non-Volatile Read Write. Data is stored in non-volatile memory and can be read and write.
Data is stored during Power-Off. For DeviceNet Limitorque Interface this storage area is EEPROM
V-RO Volatile Read Only. Data is stored in volatile memory and can only be read (e.g. Status). Data is
lost during Power-Off. For DeviceNet Limitorque Interface this storage area is RAM
V-RW Volatile Read Write. Data is stored in volatile memory and can be read and write data is lost
during Power-Off, for DeviceNet Limitorque Interface this storage area is RAM.
DNFU DeviceNet Field Unit (PCB w/in actuator control compartment)
SPI Synchronous Peripheral Interface
PCB Printed Circuit Board
6
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
1 Introduction
1.1 Purpose
This manual explains how to install and operate the Limitorque MX™/DeviceNet field unit (DNFU) and is
to be used as an addendum to Bulletin LMENIM2306, Limitorque MX Installation and Operation Manual.
Up to 63 actuators, each containing a DeviceNet field unit, may be connected by a single 5 strand,
twisted-pair cable to form a DeviceNet network, two wires for connection to the data highway and two
wires for connection to the DC power lines of the network highway, plus a screen connection. A suitable
power supply and termination resistors on the highway are required in order for the FU to function
correctly. This network permits the actuators to be operated by various control room devices such as a
distributed control system (DCS), a programmable logic controller (PLC), or a personal computer (PC).
The DeviceNet system communicates status and alarm data from each MX actuator.
1.2 How to Use this Manual
Each section provides the MX user with information on installing and operating the MX DNFU.
Section 1, Introduction: Details user safety and knowledge requirements, system capabilities, and
features.
Section 2, System Components: Focuses on the description of the DeviceNet system hardware and
software components.
Section 3, Installation and Configuration: Provides details for installing and configuring a DNFU.
Section 4, Object Model Diagram: Provides a list of inputs and outputs supported through the Assembly
Object system information.
Section 5, View DeviceNet Status
Section 6, Associated Documents
Section 7, Troubleshooting
Section 8, How to Order Parts
Section 9, Regulatory Information
Section 10, Wiring Diagram
1.3 User Safety
Safety notices in this manual detail precautions the user must take to reduce the risk of personal injury
and damage to the equipment. The user must read and be familiar with these instructions before
attempting installation, operation, or maintenance. Failure to observe these precautions could result
in serious bodily injury, damage to the equipment, warranty void, or operational difficulty. User must
follow local and state safety regulations.
Safety notices are presented in this manual in three forms:
WARNING: Refers to personal safety. Alerts the user to potential danger. Failure to follow
c
warning notices could result in personal injury or death.
c
7
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
CAUTION: Directs the user’s attention to general precautions that, if not followed, could result in
a
personal injury and/or equipment damage.
NOTE: Highlights information critical to the user’s understanding of the actuator’s installation and
operation.
1.4 User Knowledge
It is recommended that the user read this manual in its entirety before the DeviceNet equipped actuator
is installed and operated.
The user needs to have a fundamental knowledge of electronics and microprocessor concepts. An
understanding of valve actuators and digital control systems is also of benefit to the DNFU user.
1.5 DeviceNet System Capabilities and Features
DeviceNet is a low cost communications protocol which permits up to 64 nodes (devices) to be
installed over a single network and is based upon CAN (Controller Area Network), a broadcast protocol
developed for the automotive industry. DeviceNet™ protocol is defined as an open network standard and
Limitorque’s device is certified for use by the ODVA, Open Device Standard Association. DeviceNet is
usually PLC input controlled and the Limitorque MX electronic actuator is well suited for this communication system. A typical network is seen in Figure 1.1.
Figure 1.1 – Typical Network
1.5.1 General Specifications
1.5.1.1 Network Specifications
DeviceNet is a digital, trunk/drop network that connects and serves as a communication network
between industrial controllers and I/O devices.
DeviceNet follows the Open Systems Interconnection (OSI) model, an ISO standard for network
communications that is hierarchical in nature. Networks that follow this model define all necessary functions from the physical implementation up to the protocol and methodology to communicate control
and information data within and across networks.
8
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Table 1.1 – Network specifications
Network SizeUp to 63 Nodes
Network LengthSelectable end-to-end network distance varies with speed
Bus TopologyLinear (trunkline/dropline); power and signal on the same network cable
Bus AddressingMulti-Master and Master/Slave special case; polled of change-of-state
System FeaturesSelectable end-to-end network distance varies with speed
Termination resistor (121 ohms) must be used at each end of the network
1.5.1.2 MX Field Unit Specifications
CIP Generic Device Profile (Device Type = 00hex) extended to DNFU requirements
•
Group 2 Server
•
UCMM capable device
•
Predefined Master/Slave Connection Set supporting
•
Explicit Connection
•
Polled I/O Connection
•
Bit-Strobed I/O Connection
•
Change of State / Cyclic I/O Connection
•
Full support of fragmentation protocol
•
Device Heartbeat Message
•
Device Shutdown Message
•
Offline Connection Set
•
Galvanical Isolation: The isolation voltage for the DNFU is up to 1,500 VRMS for 1 minute (1,800
•
VRMS for 1 second
Power Supply: The DNFU Interface will be powered from the DeviceNet bus. A switching regulator is
•
used to generate the internal supply voltage: VCC nominal 5.0 V ± 5 %
Surge Suppression: The DNFU Interface is equipped with surge suppression for the DeviceNet
•
network data and power lines. Surge suppression is compliant with IEC 61000-6-2:2001.
125 Kbps 500 m (1,640 ft)
250 Kbps 250 m (820 ft)
500 Kbps 100 m (328 ft)
(exception-based)
Environmental conditions
The DNFU environmental parameters are within the same environmental constraints as the actuator.
9
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
2
1
2
3
7
8
4
5
11
12
10
6
9
2 System Components
2.1 Introduction
This section gives an overview of the components used in the DeviceNet system. The field unit is
installed in each MX actuator. The network cable connects the field unit to the network via the actuator
terminal block. The network cable is connected to a host controller, typically a PLC.
2.2 Hardware
NOTE: Recommended storage procedures are detailed in Bulletin LMAIM1314 Limitorque MX
Maintenance and Spare Parts Manual. Failure to comply with recommended procedures will void the
warranty. For longer-term storage, contact Limitorque for procedures and recommendations.
Figure 2.1 – MX-05 Actuator
10
Table 2.1 – MX-05 Actuator
1 Handwheel
2 Declutch Lever
3 Oil Fills (dotted arrow depicts fill on declutch side)
4 Controls Compartment (field unit location)
5LCD Display
6Control Knobs
7Ground Lug
8Thrust/Torque Base
9Conduit Entries
10Terminal Compartment
11Motor
12Nameplate
2.2.1 Limitorque MX
The MX is a multi-turn valve actuator designed for operation of ON-OFF and modulating valve applications. This actuator controls the opening and closing of valves. See Figure 2.1.
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
The MX features include:
Non-intrusive setup
•
Separately sealed terminal chamber
•
Patented absolute encoder for valve position sensing (no battery required)
•
32-character LCD for indication and calibration with configuration permitted in six languages.
•
Sophisticated electronic control, monitoring, and diagnostic capabilities with patented LimiGard™
•
technology
2.2.2 DeviceNet Field Unit
The DeviceNet field unit is installed in the MX controls compartment. This unit permits the actuator to
be controlled by a host controller, typically a PLC, via the DeviceNet network. The DNFU includes two
high-level, surge-protected, and isolated network communication channels, configurable digital I/O, and
configuration via LCD screen. The following commands and information may be transmitted over the
DeviceNet network:
“OPEN,” “STOP,” and “CLOSE” commands
•
“ESD” and “MOVE–TO” position commands
•
Actuator status and alarm messages
•
Six digital inputs and two analog inputs for user
•
A surge-protected and isolated communication channels
•
MX control panel configuration
•
Torque output (for reference only) and position feedback
•
Four digital outputs (standard)
•
Figure 2.2 – DeviceNet Field Unit
11
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
2.2.3 Hardware interface
The DeviceNet Limitorque Interface is comprised of a minimum of one PCB with two interfaces - One
for the DeviceNet Terminal Block connector and one for the SMT Main Board.
Figure 2.3 gives an overview about the hardware. The microcontroller on the DeviceNet Limitorque
Interface handles the DeviceNet protocol, stores the DeviceNet parameters in an EEPROM, and communicates with the SMT Main Board via SPI.
Figure 2.3 – DeviceNet Limitorque Interface
12
2.2.4 Network Cable
DeviceNet is a CAN - based protocol that uses 5 wires including a shield. Two of the conductors are
used for 24V DC power & up to 8 amps (4 amps for NEC Class 2) may be passed along the hi-way from
a suitable power source. Two conductors are used for the CAN bus signals, CAN_H and CAN_L, which
are usually smaller in diameter. Limitorque recommends Belden cable for connecting to a DeviceNet
network. The specifications for thick and thin cable (per site requirements) are as follows:
Table 2.2 – Belden Cable Specifications
Belden
Part No.
3082A
3084A
AWG
(Stranding)
dia. Inches
Nom. DCR
2 – 15 AWG
(19 x 28)
3.6 ohm/1000 ft
11.8 ohm/km
2 – 18 AWG
(19 x 30)
6.9 ohm/1000 ft
22.7 ohm/km
2 – 22 AWG
(19 x 34)
17.5 ohm/1000 ft
57.4 ohm/km
2 – 18 AWG
(19 x 36)
28.0 ohm/1000 ft
91.9 ohm/km
Insulation
material
(color code)
Power pair
(Black/Red)
Data pair
(Blue/White)
Power pair
(Black/Red)
Data pair
(Blue/White)
Nominal
O.D.
12.2 mm
7.2 mm12012.0 pF/ft
Nom
Impedance
(ohms)
120 12.0 pF/ft
Capacitance
Nominal
Test
Frequency
(MHz)
0.125
0.5
1
0.125
0.5
1
Maximum
Attenuation
dB/100ft
0.13
0.25
1.36
0.29
0.50
1.70
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Table 2.3 – Total cable length between repeaters or nodes:
Network Size125 KBPS 250 KBPS500 KBPS
Thick Trunk Length500 m (1,640 ft) 250 m (1,640 ft)100 m (1,640 ft)
Thin Trunk Length100 m (328 ft)100 m (328 ft)100 m (328 ft)
Flat Trunk Length380 m (1,250 ft)200 m (656 ft)75 m (246 ft)
Maximum Drop Length6 m (20 ft)6 m (20 ft)6 m (20 ft)
Cumulative Drop Length156 m (512 ft)78 m (256 ft)39 m (128 ft)
Note: Each actuator includes 0.60 meters of internal drop length.
3 Installation and Configuration
3.1 Site and Network Cable Preparation
3.1.1 Site Preparation
Prepare the site and associated equipment for operation of the DeviceNet controlled MX actuators as
follows:
1. Prepare a detailed site plan consisting of the following:
Actuator locations, tag numbers, DeviceNet addresses
•
Junction boxes, terminal strip locations, and tag numbers
•
2. Provide free access to the MX control panel and terminal block for setup, configuration, and
troubleshooting.
3. Prepare cable and label all wires. See Section 3.1.2, Network Cable Preparation.
4. Install power and control wires in separate conduits. Shielding is not sufficient to prevent induction
of stray voltages onto signal leads from the power lines.
5. Install and verify earth grounds.
NOTE: Limitorque defines an effective local earth ground as a low impedance (less than 5 ohms) path
to:
A ground electrode placed in close vicinity of the actuator that is free of ground loop currents. OR
•
A safety ground that is free of ground loop currents running from the actuator back to the system
•
ground electrode. If the signal wiring is run on aerial cable where it may be exposed to highenergy electrostatic discharge (such as lightning), a low impedance path to ground that is capable
of high current must be provided a short distance from the actuator as described above. OR
A power distribution grid identifying the impact of power isolation to a particular actuator or
•
group of actuators should be provided.
3.1.2 Network Cable Preparation
3.1.2.1 Network Cable Connection to the Field Unit
The DeviceNet field unit is connected to the network via the MX terminal block. The network cable is
connected to the terminal block as shown in Figure 3.1.
13
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Figure 3.1 – Network cable connection to terminal block
NOTE: Recommended DeviceNet cable is Belden 3084A or equal. 121 ohm, ¼ W +/-1% termination
resistors must be connected at each segment end. Customer is required to connect wire between
terminal 30 and chassis ground for surge protection. Preferred network wiring is to connect shield to
terminal 48 for only one unit on each segment. Connect remaining individual network cable shields
together to ensure proper shielding of entire network. Consult wiring diagram for exact terminal
connection points as they may change.
Prepare the network cable for connection to the MX terminal block as follows.
CAUTION: Strip stranded conductors carefully; do not damage the strands. This will weaken the
a
conductor. Do not nick conductors or conductor insulation when stripping away the insulation.
Nicking stresses the conductor and can cause the conductor to break. This type of damage may
not be apparent and failure can occur later without warning.
NOTE: Excess cable should be cut, not coiled or looped, to prevent noise induction into the network and
to reduce signal loss through unnecessarily long cable runs.
Cable Preparation
1. Remove two to three inches (5 to 8 cm) of the outer plastic jacket.
2. Separate the cable parts. Unbraid the shield and peel back the foil shield to the same point where
the outer jacket was removed. Cut away the braided shield and the foil shield. Strip the insulation
from the conductors approximately 0.4 inch (1 cm).
3. Apply heat shrink tubing to insulate the drain wire and to provide stress relief to the cable.
CAUTION: Do not melt the insulation. NOTE: Ungrounded drain wires should be cut even with
a
the cable sheath. The brand foil and drain wire should have heat shrink tubing applied.
4. Install ring tongue connectors. Flowserve recommends the use of Thomas & Betts #RZ22-6 for
optimum results.
14
5. Connect the network cables to the MX terminal block as shown in Wiring Diagram #18-499-0038-3.
Table 3.1
48Shield
15 (Blue) DATA (-)
16 (White) DATA (+)
29 (Black) Network 0 V
41 (Red) Network 24V
30 Earth ground for surge protection circuit
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
NOTE: Ground each segment of the cabling at only one point to prevent ground loops, which can affect system
performance. Verify the actuator is properly grounded.
6. Install jumper cable from terminal block pin 30 to earth ground or ground lug.
3.2 Installation Verification
3.2.1 Network Cabling Installation Verification
After installation is complete and prior to operation, inspect the network cable and its connection to
each field unit for the following:
NOTE: Units should be disconnected from power. Network should be disconnected from host.
1. There should be:
No nicks in the insulation—this can cause a short between conductors or to the grounded shield.
•
No cut strands in a stranded conductor—this can cause a poor connection and eventually an
•
open circuit.
2. Verify that there is data wiring on each actuator per wiring diagram.
3. Cable armor should not be shorted to the cable shield/drain wire. Cable armor may not be at ground
potential and could be subject to lightning surges.
The shield/drain wire should only be grounded at one end of each cable segment (the section between
adjacent actuators between the host system and an actuator) to avoid ground loop problems.
The ground/earth connection should be at true ground potential and effective at all times. See Section
3.1.1, Site Preparation.
3.2.2 DNFU Installation Verification
NOTE: Connect to either 24 V DC power or mains and activate power.
Verify the field unit is installed as follows:
1. Enter the “SETUP” mode as detailed in Bulletin LMAIM1306/2306, MX Installation and Operation
Manual.
2. In the “SETUP” mode, use the black control knob to select “YES” to the main menu selection “VIEW
DIAGNOSTICS?”
3. Select “YES” to the display “VIEW HARDWARE STATUS?”
4. Select “YES” to scroll through the menu selections. The LCD will read “DeviceNet (OK) – NEXT?” if
installed.
NOTE: If the “DeviceNet (OK) – NEXT?” does not appear, contact Flowserve for assistance.
19. To return to the normal display, use the red knob to select either “LOCAL” or “REMOTE.”
15
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
4 Object Model Diagram
Figure 4.1 – Object Model of DeviceNet Limitorque Interface
16
4.1 Assembly Objects
The Assembly Object binds attributes of multiple objects, which allows data to or from each object to
be sent or received over a single connection. Assembly Objects can be used to bind input data or output
data. The terms input and output are defined from the networks point of view. An input will produce data
on the network and an output will consume data from the network
The terms input and output are defined from the networks point of view.
An input is a signal produced at the actuator and sent to the PLC via the network. •
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
An output is a signal produced at the PLC and sent to the actuator via the
•
network.
The user may select one output and one input instance.
The default assembly objects are as follows: Polled input - 105, Polled output - 100, Bitstrobe - 107,
COS - 109.
Table 4.1
Instance ID Type Data Component Name Size
100 Output Output 1 (All Control Channels) 9
101 Output Output 2 (Analog Control and ESD only) 5
102 Output Output 3 (Discrete Control and ESD only) 4
103 Output Output 4 (Analog Control only) 3
104 Output Output 5 (Discrete Control only) 3
105 Input Input 1 (All Status Information) 16
106 Input Input 2 (Position and Faults only) 6
107 Input Input 3 (Position and Faults only) 8
108 Input Input 4 (Position, User and Faults only) 11
109 Input Input 5 (Faults and Alarms only) 6
4.2 Output Assembly Instances
Table 4.2 – Output Assembly Instance 100
Assembly
Object
Instance ID
100 Output 1 100 Channel
Data
Component
Name
Table 4.3 – Output Assembly Instance 101
Assembly
Object
Instance ID
101 Output 2 100 Channel
Data
Component
Name
Class
IDName IDName
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
Class
ID Name ID Name
Interface
100 Channel
Interface
100Channel
Interface
100 Channel
Interface
Instance
ID
1 20 Ctrl_Status_Chan BYTE
1 1 AO_Ctrl_Valve_ Flow_Chan INT
1 9 DO_Position_Chan BYTE
1 21 DO_ESD_Poll_Cnxn BOOL
1 11 DO_Relay_Chan BYTE
1 18 DO_Move_Test_ChanBOOL
1 19 AO_Analog_Output_ChanUNIT
Instance
ID
1 20Ctrl_Status_Chan BYTE
1 1 AO_Ctrl_Valve_ Flow_Chan INT
121DO_ESD_Poll_CnxnBOOL
1 10 DO_Move_Test_ChanBOOL
Attribute
Data
Type
Attribute
Data
Type
17
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Table 4.4 – Output Assembly Instance 102
Assembly
Object
Instance ID
102 Output 3 100 Channel
Data
Component
Name
Table 4.5 – Output Assembly Instance 103
Assembly
Object
Instance ID
103 Output 4 100 Channel
Data
Component
Name
Class
ID Name ID Name
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
Class
ID Name ID Name
Interface
100 Channel
Interface
Instance
ID
1 20Ctrl_Status_Chan BYTE
1 9 DO_Position_Chan BYTE
1 21 DO_ESD_Poll_Cnxn BOOL
1 18 DO_Move_ Test_Chan BOOL
Instance
ID
1 20Ctrl_Status_Chan BYTE
1 1 AO_Ctrl_Valve_ Flow_Chan INT
Attribute
Data
Type
Attribute
Data
Type
Table 4.6
Assembly
Object
Instance ID
104 Output 5 100 Channel
Data
Component
Name
Class
ID Name ID Name
Interface
100 Channel
Interface
100 Channel
Interface
Instance
ID
1 20 Ctrl_Status_Chan BYTE
1 9 DO_Position_Chan BYTE
1 21 DO_ESD_Poll_Cnxn BOOL
Attribute
Data
Type
18
Table 4.7 – Input Assembly Instance 105
Assembly
Object
Instance ID
105 Input 1 100 Channel
Data
Component
Name
Class
ID Name ID Name
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
100Channel
Interface
100Channel
Interface
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Instance
ID
1 17 DI_Actuator_
1 4 DI_Actuator_
1 6 DI_Actuator_ Alarms_Chan BYTE
1 2 DI_Pos_And_
1 5 DI_Actuator_
1 12 AI_Position_Chan INT
1 7 DI_Disc_User_ Input_Chan BYTE
1 8 DI_Read_Disc_
1 13 AI_Analog_ Input_2_Chan INT
1 14 AI_Analog_ Input_2_Chan INT
116DI_Alarms_2_
115AI_Torque_Chan INT
Attribute
Data
Type
BYTE
Faults_3_Chan
BYTE
Faults_1_Chan
BYTE
Bus_Mode_Chan
BYTE
Faults_2_Chan
BYTE
Output_Chan
BYTE
Chan
Table 4.8
Assembly
Object
Instance ID
106 Input 2 100 Channel
Data
Component
Name
Class
ID Name ID Name
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
100 Channel
Interface
Instance
ID
1 17 DI_Actuator_
1 4 DI_Actuator_
1 6 DI_Actuator_ Alarms_Chan BYTE
1 2 DI_Pos_And_
1 12 AI_Position_Chan INT
Attribute
Data
Type
BYTE
Faults_3_Chan
BYTE
Faults_1_Chan
BYTE
Bus_Mode_Chan
19
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Table 4.16 – Possible values of DI_Actuator_Faults_1_Chan
ValueDefinition
0x01Monitor Relay
0x02Valve Jammed
0x04Manual Moved
0x08Over Torque
0x10Phase Error
0x20Motor Over Temperature
0x03Monitor Relay + Valve Jammed
0x05Monitor Relay + Manual Moved
0x09Monitor Relay + Over Torque
0x11Monitor Relay + Phase Error
0x21Monitor Relay + Motor Over
0x07Monitor Relay + Valve Jammed +
0x13Monitor Relay + Valve Jammed +
0x23Monitor Relay + Valve Jammed
Temperature
Manual Moved
Phase Error
Motor Over Temperature
22
4.2.4 DI_Actuator_Faults_2_Chan
Table 4.17
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Reserved Close
Torque
Switch Fault
Open Torque
Switch Fault
Manual
Moved
Valve
Jammed
Phase Error Thermal
Overload
Table 4.18 – Possible values of DI_Actuator_Faults_2_Chan
ValueDefinition
0x01Thermal Overload
0x02Phase Error
0x04Valve Jammed
0x08Manual Moved
0x10Open Torque Switch Fault
0x20Close Torque Switch Fault
0x03Thermal Overload + Phase Error
0x05Thermal Overload + Valve Jammed
0x09Thermal Overload + Manual Moved
0x18Manual Moved + Open Torque Switch Fault
0x28Manual Moved + Close Torque Switch Fault
4.2.5 DI_Actuator_Alarms_Chan
Table 4.19
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Reserved Move Test
Active*
* Available with Revision 1 to DeviceNet board.
Not in
Remote
Close Inhibit
Active
Open Inhibit
Active
Remote ESD
Active
Local ESD
Active
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Table 4.20 – Possible values of DI_Actuator_Alarms_Chan
ValueDefinition
0x01Local ESD Active
0x02Remote ESD Active
0x04Open Inhibit Active
0x08Close Inhibit Active
0x05Local ESD Active + Open Inhibit Active
0x09Local ESD Active + Close Inhibit Active
0x06Remote ESD Active + Open Inhibit Active
0x0ARemote ESD Active + Open Inhibit Active
0x0COpen Inhibit Active + Close Inhibit Active
4.2.6 DI_Disc_User_Input_Chan
Table 4.21
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Discrete
Input #8
Discrete
Input #7
Discrete
Input #6
Discrete
Input #5
Discrete
Input #4
Discrete
Input #3
Discrete
Input #2
Discrete
Input #1
4.2.7 DI_Read_Disc_Output_Chan
Table 4.22
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Relay
Discrete
Output #7
Relay
Discrete
Output6 #
Relay
Discrete
Output #5
Relay
Discrete
Output #4
Relay
Discrete
Output #3
Relay
Discrete
Output #2
Relay
Discrete
Output #1
4.2.8 DO_Position_Chan
Table 4.23
ValueDefinition
0x00Stop
0x01Open
0x02Close
0x03
– 0xFF
Reserved
4.2.9 DO_ESD_Chan (Read Only)
Table 4.24
ValueDefinition
0x00Disable Network ESD
0x01Enable Network ESD
DO_ESD_Chan can’t be written directly via the DeviceNet network, it is Read-Only. The attribute
Enable_Broadcast_ESD_Ctrl defines if a device is part of the broadcast ESD control scheme from BitStrobe Connection or not. The resulting DO_ESD_Chan is defined in the following table.
The MX allows the standard I/O connection to assert ESD, or the broadcast bit strobe connection to
assert ESD.
23
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
7 RO DI_Disc_ User_Input_Chan BYTE Discrete input from
8 RO DI_Read_Disc_ Output_Chan BYTE Monitor state of
9 RW DO_Position_ Chan BYTE Command
10 RO DO_ESD_ Chan BOOL Command
11 RW DO_Relay_ Chan BYTE Command Energize
12 RO AI_Position_ Chan INT Current valve
13 RO AI_Analog_ Input_1_Chan INT Value of generic
14 RO AI_Analog_ Input_2_Chan INT Value of generic
15Get
(V-RO)
Bus_Mode_Chan
AI_Torque_ChanINTCurrent torque
Description of
Type
Attribute
position
BYTE Valve Status and
Control Mode
electrical faults 1
electrical faults 2
down and inhibit
information
user
relay Discrete
outputs
Stop/Open/Close
Emergency
ShutDown
relays
position
Analog input 1
Analog input 2
output
Semantics of Value
Range 0 - 1000
Section 4.2.1
Section 4.2.3
Section 4.2.4
Section 4.2.5
Section 4.2.6
Section 4.2.7
Section 4.2.8
Section 4.2.9
Section 4.2.10
Range 0 - 1000
Range 0 – 100%
Range 0 – 100%
Range 0-120%
16Get
(V-RO)
17 RO DI_actuator_ Faults_3_Chan BYTE Mechanical and
18Get/Set
(V-RW)
19Get/Set
(V-RW)
20 RW CTRL_Status_ Chan BYTE Set the status
Continued on next page
DI_Alarms_2_ChanBYTEBattery & power
supply information
electrical faults 3
DO_Move_Test_ChanBOOLMove test request0-no request
AO_Analog_Output_ChanUINTControl of generic
analog output
associated with
the various control
values
Section 4.2.13
Section 4.2.14
1-request move test
Range 0-1000%
Section 4.2.12
25
flowserve.com
26
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Table 4.31 – Continued
Data
Attribute ID Access Rule Name
21Get/Set
(V-RW)
22Get/Set
(V-RW)
23Get/Set
(NV-RW)
DO_ESD_
Poll_Cnxn
DO_ESD_
Bit_Strobe_Cnxn
Enable_
Broadcast_
ESD_Ctrl
Description of
Type
Attribute
BOOLCommand emer-
gency shutdown
from
Poll Connection
BOOLCommand emer-
gency shutdown
from
Bit-Strobe
Connection
BOOLEnable device to
be a part of the
broadcast
ESD control scheme
from Bit-Strobe
Connection
Semantics of Value
Section 4.2.9
Section 4.2.9
Section 4.2.9
0 = Disable (Default)
1 = Enable
4.4 Transducer Block Object
Table 4.32
Attribute ID Access Rule Name Data Type Description Semantics of Value
1 RW Setp_Cutoff_Dec UINT When the servo
setpoint goes below
the defined percent
of span, the position
goes to the limit
position CLOSE
2 RW Setp_Cutoff_Inc UINT When the servo
setpoint goes above
the defined percent
of span, the position
goes to the limit
position OPEN
3 RO Scaled_values_0 WORD APT/ATT scaling
information
4 RO Scaled_values_1 WORD APT (Modbus
Register 3)
5 RO Scaled_values_2 WORD ATT (Modbus
Register 4)
6 RO TP_Status_0 UINT Reserved Engineering Use
7 RO TP_Status_1 UINT Start_Position Engineering Use
8 RO TP_Status_2 UINT Stop_Position Engineering Use
9 RO TP_Status_3 UINT Num_Samples Engineering Use
10 RO TP_Status_4 UINT Max_Torque_Mid Engineering Use
11 RO TP_Status_5 UINT Max_Torque
Postion
12 RO TP_Status_6 UINT Avg_Torque Engineering Use
13 RO TP_Status_7 UINT Stop_Torque Engineering Use
14 RO TP_Status_8 UINT Max_Torque_BOT Engineering Use
15 RO TP_Status_9 UINT Maz_Torque_EOR Engineering Use
16 RO TQ_Status_0 UINT Reserved Engineering Use
17 RO TQ_Status_1 UINT MB_TQ_Close_
Avg_Last
18 RO TQ_Status_2 UINT MB_TQ_Open_Avg_
Last
19 RO TQ_Status_3 UINT MB_TQ_Open_
Peak_Last
Continued on next page
Range 0 – 1000
Default = 0
Range 0 – 1000
Default = 0
See Table 4.33
Engineering Use
Engineering Use
Engineering Use
Engineering Use
Engineering Use
Engineering Use
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Table 4.32 – Continued
Attribute ID Access Rule Name Data Type Description Semantics of Value
20 RO TQ_Status_4 UINT MB_TQ_Open_
Breakout_Last
21 RO TQ_Status_5 UINT MB_TQ_Close_
Breakout_Last
22 RO TQ_Status_6 UINT MB_TQ_Open_
Ending_Last
23 RO TQ_Status_7 UINT MB_TQ_Close_
Ending_Last
24 RO TQ_Status_8 UINT MB_TQ_Close_
Peak_Last
25 RO TQ_Status_9 UINT MB_TQ_Open_
Peak_Last
Engineering Use
Engineering Use
Engineering Use
Engineering Use
Engineering Use
Engineering Use
26 RO TQ_Status_10 UINT MB_TQ_Open_
27 RO TQ_Status_11 UINT MB_TQ_Close_
28 RO TQ_Status_12 UINT MB_TQ_Open_
29 RO TQ_Status_13 UINT MB_TQ_Close_
30 RO TQ_Status_14 UINT MB_TQ_Close_
31 RW Travel_Limit_Low UINT Lower limit of the
32 RW Travel_Limit_Up UINT Upper limit of the
33 RW Valve_Maint_ Date SHORT-
STRING
34 RW Valve_Serial_Num SHORT-
STRING
35 RO Valve_status_0 WORD Requested relay
36 RO Valve_status_1 WORD Status Register
37 RO Valve_status_2 WORD Fault Register
38 RO Valve_status_3 WORD Digital Output
39 RO Valve_status_4 WORD Digital Input #1
40 RW Valve_status_5 WORD Digital Input #2
Continued on next page
Breakout_Ref
Breakout_Ref
Ending_Ref
Ending_Ref
Peak_Ref
valve position in
percent of travel
span
valve position in
percent of travel
span
Date of last valve
maintenance
Serial number of
the valve belonging
to the positioner of
electronic device
channel value
– Modbus Register
9
– Modbus Register
10
Register – Modbus
Register 11
Register – Modbus
Register 12
Register – Modbus
Register 13
Engineering Use
Engineering Use
Engineering Use
Engineering Use
Engineering Use
Range 0 – 1000
Default = 0
Range 0 – 1000
Default = 0
String length is limited
to 16 char. Default = 0
(empty)
String length is limited
to 16 char. Default = 0
(empty)
Default = 0
Default = 0
Default = 0
Default = 0
Default = 0
Default = 0
27
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Table 4.32 – Continued
Attribute ID Access Rule Name Data Type Description Semantics of Value
41 RW Valve_Type USINT Type of valve 0 = linear moving
42 RO Actuator_Type USINT Type of actuator 0 = electropneumatic
43 RO Diagnostic_ Values_0 UINT Reserved Engineering Use
44 RO Diagnostic_ Values_1 UINT Main Voltage Engineering Use
45 RO Diagnostic_ Values_2 UINT Actuator Position Engineering Use
46 Diagnostic_ Values_3 UINT Analog input #1 Engineering Use
47 Diagnostic_ Values_4 UINT Analog Input #2 Engineering Use
48 RW Tag_Name SHORT-
ATT Polarity
0 = high
value 4 mA
1 = high
value 20 mA
Analog
Torque
Transmitter
(ATT) 0
= ATT
Disabled 1 =
ATT Enabled
APT Polarity
0 = high
value 4 mA
1 = high
value 20 mA
Analog
Position
Transmitter
(APT) 0
= APT
Disabled 1 =
APT Enabled
Table 4.34
Bit 15 - 11 Bit 10 - 9 Bit 3
Unused Scaling 0 =
0 – 100 1 =
0 – 255 2 =
0 -4095 3 =
Reserved
Unused
4.4.1 Identity Object Instance Attributes
Table 4.35 – Identity Object Instance Attributes
Attribute
ID
1Get
2Get
Access Rule NameData Type
Vendor IDUINTIdentification of
(NV-RO)
Device TypeUINTIndication of general
(NV-RO)
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Description of
Attribute
each vendor by
number
type of product
Semantics of Value
966 (3C6hex)
(Note 1)
00hex
(Generic Device)
3Get
(NV-RO)
4Get
(NV-RO)
5Get
(V-RO)
6Get
(NV-RW)
7Get
(NV-RW)
8Get
(V-RO)
10Get/Set
(NV-RW)
100Get
(V-RO)
Product CodeUINTIdentification of a
Revision STRUCT ofRevison of the item
Major RevisionUSINTMajor Revision of
Minor Revision USINTMinor Revision of
StatusWORDSummary status of
Serial NumberUDINTSerial number of
Product NameSHORT_
STRING
StateUSINTPresent state
Heartbeat IntervalUSINTThe nominal interval
EEPROM FailureBOOLResult of EEPROM
particular product
of an individual
vendor
the Identity Object
represents
DeviceNet
Limitorque Interface
DeviceNet
Limitorque Interface
device
device
Human readable
identification
of the device as
represented by
the state transition
diagram
between heartbeat
messages in
seconds
checksum
verification
19800 (4D58hex)
(Note 2)
1.1
(Note 3)
(Note 4)
(Note 5)
”Flowserve MX”
(Note 6)
The default value
is 0. Zero disables
transmission of the
heartbeat message.
0 = EEPROM contents
is o.k.
1 = EEPROM contents
may be defective due
to checksum error
The further optional attributes
Configuration Consistency Value (Attribute ID 9)
•
Active Language (Attribute ID 11)
•
Supported Language List (Attribute ID 12)
•
29
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
International Product Name (Attribute ID 13)
•
Semaphore (Attribute ID 14)
•
are not supported by DeviceNet Limitorque Interface.
Some of the instance attributes do not have any external interfaces, these values are managed directly in
the DeviceNet Slave Software.
NOTE 1:
The Vendor ID is managed by the ODVA. Flowserve has already obtained a valid Vendor ID.
The Vendor ID will be assigned during compile time as a constant of the DeviceNet Slave Software and
stored in Flash-Memory of the DeviceNet Limitorque Interface. Thus it cannot be altered during runtime.
NOTE 2:
The Product Code of the DeviceNet Limitorque Interface has already been assigned by
Flowserve. It typically maps to a catalog or model number. The Product Code will be assigned during
compile time as a constant of the DeviceNet Slave Software and stored in Flash-Memory of the
DeviceNet Limitorque Interface. Thus it cannot be altered during runtime.
NOTE 3:
The Revision of the DeviceNet Limitorque Interface. Has already been assigned by Flowserve.
It typically links to the revision control system of a company. The format of the revision is Major.Minor,
starting with 1.1, because 0 is not allowed in CIP. The default value for this attribute is therefore 0x0101.
The revision must match the entry of the EDS-File delivered with the DeviceNet Limitorque Interface.
The Revision will be assigned during compile time as a constant of the DeviceNet Slave Software and
stored in Flash-Memory of the DeviceNet Limitorque Interface. Thus it cannot be altered during runtime.
30
NOTE 4:
The Status represents the current status of the device. Important here are the bits 8 to 11
which make faults visible to the user.
NOTE 5:
The Serial Number is used in conjunction with the Vendor ID to form a unique identifier for
each device. Flowserve is responsible for guaranteeing the uniqueness of the serial number across all of
its devices. The SMT Main Board will initialize the DeviceNet Limitorque Interface with data every time a
loss of communication condition between the DeviceNet Limitorque Interface and the SMT Main Board
had occurred. A part of this initialization data will be a unique board ID coming from the SMT Main
Board. Upon reception of this unique board ID from the SMT Main Board, the DeviceNet Limitorque
Interface will construct a Serial Number value. The transducer/spi software will then get the currently
stored serial number value from the DeviceNet stack, compare it to the one just constructed based on
the data from the main board, and if different, set the new value in the Identity Object / EEPROM. Also,
if the values were different, the transducer / spi software will then request that the DeviceNet board
reset to it’s “factory default” non-volatile condition (exception: the serial number in EEPROM is not
overwritten again).
NOTE 6:
The Product Name should represent a short description of the product/product family
represented by the product in attribute 3. It is limited to 32 characters. The product name should default
to “Limitorque”. However, at “spi initialization time”, the product name attribute can be updated by some
kind of API function call by the transducer / spi driver.
4.4.2 Behavior
Table 4.36 – Behavior
EventSourceDescription
Power AppliedDeviceNet Limitorque Interface Connect DeviceNet bus power
Passed TestsDeviceNet Limitorque Interface No errors detected during internal selftest
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
FailedTestsDeviceNet Limitorque Interface One or more of the following errors have been
ActivatedSMT Main BoardIs_Active-Flag is TRUE
DeactivatedSMT Main BoardIs_Active-Flag is FALSE OR
Minor Fault SMT Main BoardConditions that can cause this event are e.g.
Major Recoverable FaultSMT Main BoardConditions that can cause this event are e.g.
Major Unrecoverable FaultDeviceNet Limitorque Interface Internal Diagnostic Fault detected e.g.
detected during self-test of the DeviceNet
Limitorque Interface e.g.
- FLASH Checksum Error
- RAM Memory Test Error
EEPROM Checksum Error
valve jam, overtemp, overtorque and phase loss.
This event is triggered if Attribute DI_Actuator_
Faults_1_Chan in Channel Object Class is ≠
0x00
communication fault, power fault or Limiguard
fault of the SMT Main Board.
This event is triggered if Attribute DI_Actuator_
Faults_3_Chan in Channel Object Class is ≠
0x00
- Receive Queue Overrun
- Transmit Queue Overrun
- CAN Controller Overrun
4.4.3 DeviceNet Object Instance Attributes
Table 4.37 – DeviceNet Object Instance Attributes
Attribute
ID
1Get/Set
2Get/Set
3Get/Set
4Get/Set
5Get
6Get
7Get
8Get
9Get
100Get/Set
Access Rule Name
(NV-RW)
(NV-RW)
(V-RW)
(V-RW)
(V-RO)
(V-RO)
(V-RO)
(NV-RW)
(NV-RW)
(NV/RW)
MAC IDUSINTNode AddressRange 0 – 63
Baud RateUSINTBaud RateRange 0 – 2
BOIBOOLBus-Off Interrupt
Bus-Off CounterUSINTNumber of times
Allocation InformationSTRUCT
Allocation Choice ByteBYTESee [2] Chapter 3-5
Master’s MAC IDUSINTMAC ID of Master
MAC ID Switch ChangedBOOLThe Node Address
Baud Rate Switch ChangedBOOLThe Baud Rate
MAC ID Switch ValueUSINTActual Value of
Baud Rate Switch ValueUSINTActual Value of
AutobaudBOOLEnable/Disable
Data
Type
of
Description of
Attribute
CAN went to the
bus-off state
(from allocate)
Switch(es) have
changed since last
power-up/reset
Switch(es) have
changed since last
power-up/reset
Node Address
Switch(es)
Baud Rate
Switch(es)
Autobaud Detection
Semantics of Value
see also
Chapter 5.2.1
0 = No Change
1 = Change since
last power-up
or reset
0 = No Change
1 = Change since
last power-up
or reset
Range 0 – 99
Range 0 – 9
0 = Disable
1 = Enable (default)
31
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
NOTE 1: At boot time of the DeviceNet Limitorque Interface the values stored in non-volatile memory
are used. The SMT Main Board could at any time send new values via SPI.
The other instance attributes do not have any external interfaces, these values are managed in the
protocol stack of the DeviceNet Slave Software.
The further optional attribute Quick Connect (Attribute ID 10) is not supported by DeviceNet Limitorque
Interface.
32
4.4.4 Discrete Input Point Object – Class ID 8 (08
hex
)
The Discrete Input Point Object is used to provide an interface to a subset of the discrete inputs of the
MX.The Discrete Input Point Object is implemented with 15 instances described in Table 3.1-25, so that
each of the selected discrete inputs of the MX is connected to one instance.
The purpose of this object is to have a SINGLE-BIT access to the discrete inputs from user and to
monitor the state of relay discrete outputs of the MX via the DeviceNet network for test and diagnostic
purposes.
The Discrete Input Point Object is just another representation of the selected discrete input data in the
Channel Interface Object Instance Attribute 7 (DI_Disc_User_Input_Chan) and Attribute 8 (DI_Read_
Disc_Output_Chan) see Chapter 3.2.1.2.
Table 4.38 – Discrete Input Point Object
Instance IDChannel Interface ObjectSource
1Instance Attribute 7, Bit 0DI_Disc_User_Input_Chan
2Instance Attribute 7, Bit 1DI_Disc_User_Input_Chan
3Instance Attribute 7, Bit 2DI_Disc_User_Input_Chan
4Instance Attribute 7, Bit 3DI_Disc_User_Input_Chan
5Instance Attribute 7, Bit 4DI_Disc_User_Input_Chan
6Instance Attribute 7, Bit 5DI_Disc_User_Input_Chan
7Instance Attribute 7, Bit 6DI_Disc_User_Input_Chan
8Instance Attribute 7, Bit 7DI_Disc_User_Input_Chan
9Instance Attribute 8, Bit 0DI_Read_Disc_Output_Chan
10Instance Attribute 8, Bit 1DI_Read_Disc_Output_Chan
11Instance Attribute 8, Bit 2DI_Read_Disc_Output_Chan
12Instance Attribute 8, Bit 3DI_Read_Disc_Output_Chan
13Instance Attribute 8, Bit 4DI_Read_Disc_Output_Chan
14Instance Attribute 8, Bit 5DI_Read_Disc_Output_Chan
15Instance Attribute 8, Bit 6DI_Read_Disc_Output_Chan
Discrete Input #1
Discrete Input #2
Discrete Input #3
Discrete Input #4
Discrete Input #5
Discrete Input #6
Discrete Input #7
Discrete Input #8
Relay Discrete Output #1
Relay Discrete Output #2
Relay Discrete Output #3
Relay Discrete Output #4
Relay Discrete Output #5
Relay Discrete Output #6
Relay Discrete Output #7
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
4.4.5 Discrete Output Point Object – Class ID 9 (09
The Discrete Output Point Object is used to provide an interface to a subset of the discrete outputs of
the MX. The implementation of this object follows the guidelines of [1] Chapter 5-10.
The Discrete Output Point Object is implemented with 7 instances described in Table 3.1-29, so that
each of the selected discrete outputs of the MX is connected to one instance.
The purpose of this object is to have a SINGLE-BIT access to the relays of the MX via the DeviceNet
network for test and diagnostic purposes.
The Discrete Output Point Object is just another representation of the selected discrete output data in
the Channel Interface Object Instance Attribute 11 (DO_Relay_Chan) see Chapter 3.2.1.2.
Table 4.39 – Discrete Output Point Object
Instance IDChannel Interface ObjectSource
1Instance Attribute 11, Bit 0DO_Relay_Chan User Output AS-1
2Instance Attribute 11, Bit 1DO_Relay_Chan User Output AS-2
3Instance Attribute 11, Bit 2DO_Relay_Chan User Output AS-3
4Instance Attribute 11, Bit 3DO_Relay_Chan User Output AS-4
5Instance Attribute 11, Bit 4DO_Relay_Chan User Output AR-1
6Instance Attribute 11, Bit 5DO_Relay_Chan User Output AR-2
7Instance Attribute 11, Bit 6DO_Relay_Chan User Output AR-3
4.4.6 Analog Input Point Object – Class ID 10 (0A
The Analog Input Point Object is used to provide an interface to a subset of the analog inputs of the MX.
The implementation of this object follows the guidelines of [1] Chapter 5-11.
hex
hex
)
)
The Analog Input Point Object is implemented with 2 instances described in Table 3.1-33, so that each
of the selected analog inputs of the MX is connected to one instance.
The purpose of this object is to have a SINGLE access to the generic analog inputs of the MX via the
DeviceNet network for test and diagnostic purposes.
The Analog Input Point Object is just another representation of the selected analog input data in
the Channel Interface Object Instance Attribute 13 (AI_Analog_Input_1_Chan ) and Attribute 14
(AI_Analog_Input_1_Chan) see Chapter 3.2.1.2.
4.4.7 Analog Output Point Object – Class ID 11 (0B
The Analog Output Point Object is used to provide an interface to a subset of the analog outputs of the
MX. The implementation of this object follows the guidelines of [1] Chapter 5-12.
The Analog Output Point Object is implemented with 1 instance described in Table 3.1-37, so that each
of the selected analog outputs of the MX is connected to one instance.
The purpose of this object is to have a SINGLE access to the generic analog outputs of the MX via the
DeviceNet network for test and diagnostic purposes.
hex
)
33
The Analog Output Point Object is just another representation of the selected analog output data in the
Channel Interface Object Instance Attribute 19 (AO_Analog_Output_Chan) see Chapter 3.2.1.2.
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
Table 4.41 – Analog Output Point Object
Instance IDChannel Interface ObjectSource
1Instance Attribute 19AO_Analog_Output_CHAN
4.4.8 MAC ID
The MX-DeviceNet unit may have the MAC ID set by one of two different methods. The first is the MX
LCD display. The other is via the DeviceNet bus.
4.4.9 Baud Rate
The MX-DeviceNet unit may have the Baud Rate set by one of two different methods. The first is the MX
LCS display. The other is via the DeviceNet bus.
4.5 Network Management
4.5.1 Offline Connection Set
NOTE: The DeviceNet Limitorque Interface supports Offline Connection Set. The Offline Connection Set
is used to bring back a node to the DeviceNet bus which is in the Communication Fault State. This state
will be entered in the case of a duplicate MAC ID error is detected.
4.5.2 Device Heartbeat Message
The DeviceNet Limitorque Interface supports Device Heartbeat message. This message broadcasts the
current state of the DeviceNet Limitorque Interface. Table 4.42 shows the format of the data field of the
Device Heartbeat Message.
Table 4.42 – Format of the Device Heartbeat Message
(0)
6(0) because the Configuration Consistency Value (Attribute 8 of the Identity Object Instance) is not
7
EV Event Flag, zero (0)
SF System Fault, a fault in the device caused by DeviceNet bus interaction (e.g. connection timeout).
This flag is set, when a system fault is present. This DeviceNet Limitorque Interface flag is set when a
connection times out.
UF User Fault, a fault in the device caused by user interaction. This flag is set when a user fault is
present. The conditions under which is set are vendor specific. This DeviceNet Limitorque Interface flag
is not used and is zero (0).
supported by the DeviceNet Limitorque
EV
(0)
SFUF
(0)
DF
34
DF Device Fault, an internal fault in the device not caused by user or bus interaction (e.g. hardware
fault). This flag is set when a device fault is present. This DeviceNet Limitorque Interface flag is set
under the following conditions:
(DI_Actuator_Faults_1_Chan ≠ 0) OR (DI_Actuator_Faults_3_Chan ≠ 0)•
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
The Device Heartbeat Message is triggered by the Identity Object Instance Attribute Heartbeat Interval
(Attribute ID 10). For this, the Heartbeat Interval has to be set to the time interval of the Device
Heartbeat Message in seconds.
4.5.1 Device Shutdown Message
The DeviceNet Limitorque Interface supports the Device Shutdown Message. The DeviceNet Limitorque
Interface produces this message when it transitions to the offline state. Table 4.43 shows the format of
the data field of the Device Shutdown in Message.
Table 4.43 – Format of the Device Shutdown Message
Byte
Offset
0DeviceNet Protocol Specific
1
2Class ID
3
4Instance ID
5
6Shutdown Code
7
76543210
Range 200hex – 2FFhex
For the DeviceNet Limitorque Interface, the Class ID and the Instance ID of this message depends on the
originator of the Device Shutdown Message, e.g. after Reset-Service performed on the Identity Object,
Class ID 1 and Instance 1, a Device Shutdown Message is sent.
For application purposes 2 Bytes of the Device Shutdown Message are reserved for the Shutdown
Code. Then vendor specific range of this code is 200 – 2FF. Table 4.44 lists all Shutdown Codes of the
DeviceNet Limitorque Interface.
Table 4.44 – Device Shutdown Codes
Class IDInstance ID
114Remote Reset: Reset service of the identity Object
314Remote reset: Setting of the MAC ID via Attribute 1 of the DeviceNet
005Internal diagnostic fault: An internal diagnostic fault has caused the
004DeviceNet Limitorque Interface will be reset because SMT Main Board
10210x201DeviceNet Limitorque Interface will be reset because SMT Main Board
10210x202DeviceNet Limitorque Interface will be reset because SMT Main Board
Shutdown
Code
Causes of Shutdown
Object
service to shut down. Reason for this can be an overrun of the CAN
transmit queue, CAN receive queue or CAN Controller receive buffer
signal RESET is active.
has changed MAC ID via LCD
has changed Baud rate via LCD
4.6 Configuration Confirmation
DNFU operation cannot be verified until the complete DeviceNet system is operational. However, routine
checks can be performed to verify many functions.
4.6.1 Checking Connections
Verify that all connections, including data wires, shield ground, are in accordance with MX wiring
diagrams and DNFU diagrams in Section 3.1.2, Network Cable Preparation.
35
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
YES
NO
CHANGE
DEVICENET?
(ON)
YES
NO
STATUS
(OFF)-OK?
(CLOSE)
(OPEN)
(STOP)
(POSITION)
YES
NO
ESD ACTION
(IGNORE)-OK?
(CLOSE)
(OPEN)
(STOP)
(POSITION)
YES
NO
COMMLOSSACTION
(NONE)-OK?
(0-4095)
YES
NO
COMMLOSSDELAY
(60 SEC)-OK?
(0-100%)
**
YES
NO
MOVE TO
XXX% OPEN
(0-100%)
YES
NO
MOVE TO
XXX% OPEN
(125K)
(250K)
(500K)
(NET CTRL)
YES
NO
BAUD RATE
AUTO-OK?
(0-63)
YES
NO
DNET ADDRESS
NET CTRL-OK?
(0-255)
(0-4095)
YES
NO
ANALOG SCALE
(0-100)-OK
YES
NO
CHANGE PROP
DEAD BAND?
(1-100%)
YES
NO
PROP BAND
(8%)-OK?
(1-?%)
YES
NO
DEADBAND
(2%)
* If POSITION is chosen, as action,
this menu will appear.
YES
NO
CHANGE
DEVICENET?
(ON)
YES
NO
STATUS
(OFF)-OK?
(CLOSE)
(OPEN)
(STOP)
(POSITION)
YES
NO
ESD ACTION
(IGNORE)-OK?
(CLOSE)
(OPEN)
(STOP)
(POSITION)
YES
NO
COMM LOSS ACTION
(NONE)-OK?
(0-4095)
YES
NO
COMM LOSS DELAY
(60 SEC)-OK?
(0-100%)
**
YES
NO
MOVE TO
XXX% OPEN
(0-100%)
YES
NO
MOVE TO
XXX% OPEN
(125K)
(250K)
(500K)
(NET CTRL)
YES
NO
BAUD RATE
AUTO-OK?
(0-63)
YES
NO
DNET ADDRESS
NET CTRL-OK?
(0-255)
(0-4095)
YES
NO
ANALOG SCALE
(0-100)-OK
YES
NO
CHANGE PROP
DEAD BAND?
(1-100%)
YES
NO
PROP BAND
(8%)-OK?
(1-?%)
YES
NO
DEADBAND
(2%)
* If POSITION is chosen, as action,
this menu will appear.
4.6.2 View Settings
Refer to Bulletin LMAIM1306/2306, MX Installation and Operation Manual to access the “VIEW
SETTINGS” menu. Verify the settings as follows:
5 View DeviceNet Status
Figure 5.1 – DeviceNet Screens
36
VIEW DNET STATUS?
This selection permits the User to view pertinent information which summarizes the status of the
DeviceNet option board.
VIEW MODULE STATUS?
Answer "YES" to determine status of individual DN board within the actuator.
•
Configuration choices are:
•
"OFF" = board installed but turned off
•
“OPERATIONAL” – The device is operating in a normal condition.
•
"STANDBY" = The device needs commissioning due to configuration missing, incomplete or incorrect.
•
"RECOVERABLE FAULT" = Conditions that can cause this event are e.g. communication fault, power
•
fault or Limigard fault of the SMT Main Board. Device may need resetting.
"UNRECOVERABLE FAULT" = Internal Diagnostic Fault detected e.g.
•
•
•
•
Device may need replacing.
•
"SELF TESTING" = The device is in self-test mode.
•
VIEW NETWORK STATUS?
Answer “YES” to determine status of DN network.
"NOT ON LINE" = Device is not on-line.
•
Receive Queue Overrun
Transmit Queue Overrun
CAN Controller Overrun
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
100% OPEN
STATUS OK
Remote
Local
or
100% OPEN
DNET COMM LOSS
Remote
Local
or
•
The device has not completed the self test yet.
•
The device may not be powered, look at Module Status Display.
•
"ONLINE" = Device is on-line but has no connections in the established state.
•
The device has passed the SELF test, is on-line, bus has no established connections to other
nodes.
•
For a Group 2 Only device it means that this device is not allocated to a master.
•
For a UCMM capable device it means that the device has no established connections.
•
"CONNECTED" = The device is on-line and has connections in the established state.
•
For a Group 2 Only device it means that the device is allocated to a Master.
•
For a UCMM capable device it means that the device has one or more established connections.
•
"CONN TIMEOUT" = One or more I/O Connections are in the Timed-Out state.
•
"COMM FAULT" = Failed communication device. The device has detected an error that has rendered it
incapable of communicating on the network (Duplicate MAC ID, or Bus-off).
•
"ID COM FLT REQ" = A specific Communication Faulted device. The device has detected a Network
Access error and is in the Communication Faulted state. The device has subsequently received and
accepted an Identify Communication Faulted Request Long Protocol message.
5.1 Checking the Normal Display
Place the selector switch in “LOCAL” or “REMOTE” position. The valve position will be indicated at the
top of the LCD. “STATUS OK” or “DNET COMM LOSS” should be indicated at the bottom of the LCD
display.
If “STATUS OK” is displayed, the DNFU is communicating with the DeviceNet network.
If “DNET COMM LOSS” is displayed, no communication is occurring. This could be due to a number of
factors, including problems with the host DeviceNet system and/or network. Check all local connections
and configurations. Confirm that the host is connected, configured for baud rate, protocol to match
DeviceNet, and operational. See also Section 7, Troubleshooting.
Figure 5.2
37
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
5.2 EDS File
The DeviceNet Limitorque Interface can be configured using Rockwell Automation RSNetWorx for
DeviceNet and an EDS-File. Table 5.1 shows a list of all supported parameters.
MX Installation and Operation Manual: Limitorque Bulletin LMAIM1306/2306
Protection, Control and Monitoring Features of MX Electric Actuators: Limitorque Bulletin
LMABR1300/2300
MX Maintenance and Spare Parts Manual: Limitorque Bulletin LMAIM1314/2314
ODVA Planning and Installation Manual available from ODVA.
7 Troubleshooting
Refer to Section 10, Wiring Diagram.
1. With power off and network disconnected, verify continuity between A1, A2 and A1*, A2*.
2. With power applied and network disconnected, verify 0.2 to 0.45 VDC between A1, A1* and A2,
A2*.
3. Confirm that a jumper cable is installed between the grounding lug and terminal 30.
Verify proper setup for MX DeviceNet.
4. MPC (modulating position control) must be OFF.
5. ESD must be configured for desired function and properly wired.
6. OPEN INHIBIT must be configured for desired function and properly wired.
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
7. CLOSE INHIBIT must be configured for desired function and properly wired.
8. Remote control is not selected if not in use. Properly wired if selected.
9. Confirm there are no duplicate DeviceNet addresses.
10. Confirm that ground is at one end only per network cable segment.
11. Confirm protocol, baud rate
Main power supply must be within +/- 10% of nominal unit power rating at all times. Refer to nameplate
for voltage.
UPS of 24 V DC must be within +/- 10% at all times.
7.1 Workmanship
The Limitorque MX is non-intrusive which facilitates ease of configuration without removal of the
controls cover. Removal of the controls cover without permission from Flowserve can void the warranty.
Practice all plant and safety codes and standards. Failure to follow instructions can result in personal
injury and/or property damage.
Do NOT remove covers of Division 1 units with power applied to prevent the possible ignition of
hazardous atmospheres.
Qualified technicians should perform all service. Dangerous voltages may be present on the circuit
boards and terminations.
Use extreme caution when working around power input cables. These cables have potentially lethal
voltages on them.
Replace fuses only with specified parts for continued safe operation.
Have qualified personnel verify all wiring and connections against vendor drawings prior to energizing
the equipment. Incorrect wiring and/or connections can result in equipment damage.
CAUTION: There is potential to cause electrostatic damage to electronic components. Before
a
handling electronic components, ensure that you are discharged of static electricity by briefly
touching a grounded metal object.
The circuit boards in the MX DeviceNet contain components that are subject to damage from electrostatic discharge (static electricity). The following precautions and procedures are recommended when
handling circuit boards and components. Failure to observe these practices when handling and shipping
circuit board products may void your warranty.
Keep plastics and other materials prone to the buildup of electrostatic charges (static electricity) away
•
from boards, components, and work area.
Avoid synthetic or wool clothing; wear cotton or cotton blend materials. Keep components and circuit
•
boards away from clothing and hair.
Discharge static electricity on your body by touching and momentarily holding a grounded metal
•
object before handling electronic components. This is especially important after walking across
carpeted areas.
Handle components in the field as little as necessary.
•
Handle components only by the edges, and avoid contact with leads, circuits, or connectors.
•
39
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
•
Do not touch the surface of the printed circuit board, the connectors, or the components with conductive devices or with your hands.
•
Always place the component or board into an anti-static protective bag for transportation or storage.
•
Transport all static-sensitive components only in static-shielding carriers or packages. Place static
awareness labels on all components to prevent removal from static-shielding container during transit.
•
Handle all static-sensitive components at a static-safe work area including floor mat, wrist strap, air
ionizer, ground cord, and conductive table mat.
•
Do not subject components to sliding movements over any surface, at any time.
8 How to Order Parts
To order parts or obtain further information about your Limitorque DeviceNet field unit, contact your
local Limitorque distributor sales office, or:
Flowserve Corporation Flow Control Division
Limitorque Actuation Systems
5114 Woodall Road
P.O. Box 11318 Lynchburg, VA 24506-1318
Phone (434) 528-4400
Fax (434) 845-9736
To find the Limitorque distributor or sales office near you, go to http://www.limitorque.com
All inquiries or orders must be accompanied by the following information supplied on the actuator
nameplate:
•
Unit size
•
Order number
•
Serial number
9 Regulatory Information
The Flowserve Limitorque DeviceNet board has been tested in accordance with the listed specifications
and complies with European Directive 89/336 EEC, EMC Directive and 73/23 EEC, Low Voltage Directive;
EN 55011:1998 + A2:2001
EN 61000-6-2:2001
40
10 Wiring Diagram
DEVICENET
BOARD
REVERSING
CONTACTOR
CLOSE
STOP
OPEN
DIG COM #1-Ve
0V AC
110V AC
24V DC +Ve
0V DC
24V DC +Ve
0V DC
5
6
7
9
8
51
10
12
11
14
13
37
38
L1
L2
L3
FS1
FS2
FS3
LIMIGARD
POSITION
SENSOR
1
2
3
4
31
32
42
43
AS1
AS2
AS3
AS4
"CLOSE"
POSITION
"OPEN"
POSITION
"CLOSE"
POSITION
"OPEN"
POSITION
17
18
19
SHOWN
WITH POWER
SUPPLY OFF
CONTROL PANEL
MOTOR
PE
3 PHASE
SUPPLY
TORQUE
SENSOR
MONITOR RELAY
REMOTE
LOCAL
S
T
O
P
(YES)
OPEN
CLOSE
(NO)
CONTROL
SUPPLY
CIRCUIT SHOWN WITH VALVE IN FULLY CLOSED POSITION AND WITH POWER OFF
STATUS FEEDBACK
OUTPUT SWITCHES
VIEW OF
TERMINAL
BLOCK
REMOTE
LOCAL
S
T
O
P
(YES)
OPEN
CLOSE
(NO)
ANALOG INPUT
8.EXACT END POSITION INDICATION
1.FUSES
FSI (PRIMARY)
FS2 (PRIMARY)
3.MAXIMUM EXTERNAL LOAD
TERMINALS 13 AND 14 (24V DC) - 10W MAX. EXT. LOAD
TERMINALS 11 AND 12 (110V AC) - 0V MAX EXT. LOAD
SUITABLE FOR DIGITAL INPUTS
ONLY, PROTECTED BY FS3.
5.CONTROL SIGNAL DURATION
REQUIRED CONTROL SIGNAL
DURATION = 250 - 350ms.
6.STATUS FEEDBACK OUTPUT SWITCHES
CLOSE
CLOSING
MID-TRAVEL
OPENING
OPEN
STOPPED
9.DEFAULT SETTING
ACTUATORS ARE NORMALLY SHIPPED WITH DEFAULT
SETTINGS AS SHOWN ON THIS DIAGRAM. THE "AS"
CONTACTS ARE SHOWN WITH VALVE IN FULLY CLOSED
POSITION. SEE CONTACT DEVELOPMENT BELOW.
7.CONTACT RATINGS
VALVE MOVING
VALVE JAMMED
MOTOR OVERTEMP
OVERTORQUE
CLOSE TORQUE SW
OPEN TORQUE SW
CLOSE INHIBIT
OPEN INHIBIT
ESD SIGNAL
NO ANALOG SIGNAL
LOST PHASE
LIMIGARD ACTIVE
HARDWARE FAILURE
LOCAL SELECTED
LOCAL STOP/OFF
MANUAL OVERRIDE
REMOTE SELECTED
OUTPUT SWITCH CONTACT DEVELOPMENT
VALVE POSITION
FULL
CLOSE
FULL
OPEN
FUNCTION
CLOSE LIMIT
AS4
OPEN LIMIT
AS3
CLOSE LIMIT
OPEN LIMIT
AS1
AS2
OUTPUT
SWITCH
ON TORQUE-SEATED VALVES THE LCD AND "AS"
CONTACTS, CONFIGURED AS END OF TRAVEL LIMITS,
AUTOMATICALLY PROVIDE EXACT END OF POSITION
INDICATION.
600V AC, 1A, 200kA Int RATING,
FAST ACTING 10.3 x 38.1mm TUBE.
FS3 (SECONDARY) - 0.1A, 250V, TIME DELAY,
5 x 20mm, GLASS TUBE
AS1,2,3 AND 4 - 5.0 AMPS AT 125V AC, 30V DC (250V AC-CENELEC)
MONITOR RELAY - 5.0 AMPS AT 250V AC, 30V DC
NOTES
TRANSFORMER TAPPING OPTIONS
TYPE
TAPPING
A
220V
380V
415V
460V
B
TYPE
TAPPING
115V
220V
525V
575V
TYPE
TAPPING
A
220V
380V
415V
460V
B
TYPE
TAPPING
115V
220V
525V
575V
TRANSFORMER TAPPING OPTIONS
DEFAULT SETTING
SEE NOTE 6 AND 9
2.AUXILIARY INPUT
AUXILIARY INPUT
SEE NOTE 2
52
21
DIG COM #2-Ve
DIG COM #3-Ve
2 mA / 24V DC
MAX LOAD - 10 mA / 110V AC
MAXIMUM "OFF" 5.0V AC/DC
SIGNAL THRESHOLD - MINIMUM "ON" 19.2V AC/DC
4.REMOTE INPUTS
REMOTE
INPUTS
SEE NOTE 4
INPUT 2
INPUT 1
INPUT 0
120 OHM, 1/4W TERMINATION RESISTORS MUST BE CONNECTED
AT EACH SEGMENT END.
SHIELDS TOGETHER TO ENSURE PROPER SHIELDING OF ENTIRE NETWORK.
ON EACH SEGMENT. CONNECT REMAINING INDIVIDUAL NETWORK CABLE
WIRING IS TO CONNECT SHIELD TO TERMINAL 48 FOR ONLY ONE UNIT
AND CHASSIS GROUND FOR SURGE PROTECTION. PREFERRED NETWORK
CUSTOMER IS REQUIRED TO CONNECT WIRE BETWEEN TERMINAL 30
SEE NOTE 11
RECOMMENDED DEVICENET CABLE IS BELDEN 3084A OR EQUAL.
15
16
48
SHIELD
NETWORK DATA (+)
NETWORK DATA (-)
0% OPEN
STATUS OK
1
2 3 4 5
6 7
8
9
101
1
1
2
1
3
1
4
1
5
1
6
1
7
1
8
1
9
2
0
2324252
6
2
7
2
8
2
9
3
0
3
2
3
3
3
4
3
1
3536373
8
3
9
4
0
4
1
4
2
4
3
4
4
4
5
4
6
4
7
4
8
4
9
5
0
5
1
5
2
2
2
2
1
L1
L2L3
GROUNDING
LUG
0% OPEN
STATUS OK
NETWORK +24V
NETWORK 0V
29
41
39
28
-ve ANALOG COMMON
+ve ANALOG INPUT-1
+ve ANALOG INPUT-2
40
(MODUTRONIC)
STANDARD SIGNAL 4-20 mA
INPUT IMPEDANCE = 250 OHMS
INPUT CAPACITACNE = 0.1uf±30%
99% ACCURACY
CONFIGURABLE SCALING
10.ANALOG INPUT
BACK-UP 24v DC UPS POWER MAY BE CONNECTED
TO TERMINAL'S 37 AND 38. MAXIMUM CURRENT
DRAW IS 1 AMP. THIS POWERS ALL CONTROLS FOR
LOCAL INDICATION AND CONFIGURATION. ANALOG OUTPUT AND ALARM
RELAYS SUPPLIED WILL BE POWERED FOR UNITS MANUFACTURED
SUBSEQUENT TO Q1/2003. REVERSING CONTACTOR WILL NOT
BE POWERED. CUSTOMER SHOULD SUPPLY EXTERNAL FUSE AS
REQUIRED BY LOCAL ELECTRICAL CODES.
THE ACTUATOR STATUS CONTACTS (AS) AND ALARM RELAYS (AR)
MAY BE INDIVIDUALLY CONFIGURED AS NORMALLY OPEN OR NORMALLY
CLOSED LATCHED CONTACTS OR AS BLINKER CONTACTS TO INDICATE
ONE OF THE FUNCTIONS LISTED BELOW:
BLU
BLK
WHT
RED
11.DEVICENET
EGND
30
INPUTS 0,1,2 ARE FIELD CONFIGURABLE (FIRMWARE VERSION 04\08.00 OR LATER)
FOR CLOSE INHIBIT, OPEN INHIBIT, CLOSE/OPEN INHIBIT, USER INPUT, OR ESD. IN
ADDITION, INPUT 2 MAY BE CONFIGURED FOR CSE REMOTE SELECTED INDICATION.
DEFAULT INPUT CONFIGURATION: INPUT 0 - ESD, INPUT 1 - OPEN INHIBIT, INPUT 2 CLOSE INHIBIT
SEE INSTALLATION AND OPERATION MANUAL FOR CONFIGURATION PROCEDURES.
DEVICENET
BOARD
REVERSING
CONTACTOR
CLOSE
STOP
OPEN
DIG COM #1-Ve
0V AC
110V AC
24V DC +Ve
0V DC
24V DC +Ve
0V DC
5
6
7
9
8
51
10
12
11
14
13
37
38
L1
L2
L3
FS1
FS2
FS3
LIMIGARD
POSITION
SENSOR
1
2
3
4
31
32
42
43
AS1
AS2
AS3
AS4
"CLOSE"
POSITION
"OPEN"
POSITION
"CLOSE"
POSITION
"OPEN"
POSITION
17
18
19
SHOWN
WITH POWER
SUPPLY OFF
CONTROL PANEL
MOTOR
PE
3 PHASE
SUPPLY
TORQUE
SENSOR
MONITOR RELAY
REMOTE
LOCAL
S
T
O
P
(YES)
OPEN
CLOSE
(NO)
CONTROL
SUPPLY
CIRCUIT SHOWN WITH VALVE IN FULLY CLOSED POSITION AND WITH POWER OFF
STATUS FEEDBACK
OUTPUT SWITCHES
VIEW OF
TERMINAL
BLOCK
REMOTE
LOCAL
S
T
O
P
(YES)
OPEN
CLOSE
(NO)
ANALOG INPUT
8.EXACT END POSITION INDICATION
1.FUSES
FSI (PRIMARY)
FS2 (PRIMARY)
3.MAXIMUM EXTERNAL LOAD
TERMINALS 13 AND 14 (24V DC) - 10W MAX. EXT. LOAD
TERMINALS 11 AND 12 (110V AC) - 0V MAX EXT. LOAD
SUITABLE FOR DIGITAL INPUTS
ONLY, PROTECTED BY FS3.
5.CONTROL SIGNAL DURATION
REQUIRED CONTROL SIGNAL
DURATION = 250 - 350ms.
6.STATUS FEEDBACK OUTPUT SWITCHES
CLOSE
CLOSING
MID-TRAVEL
OPENING
OPEN
STOPPED
9.DEFAULT SETTING
ACTUATORS ARE NORMALLY SHIPPED WITH DEFAULT
SETTINGS AS SHOWN ON THIS DIAGRAM. THE "AS"
CONTACTS ARE SHOWN WITH VALVE IN FULLY CLOSED
POSITION. SEE CONTACT DEVELOPMENT BELOW.
7.CONTACT RATINGS
VALVE MOVING
VALVE JAMMED
MOTOR OVERTEMP
OVERTORQUE
CLOSE TORQUE SW
OPEN TORQUE SW
CLOSE INHIBIT
OPEN INHIBIT
ESD SIGNAL
NO ANALOG SIGNAL
LOST PHASE
LIMIGARD ACTIVE
HARDWARE FAILURE
LOCAL SELECTED
LOCAL STOP/OFF
MANUAL OVERRIDE
REMOTE SELECTED
OUTPUT SWITCH CONTACT DEVELOPMENT
VALVE POSITION
FULL
CLOSE
FULL
OPEN
FUNCTION
CLOSE LIMIT
AS4
OPEN LIMIT
AS3
CLOSE LIMIT
OPEN LIMIT
AS1
AS2
OUTPUT
SWITCH
ON TORQUE-SEATED VALVES THE LCD AND "AS"
CONTACTS, CONFIGURED AS END OF TRAVEL LIMITS,
AUTOMATICALLY PROVIDE EXACT END OF POSITION
INDICATION.
600V AC, 1A, 200kA Int RATING,
FAST ACTING 10.3 x 38.1mm TUBE.
FS3 (SECONDARY) - 0.1A, 250V, TIME DELAY,
5 x 20mm, GLASS TUBE
AS1,2,3 AND 4 - 5.0 AMPS AT 125V AC, 30V DC (250V AC-CENELEC)
MONITOR RELAY - 5.0 AMPS AT 250V AC, 30V DC
NOTES
TRANSFORMER TAPPING OPTIONS
TYPE
TAPPING
A
220V
380V
415V
460V
B
TYPE
TAPPING
115V
220V
525V
575V
TYPE
TAPPING
A
220V
380V
415V
460V
B
TYPE
TAPPING
115V
220V
525V
575V
TRANSFORMER TAPPING OPTIONS
DEFAULT SETTING
SEE NOTE 6 AND 9
2.AUXILIARY INPUT
AUXILIARY INPUT
SEE NOTE 2
52
21
DIG COM #2-Ve
DIG COM #3-Ve
2 mA / 24V DC
MAX LOAD - 10 mA / 110V AC
MAXIMUM "OFF" 5.0V AC/DC
SIGNAL THRESHOLD - MINIMUM "ON" 19.2V AC/DC
4.REMOTE INPUTS
REMOTE
INPUTS
SEE NOTE 4
INPUT 2
INPUT 1
INPUT 0
120 OHM, 1/4W TERMINATION RESISTORS MUST BE CONNECTED
AT EACH SEGMENT END.
SHIELDS TOGETHER TO ENSURE PROPER SHIELDING OF ENTIRE NETWORK.
ON EACH SEGMENT. CONNECT REMAINING INDIVIDUAL NETWORK CABLE
WIRING IS TO CONNECT SHIELD TO TERMINAL 48 FOR ONLY ONE UNIT
AND CHASSIS GROUND FOR SURGE PROTECTION. PREFERRED NETWORK
CUSTOMER IS REQUIRED TO CONNECT WIRE BETWEEN TERMINAL 30
SEE NOTE 11
RECOMMENDED DEVICENET CABLE IS BELDEN 3084A OR EQUAL.
15
16
48
SHIELD
NETWORK DATA (+)
NETWORK DATA (-)
0% OPEN
STATUS OK
1
2 3 4 5
6 7
8
9
101
1
1
2
1
3
1
4
1
5
1
6
1
7
1
8
1
9
2
0
2324252
6
2
7
2
8
2
9
3
0
3
2
3
3
3
4
3
1
3536373
8
3
9
4
0
4
1
4
2
4
3
4
4
4
5
4
6
4
7
4
8
4
9
5
0
5
1
5
2
2
2
2
1
L1
L2L3
GROUNDING
LUG
0% OPEN
STATUS OK
NETWORK +24V
NETWORK 0V
29
41
39
28
-ve ANALOG COMMON
+ve ANALOG INPUT-1
+ve ANALOG INPUT-2
40
(MODUTRONIC)
STANDARD SIGNAL 4-20 mA
INPUT IMPEDANCE = 250 OHMS
INPUT CAPACITACNE = 0.1uf±30%
99% ACCURACY
CONFIGURABLE SCALING
10.ANALOG INPUT
BACK-UP 24v DC UPS POWER MAY BE CONNECTED
TO TERMINAL'S 37 AND 38. MAXIMUM CURRENT
DRAW IS 1 AMP. THIS POWERS ALL CONTROLS FOR
LOCAL INDICATION AND CONFIGURATION. ANALOG OUTPUT AND ALARM
RELAYS SUPPLIED WILL BE POWERED FOR UNITS MANUFACTURED
SUBSEQUENT TO Q1/2003. REVERSING CONTACTOR WILL NOT
BE POWERED. CUSTOMER SHOULD SUPPLY EXTERNAL FUSE AS
REQUIRED BY LOCAL ELECTRICAL CODES.
THE ACTUATOR STATUS CONTACTS (AS) AND ALARM RELAYS (AR)
MAY BE INDIVIDUALLY CONFIGURED AS NORMALLY OPEN OR NORMALLY
CLOSED LATCHED CONTACTS OR AS BLINKER CONTACTS TO INDICATE
ONE OF THE FUNCTIONS LISTED BELOW:
BLU
BLK
WHT
RED
11.DEVICENET
EGND
30
INPUTS 0,1,2 ARE FIELD CONFIGURABLE (FIRMWARE VERSION 04\08.00 OR LATER)
FOR CLOSE INHIBIT, OPEN INHIBIT, CLOSE/OPEN INHIBIT, USER INPUT, OR ESD. IN
ADDITION, INPUT 2 MAY BE CONFIGURED FOR CSE REMOTE SELECTED INDICATION.
DEFAULT INPUT CONFIGURATION: INPUT 0 - ESD, INPUT 1 - OPEN INHIBIT, INPUT 2 CLOSE INHIBIT
SEE INSTALLATION AND OPERATION MANUAL FOR CONFIGURATION PROCEDURES.
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
41
flowserve.com
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
42
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
flowserve.com
43
FCD LMENIM2328-00 Printed in USA.
To find your local Flowserve representative:
For more information about Flowserve Corporation, visit
www.flowserve.com or call USA 1 800 225 6989
United States
Flowserve Corporation
Flow Control
Limitorque Actuation Systems
5114 Woodall Road
P.O. Box 11318
Lynchburg, VA 24506-1318
Telephone: 1 434 528 4400
Telefax: 1 434 845 9736
Flowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flowserve product is designed to perform its intended
function safely during its useful life. However, the purchaser or user of Flowserve products should be aware that Flowserve products might be used in numerous applications under a wide
variety of industrial service conditions. Although Flowserve can (and often does) provide general guidelines, it cannot provide specific data and warnings for all possible applications. The
purchaser/user must therefore assume the ultimate responsibility for the proper sizing and selection, installation, operation, and maintenance of Flowserve products. The purchaser/user
should read and understand the Installation Operation Maintenance (IOM) instructions included with the product, and train its employees and contractors in the safe use of Flowserve
products in connection with the specific application.
While the information and specifications contained in this literature are believed to be accurate, they are supplied for informative purposes only and should not be considered certified or as
a guarantee of satisfactory results by reliance thereon. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding any matter with respect to this
product. Because Flowserve is continually improving and upgrading its product design, the specifications, dimensions and information contained herein are subject to change without notice.
Should any question arise concerning these provisions, the purchaser/user should contact Flowserve Corporation at any one of its worldwide operations or offices.