The use and storage of gasoline or other flammable vapors and
liquids in open containers in the vicinity of this appliance is
hazardous.
W ARNING: Impr oper installation, adjustment, alteration, service,
or maintenance can cause property damage, injury , or death. Read
the installation, operation, and maintenance instructions
thoroughly before installing or servicing this equipment.
WARNING: Gas-fired appliances are not designed for use in
hazardous atmospheres containing flammable vapors or
combustible dust, in atmospheres containing chlorinated or
halogenated hydrocarbons, or in applications with airborne silicone
substances. See Hazard Levels, page 2.
WARNING: Should overheating occur, or the gas supply fail to
shut off, shut off the manual gas valve to the appliance before
shutting off the electrical supply.
WARNING: Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect
the appliance and replace any gas control that has been under water .
E
S
R
E
G
S
V
E
N
N
O
T
P
U
-
T
R
A
T
S
M
A
L
I
T
Y
U
C
T
Y
E
T
T
S
Y
S
N
A
R
R
A
W
Reznor
®
Model
LDAP 1200
FOR YOUR SAFETY
FOR YOUR SAFETY
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 1
Hazard Levels of
Warnings in this
Manual
HAZARD INTENSITY LEVELS
1. DANGER: Failure to comply will result in sever e personal injury or death
and/or property damage.
2. WARNING: Failure to comply could result in severe personal injury or
death and/or property damage.
3. CAUTION: Failure to comply could result in minor personal injury and/or
property damage.
1. General
2. Installation
Codes
Special Installations
(Aircraft Hangars/
Repair Garages/
Parking Garages)
All Model LDAP high bay packaged heaters are design certified by ITS for use in
industrial and commercial installations. All models and sizes are available for use
with either natural or propane gas. The type of gas, the input rate, and the electrical
supply requirement are shown on the heater rating plate. Check the rating plate to
determine if the heater is appropriate for the intended installation.
®
The instructions in this manual apply only to Reznor
Installation should be done by a qualified agency in accordance with these instruc-
tions. The qualified service agency installing this heater is responsible for the installation.
These heaters must be installed in accordance with local building codes. In the absence of local codes, in the United States, the heater must be installed in accordance
with the National Fuel Gas Code, ANSI Z223.1. A Canadian installation must be in
accordance with the CSA B149 Installation Codes. These codes are available from
CSA Information Services, 1-800-463-6727. Local authorities having jurisdiction
should be consulted before installation is made to verify local codes and installation
procedure requirements.
Installations in aircraft hangars should be in accordance with ANSI/NFPA No. 409
(latest edition), Standard for Aircraft Hangars; in public garages in accordance with
ANSI/NFPA No. 88A (latest edition), S tandard for Parking S tructures; and for repair
garages in accordance with ANSI/NFP A No. 88B (latest edition), S tandard for Repair
Garages. In Canada, installations in aircraft hangars should be in accordance with the
requirements of the enforcing authorities, and in public garages in accordance with
CSA B149 codes.
Model LDAP heaters.
California Warning
Label
Massachusetts
Requirement
3. Warranty
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 2
If the heater is being installed in the state of California, the installer MUST attach a
warning label on the outside of the access door . The California W arning label is shipped
in the owner’s envelope along with this manual, the warranty form, and any other
paperwork that applies.
If installation is in California, select a location on the heater access panel. Be sure the
surface is clean and dry and adhere the label.
If the heater is being installed in the Commonwealth of Massachusetts, this heater
must be installed by a licensed plumber or licensed gas fitter.
Refer to the limited warranty information on the Warranty Card in the "Owner's Envelope".
Warranty is void if ...
a. Wiring is not in accordance with the diagram furnished with the heater.
b. The heater is installed without proper clearance to combustible materials.
c. The heater is connected to a duct system or if the air delivery system is
modified by other than manufacturer-designed accessories.
4. Uncrating and
Preparation
This heater was test operated and inspected at the factory prior to crating and was in
operating condition. If the heater has incurred any damage in shipment, document
the damage with the transporting agency and contact an authorized Reznor Distributor. If you are an authorized Distributor , follow the FOB freight policy procedures as
published by Thomas & Betts for Reznor products.
Check the rating plate for the gas specifications and electrical characteristics of the
heater to be sure that they are compatible with the gas and electric supplies at the
installation site.
MPORTANT: The crate bottom should be removed after the heater is lifted.
I
Shipping brackets are attached with cabinet screws. When removing shipping
brackets, re-insert ALL screws into the cabinet.
Read this booklet and become familiar with the installation requirements of your
particular heater. If you do not have knowledge of local requirements, check with the
local gas company or any other local agencies who might have requirements concerning this installation. If the installation is above 2000 ft (610M) elevation, follow
the instructions in Paragraph 5 and Paragraph 12.
Before beginning, make preparations for necessary supplies, tools, and manpower.
Locate the hardware kit supplied with the heater. The plastic bag contains spring
nuts, hex nuts, “U”-shape fittings, lock washers, louvers, and compression springs.
Be sure that all shipped-separate options that were ordered are at the installation site.
Shipped-separate items could include a vent cap, louvers, nozzles, hanger kit, a manual
shutoff valve, a thermostat, multiple heater controls, high temperature tape, and/or a
high altitude kit.
5. High Altitude
Operation
Pressure Switch
Instructions for Changing
Heat section Pressure
NOTE: Do not change the
main pressure switch located
on top of a Size 800 and Size
1200 heater. It is the same for
all elevations.
If the heater is being installed at an elevation above 2000 ft (610M), the input rate
will have to be derated. This is done by adjusting the outlet pressure of the gas valve
and can only be done after the heater is in operation. Follow the instructions in Paragraph 12.
If the heater is being installed at an elevation above 6000 ft (1830M), the heat section
pressure switch(es) will need to be changed. If ordered with the heater as Option
DJ20, the pressure switch is shipped separately.
High Altit u de Unit Pressure Sw it ch (es)
Start-up Cold Equilibrium Hot Setpoint OFF Setpoint ON
QtySize
40011.75 to 1.451.00 to 0.800.600.78Lt. Blue197029
80021.85 to 1.551.05 to 0.850.600.78Lt. Blue197029
120032.35 to 1.851.50 to 0.950.600.78Lt. Blue197029
Label
Color
Switch
Part No.Differential Pressure (in. w.c.)
Switch(es)
1. In the control compartment of the first heat section, locate the pressure switch.
2. Mark and disconnect the two wires attached to the pressure switch.
3. Mark and disconnect the sensing tubes from the pressure switch.
4. Locate the two screws holding the switch mounting bracket. Remove the screws
(save screws) and the pressure switch.
5. Using the same screws, install the high altitude pressure switch. Attach the
sensing tubes and wires.
6. If installing a Model LDAP 400, the pressure switch change for high altitude is
complete. If installing a Model LDAP 800, repeat Steps 1-5 to change the
pressure switch on the second heat section. If installing a Model LDAP 1200,
repeat Steps 1-5 to change the pressure switches on the second and third heat
sections.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 3
6. T echnical Dat a
38
(965mm)
13-1/8
(333mm)
2-5/8
(67mm)
5
(127mm)
9-7/8
(251mm)
43-1/2
(1,105mm)
RIGHT SIDE VIEW
LINE VOLTAGE
CONNECTION
DISCONNECTION
SWITCH
1 NPT
GAS CONNECTION
m
m
m
m
Model
LDAP
400
Model LDAP 800
Model LDAP 1200
One
Downflow
Heater
One Heater
with Two
Downflow
Heat
Sections
One Heater with
Three Downflow
Heat Sections
Mo del LDAP Size
Input Heating Capa c ity
btuh400,000800,0001,200,000
kw/h117.1234.2351.4
Thermal Efficiency (%)
O ut put Heating Capacity
btuh332,000664,000996,000
kw/h97.2194.4291.6
Gas Co nnection (I nches)
Vent Connection Diameter (Inches)
Contr ol Amps ( 24 volt)
Fu ll Load Amps (208 volt)
Fu ll Load Amps (230 volt)
N orm al Power Consumpti o n @ 2 08V (w a t ts)
N orm al Power Consumpti o n @ 2 30V (w a t ts)
Discharge Air Temperature Rise (°F)
Air Volum e (Heat @ High Speed)
D ischarge Ai r Opening Are a
Outlet Velocity (Heat @ High
Speed)
Air Volume (Destratification @
Medium Speed)
Outlet Velocity (Destrati ficati on
@ Me dium Speed)
Air Volume (Destratification @
Low Speed)
Outlet Velocity (Destrati ficati on
@ L ow S peed)
cfm55891117816768
3
/minute
2
ft
2
fpm152115211521
m/minute464464464
cfm4650930013950
3
/minute
fpm126612661266
m/minute386386386
cfm325065009750
3
/minute
fpm885885885
m/minute270270270
Fan Motor HP (Qty)
Fan Motor RPM
Fan Diameter (I nches)
4008001200
838383
11-1/41-1/4
68 8
1.02.03.0
5.613.619.4
5.512.818.5
115024483730
123025973959
555555
158317475
3.677.3511.02
0.340.681.02
132263395
92184276
1 (1)1 (2)1 (3)
105010501050
242424
7. Dimensions
FIGURE 1A - Model LDAP 400
30
(762mm)
17-1/8
(435mm)
14-7/8
(378mm)
9-1/8
(232mm)
15-1/4
(387mm)
34-3/8
(873mm)
TOP VIEW
ø 6 FLUE
OUTLET
2-1/8
(54mm)
7/8
(22mm)
AIR DESTRATIFICATION
FAN CONTROL
28-1/8
(714mm)
HANGER LOCATION
1/2 - 13 FEMALE THREAD
THERMOSTAT
CONNECTION
FRONT VIEW
BOTTOM VIEW
DISCHARGE OPENING
9-1/4
(235mm)
1-1/4
(32mm)
23
(584mm)
48-1/2
(1,232mm)
3-1/4
(83mm)
5-5/8
(143mm)
23
(584mm)
NOTE: If an optional
nozzle is added to the
discharge opening,
see dimensions on
page 32.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 4
FIGURE 1B - Model LDAP800 and Model LDAP1200
RIGHT SIDE VIEW
LINE VOLTAGE
CONNECTION
DISCONNECT
SWITCH
1 NPT
GAS CONNECTION
38
(965mm)
13-1/8
(333mm)
2-5/8
(67mm)
5
(127mm)
9-7/8
(251mm)
A Model LDAP1200 with three heat sections is illustrated. A Model LDAP800 has two heat sections. A Model LDAP800
is the same layout as illustrated less the middle heat section.
SizeAB
HANGER LOCATION
1/2 - 13 FEMALE THREAD
800
11-7/8
A
(302mm)
1200
inches
mm
inches
mm
4669
11681753
80103-3/4
20322635
14-7/8
(378mm)
COMBUSTION BOX ASSEMBLY
34-3/4
(883mm)
TOP VIEW
B
34-3/4
(883mm)
ø8 FLUE OUTLET
17-1/8
(435mm)
12
(305mm)
13-3/4
(349mm)
(1,346mm)
7/8
(22mm)
1-5/8
(41mm)
53
28-1/8
(714mm)
AIR DESTRATIFICATION
FAN CONTROL
43-1/2
(1,105mm)
46
(1,168mm)
1-1/4 NPT
5-5/8
(143mm)
3-1/4
(83mm)
23
(584mm)
FRONT VIEW
THERMOSTAT
CONNECTIONS
11-3/4
(298mm)
23
(584mm)
(584mm)
DISCHARGE OPENING
11-3/4
(298mm)
23
BOTTOM VIEW
1-1/4
(32mm)
23
(584mm)
NOTE: If optional
nozzles are added to the
discharge openings, see
dimensions on page 32.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 5
8. Clearances
(
)
Heaters must be installed so that the clearances in the table are provided for combustion air space, inspection and service, and for proper spacing from combustible construction. Clearance to combustibles is defined as the minimum distance from the
heater to a surface or object that is necessary to ensure that a surface temperature of
90°F above the surrounding ambient temperature is not exceeded.
Clearances inches/mm
9. Combustion
Air
Size
400
800
1200
Top
inches mm inchesmminchesmminches mm in ches mm inches mm inches mm
This heater must be supplied with the air that enters into the combustion process and
is then vented to the outdoors. Sufficient air must enter the equipment location to
replace that exhausted through the heater vent system. In the past, the infiltration of
outside air assumed in heat loss calculations (one air change per hour) was assumed
to be sufficient. However, current construction methods using more insulation, vapor
barriers, tighter fitting and gasketed doors and windows, weather-stripping, and/or
mechanical exhaust fans may now require the introduction of outside air through wall
openings or ducts.
The requirements for combustion and ventilation air depend upon whether the heater
is located in a confined or unconfined space. An "unconfined space" is defined as a
space whose volume is not less than 50 cubic feet per 1000 BTUH of the installed
appliance. Under ALL conditions, enough air must be provided to ensure there will
not be a negative pressure condition within the equipment room or space.
Flue
Connector
Front
Access Panel
Rear
Disconnect
Side
Side
Bottom
FIGURE 2 - Definition of
Confined Space and
Required Openings for
Combustion Air
Confined Space:
A space whose volume is
less than 50 cubic feet
per 1000 BTUH of the
installed appliance input
rating
(3)
Confined
Space
(3)
(1)
(1)
(2)
(2)
W ARNING: A Model LDAP power-vented heater is designed to take
combustion air from the space in which the heater is installed and is
not designed for connection to outside combustion air intake ducts.
Connecting outside air ducts voids the warranty and could cause
hazardous operation. See Hazard Levels, page 2.
Combustion Air Requirements for a Heater
Located in a Confined Space
Do not install a heater in a confined space without providing wall openings leading to
and from the space. Provide openings near the floor and ceiling for ventilation and air
for combustion as shown in FIGURE 2, depending on the combustion air source as
noted in Items 1, 2, and 3 below.
Add total BTUH of all appliances in the confined space and divide by figures below
for square inch free area size of each (top and bottom) opening.
1. Air from inside the building - openings 1 square inch free area per 1000 BTUH.
Never less than 100 square inches free area for each opening. See (1) in FIGURE 2.
2. Air from outside through duct - openings 1 square inch free area per 2000 BTUH.
See (2) in FIGURE 2.
3. Air direct from outside - openings 1 square inch free area per 4000 BTUH. See
(3) in FIGURE 2.
NOTE: For further details on supplying combustion air to a confined space, see the
National Fuel Gas Code ANSI Z223.1a (latest edition).
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 6
10. Heater
Location
Use the clearances in Paragraph 8; the combustion air requirements in Paragraph 9;
the mounting height requirements, throw information, sound data, and location recommendations below; the weights in Paragraph 11; and the venting requirements in
Paragraph 24 to determine where to suspend the heater.
CAUTION: Do not locate the heater where it may be exposed to
water spray, rain, or dripping water.
Mounting Height
Locate the heater so that it is a minimum of 15 feet (4.6M) above the floor and in
compliance with the clearances in Paragraph 8.
WARNING: If touched, the vent pipe and internal heater surfaces
that are accessible from outside the heater will cause burns. Suspend
the heater a minimum of 15 feet (4.6M) above the floor.
Heater Throw All Models
FIGURE 3 - Model LDAP Air Throw (Heat Mode @ High Speed) - Applies to All Sizes
60° Nozzle
Mounting
Height
Standard
Louvers
Standard Louvers
0
X
Y
Z
30° Nozzle
X
30° Nozzle
Y
Z
X
60° Nozzle
Y
Z
= “Rear” of Heater Discharge
0
NOTES:
• X = Distance from “0” to beginning
of floor coverage.
• Y = Distance from “0” to end of
floor coverage.
• Length of floor coverage = Y - X.
• Z = Distance from “0” to the point
where the air velocity drops below
50 feet (15.2M) per minute.
• Throws listed are with standard
louvers facing one direction and
fully open. Throw pattern changes
with louver angle, 2-way louver
direction, and or optional 4-way
louvers.
Throw (feet and meters)
Sta ndard Lou vers30° Degree No zzle60° Degree Nozzle
NOTE: Venting
requirements may affect
location. Consult
requirements in Paragraph 24
before making final
determination.
Hazards of Chlorine
For best results, the heater should be placed with certain rules in mind. In general, a
heater should be located from 15-40 feet (4.6-12.2 M) above the floor. If two or more
heaters are installed in the same room, a general scheme of air circulation should be
maintained for best results.
Suspended heaters are most effective when located as close to the working zone as
possible, and this fact should be kept in mind when determining the mounting heights
to be used. However, care should be exercised to avoid directing the discharged air
directly on the room occupants.
Partitions, columns, counters, or other obstructions should be taken into consideration when locating the heater so that a minimum quantity of airflow will be deflected
by such obstacles.
The presence of chlorine vapors in the combustion air of gas-fired heating equipment
presents a potential corrosion hazard. Chlorine found usually in the form of freon or
degreaser vapors, when exposed to flame will precipitate from the compound, and go
into solution with any condensation that is present in the heat exchanger or associated
parts. The result is hydrochloric acid which readily attacks all metals including 300
grade stainless steel. Care should be taken to separate those vapors from the combustion process. This may be done by wise location of the heater with regard to exhausters or prevailing wind directions. Chlorine is heavier than air. Keep these facts in
mind when determining installation location of the heater in relation to building exhaust systems.
11. Hanging or
Mounting
the Heater
Weight (lbs/kg)
Size4008001200
lbs3758051195
kg170365542
and
Suspending the Heater
Installing
Louvers
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 8
Locate the hardware kit shipped with the heater. The kit contains spring nuts, hex
nuts, “U”-shape fittings, and lock washers for suspending the heater. It also includes
louvers and the compression springs needed to install them.
When the heater is lifted for suspension, support the bottom of the heater with the
crate bottom. If the bottom is not supported, damage could occur. Before hanging or
mounting, verify that any screws used for holding shipping brackets were re-installed
in the cabinet.
WARNINGS: Check the supporting structure to be used to verify
that it has sufficient load carrying capacity to support the weight of
the heater . Suspend the heater only fr om the threaded nut retainers
or with a manufacturer provided kit. Do NOT suspend from the
heater cabinet.
See FIGURE 1A or 1B for the appropriate hanging locations, and install the ½”-13
spring nuts in the strut that is attached to the top of the unit. Comply with the requirements in FIGURE 4A when using threaded rod. If ordered with swivel connectors
for 1” pipe, Option CK10, attach the swivels to the spring nuts according to illustration in FIGURE 4B and suspend with 1” pipe.
Before installing the heater, check the supporting
structure to be used to verify that it has sufficient loadcarrying capacity to support the weight.
WARNING: All heaters must be level for proper operation. Do not
place or add additional weight to the suspended heater. Hazard
Levels, page 2.
FIGURE 4A Suspending the
Heater with Rods
from the Threaded
Nut Retainers
1/2”-13
Threaded Rod
Hex Nut
Lockwasher
“U”-shape
Fitting
Spring
Nut
Strut
attached to
top of heater.
Be sure the threaded hanger rods are locked to the heater as
illustrated. Recommended maximum hanger rod length is 6
feet (1.8M).
W all Mounting
The heater may be attached to a wall. Place supports as shown in FIGURE 5 and
comply with all guidelines listed.
FIGURE 4B- Swivel Connectors to
Suspend the Heater from 1” Pipe, Option
CK10
Pipe Coupling
Assembly
Hex Nut
“U”-shape
Fitting
Lockwasher
Spring
Nut
Strut
attached to
top of heater.
Be sure the threaded swivel connectors are locked
to the heater as illustrated.
Guidelines for Wall Mounting
Model LDAP Heaters
Mounting is the responsibility of the
installer. Verify that the supporting
structure has sufficient load-carrying
capacity to support the weight. (See
weights, page 8.)
Prior to installation, be sure that the
method of support is in agreement with
all local building codes. Check for
service platform requirements.
Maintain a minimum of 2” (51mm)
clearance from the discharge air
openings to structural supports. Additional clearance will be required if an
optional nozzle is to be field installed.
Determining the need for installing
vibration or noise isolation is the
responsibility of the installer.
To prevent potential movement, field-
supplied angles must be placed around
the perimeter of the heater to anchor it
to the structural supports.
Structural supports must be placed as
shown to prevent damage to the heater.
All structural supports must be non-
combustible materials.
FIGURE 5 - Wall Mounting
(All structural supports and angles are field supplied.)
All dimensions are measured from centerlines of field-supplied structural supports.
Field-Supplied
Mounting Angles
(MUST be on all
Model LDAP 800
(2 heat sections)
Front View
34-33/64
(877mm)
34-33/64
(877mm)
34-33/64
(877mm)
Model LDAP 1200
(3 heat sections)
Front View
34-43/64
(881mm)
four sides of the
heater.)
Side View
Dimensions are
centerline of the
mounting angles
and apply to all sizes.
34-33/64
(877mm)
(1080mm)
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 9
Model
LDAP 400
(1 heat
section)
Front View
34-11/32
(872mm)
Wall
28-1/4
(718mm)
42-1/2
Airflow direction;
springs are on
the upper end.
Airflow direction;
springs are on
the lower end.
l
11. Installing
Heater and
Louvers
(cont’d)
Installing Louvers
NOTE: Do not install louvers
if installing a nozzle. Follow
the instructions shipped with
the nozzle.
FIGURE 6 - Use
Compression Springs to
Install Louvers in the
Discharge Opening(s)
CAUTION: To avoid getting
burned, adjust louvers while
heater is not operating. If
adjusting louvers while
heater is operating, wear
gloves.
After the unit is suspended/mounted, install the air directional louvers or optional
nozzle. If an optional nozzle is being installed, follow the instructions included with
the nozzle. If a nozzle is not being used, install the louvers in the discharge opening(s).
Louvers and springs are in the hardware kit shipped with the heater.
Before actually installing the louvers, note the louver curve and determine how the
louvers should be positioned to provide the optimal throw pattern. Opening is square
so louvers may be installed either horizontal or vertical. Louvers may be installed
with the curve all the same direction (either way) or the right half one way and left
the other as illustrated in FIGURE 6.
Louver Installation Instructions:
1) With the wider section of the louver facing out of the heater, place one of the compres-
sion springs over the tab on the notched end of a louver. The end of the louver with the
spring will fit in any direction in the square opening. How the louver turns depends on
which end of the louver is inserted first.
2) Depending on the throw pattern selected, push the louver tab with the spring into a
hole in the discharge opening and insert the louver tab on the other end into the
corresponding hole on the opposite side.
3) Continue until all louvers are installed.
Adjust the louvers to provide the
desired throw pattern.
Compression Spring
Wider side of the louver
blade must always be
facing out of the heater.
Airflow direction depends on
how the louvers are installed.
12. Gas Piping
and
Pressures
Sizing Gas Supply
Line
W ARNING: All components of a gas supply
system must be leak
tested prior to placing
equipment in service.
NEVER TEST FOR
LEAKS WITH AN OPEN
FLAME. Failure to
comply could result in
personal injury, pr operty
damage or death.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 10
WARNING: This appliance is equipped for a maximum gas supply
pressure of 1/2 psi, 3.5 kPa, or 14 inches water column. Supply
pressure greater than 1/2 psi requires installation of an additional
lockup-type service regulator external to the heater.
W ARNING: PRESSURE TESTING SUPPLY PIPING
Test Pressures Above 1/2 PSI: Disconnect the heater and manual valve from the
gas supply line which is to be tested. Cap or plug the supply line.
T est Pressur es Below 1/2 PSI: Before testing, close the manual valve on the heater .
Capacity of Piping
Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)
Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)
Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.
Propane Natural Propane Na t uralPropane NaturalPropane Natural Propane
Refer to National Fuel Gas Code for additional information on line sizing.
- Cubic Feet per Hour based on 0.3" w.c. Pressure Drop
1600
976
Gas Connection Size
Ga s Connection - inches/mm
400
800
1200
Size
inches
mm
inches
mm
inches
mm
Natural
Gas
25.425.4
1-1/41-1/4
31.831.8
1-1/41-1/4
31.831.8
Propane
Gas
11
FIGURE 7 - Gas
connection is at the pipe
nipple that extends outside
the cabinet.
IMPORTANT: Two pipe
wrenches are required when
installing gas piping. The gas
pipe that is supplied with the
heater MUST be held with a
pipe wrench to prevent damage
to the heater.
NOTE: Gas Conversion Kits
are available for changing
from propane gas to natural
gas or natural gas to propane
gas. A factory-authorized
conversion kit MUST be
used.
Valve Outlet or
Orifice Pressure
Setting
W ARNING: V alve outlet
gas pressure must never
exceed 3.5" w .c. for
natural gas and 10" w .c.
for propane gas.
All piping must be in accordance with requirements outlined in the National Fuel
Gas Code ANSI/Z223.1a (latest edition) or CSA-B149.1 and B149.2 (See Paragraph
2). Gas supply piping installation should conform with good practice and with local
codes. Support gas piping with pipe hangers, metal strapping, or other suitable material; do not rely on the heater to support the gas pipe.
The heater is orificed for operation with natural gas having a heating value of 1000
(± 50) BTUH per cubic ft or propane gas with a heating value of 2500 (± 100) BTUH
per cubic ft. If the gas at the installation does not meet these specifications, consult
the factory for proper orificing.
Pipe joint compounds (pipe dope) shall be resistant to the action of liquefied petroleum gas or any other chemical constituents of the gas being supplied.
Install a ground joint union and manual shutoff valve upstream of the heater control
system, as shown in FIGURE 7. Installation of a trap with a minimum 3" (76mm)
drip leg is required.
To connect the gas, the heater is equipped with a nipple that extends outside the
cabinet.
Leak-test all connections by brushing on a leak-detecting solution.
Ground
To Gas Valve
(inside the
cabinet)
Pipe nipple extending
outside the cabinet.
Joint Union
To Gas Valve
(inside the
cabinet)
Manual shutoff
Drip
Leg
Ground
Horizontal Supply
From Gas Supply
(horizontal or vertical)
Vertical Supply
Drip
Joint
Union
Leg
Manual
shutoff
Measuring valve outlet gas pressure cannot be done until the heater is in operation. It
is included in the steps of the "Check-Test-Start" procedure in Paragraph 25. The
following warnings and instructions apply. Model LDAP 400 has one gas valve;
Model LDAP 800 has two gas valves; and Model LDAP 1200 has three gas valves.
For Natural Gas: When the heater leaves the factory, the combination gas valve(s)
is set so that the valve outlet gas pressure for a single stage valve or high fire of a two
stage valve is regulated to 3.5" w .c. Low fire on a two-stage valve (Size 400 only) is
set to 1.8” w .c. Inlet supply pressure to the heater for natural gas must be a minimum
of 5" w.c. or as noted on the rating plate and a maximum of 14" w.c.
For Propane Gas: When the heater leaves the factory , the combination gas valve(s)
is set so that the valve outlet gas pressure for a single stage valve or high fire of a two
stage valve is regulated to 10" w.c. Low fire on a two-stage valve (Size 400 only) is
set to 5.0” w.c. Inlet supply pressure to the heater for propane gas must be a minimum of 11" w.c. and a maximum of 14" w.c.
Before attempting to measure or adjust valve outlet gas pressure, the inlet
supply pressure must be within the specified range both when the heater is in operation and on standby. Incorrect inlet pressure could cause excessive valve outlet gas
pressure immediately or at some future time. If natural gas supply pressure is too
high, install a regulator in the supply line before it reaches the heater. If natural gas
supply pressure is too low , contact your gas supplier .
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 11
12. Gas
g
g
Pressures
(cont’d)
Check V alve Outlet
Pressure (can only
be done after heater
is operating)
NOTE: If operating at high
altitude, outlet pressure
requires adjustment. Follow
instructions below.
NOTES: If installation is
above 6000 ft (1830M), a
high altitude pressure switch
is required on each heat
section (all sizes). See
Paragraph 5.
The main combustion air
pressure switch (Sizes 800
and 1200 only) does not need
to be changed for high
Instructions
1) Locate the 1/8” output pressure tap on the first valve (See FIGURE 8). With
the manual valve turned off to prevent flow to the gas valve, connect a manom-
eter to the 1/8" pipe outlet pressure tap in the valve. NOTE: A manometer (fluid-
filled gauge) is recommended rather than a spring type gauge due to the difficulty
of maintaining calibration of a spring type gauge.
2) Open the manual valve and operate the heater. Measure the outlet pressure of
the gas valve. To measure low-stage pressure on a Size 400 unit equipped with a
two-stage valve, disconnect the wire from the “HI” terminal on the valve. (Be
sure to reconnect wire after testing.)
Normally when operating at sea level, adjustments should not be necessary to the
factory setting(s). (For high altitude settings, see below .) If adjustment is neces-
sary, remove the cap from the adjustment screw(s). Set pressure to correct
settings by turning the regulator screw IN (clockwise) to increase pressure. Turn
regulator screw OUT (counterclockwise) to decrease pressure.
3) If installing a Model LDAP 800, repeat to verify outlet pressure on second valve.
If installing a Model LDAP 1200, repeat to verify outlet pressure check on
second and third valve.
Derate by Valve Outlet Pressure Adjustment for High
Altitude Operation
Instructions for High Altitude Derate
1. Determine the required valve outlet pressure for the elevation where the heater
will be operating. If unsure of the elevation, contact the local gas supplier.
Valve Outlet Pressure Settings by Elevation
altitude installation.
FIGURE 8 - Top View of
Valves showing Outlet
Pressure Tap and
Adjustment Locations
2. Locate the 1/8” output pressure tap on the first valve (See FIGURE 8). Turn
the knob on the top of the valve to “OFF”. Connect a manometer to the 1/8"
pipe outlet pressure tap in the valve. Use a water column manometer that is
readable to the nearest tenth of an inch.
Single-Stage and Two-Stage High Fire - Turn the knob on the top of the
3.
valve to “ON”. Remove the cap from the pressure adjusting screw and adjust
the gas train pressure to the pressure selected from the table above. Adjust
pressure by turning the regulator screw IN (clockwise) to increase pressure or
OUT (counterclockwise) to decrease pressure.
Two-Stage Low Fire - Disconnect the wire from the “HI” terminal on the gas
valve and check the low fire pressure. Turn the regulator screw to adjust the low
fire outlet pressure to the “Low Fire” pressure selected from the table. Reconnect the wire to the gas valve.
M anifold Pressure Settings by Altitude for the UNI T ED STATES
Al titudeNatural Gas (inches w.c .)Propane Gas (i nc he s w.c .)
Single-Stage and
Two-Sta
Ma nifold Pressure Settings b y Altitude for CANADA
Al titudeNatural Gas (inches w.c .)Propane Gas (i nc he s w.c .)
Single-Stage and
Two-Sta
e High Fire
e High Fire
Two-Stage
Low Fire
Two-Stage
Low Fire
Single-Stage and
Two-Stage High Fire
Single-Stage and
Two-Stage High Fire
Two-Stage
Low Fire
Two-Stage
Low Fire
4. Turn up the thermostat. Cycle the burners once or twice to properly seat the
adjustment spring in the valve.
Re-check the pressure(s). When the outlet pressure is right for the installation,
remove the manometer and replace the cap.
Check for leak at the pressure tap fitting.
5. If installing a Model LDAP 800, repeat the adjustment at the second single-stage
gas valve. If installing a Model LDAP 1200, repeat the adjustment at the second
and third single-stage gas valves.
6. With the heater operating determine that the inlet pressure to the heater for
natural gas is between 5 and 13.5 inches w.c. and for propane between 10 and
13.5 inches w.c. Take this reading at the inlet pressure tap of the first gas valve.
If the inlet pressure is not within the specified range, the inlet pressure must be
corrected and Steps 3 - 5 repeated.
7. Find the High Altitude Adjustment label in the plastic bag that contained these
instructions. Using a permanent marker, fill-in the appropriate information from
the “BTUH Input & Capacity by Altitude” Table, below. Select a location for the
label on the outside of the heater main access panel so that it will be conspicuous
to anyone operating or servicing the heater. Be sure the surface is clean and dry
and adhere the label.
High Altitude
Capacity Changes
BTUH Inputs & Capacities by Altitude in the UNI T ED STATES for Model LDAP
The input and/or the capacity of the heater changes with the derate. The tables below
list inputs and capacities at altitudes from sea level to 10,000 ft (3045M) for the U.S.
and to 4500 ft (1373M) for Canada.
Thermal Output
Capacity
BTUH Inputs & Capacities by Altitude in the CANADA for Mod el LDAP
Thermal Output
Capacity
Size 400Size 800Size 1200
Each heat section in this heater has a one-piece TCORE
Minimum
Input
Minimum
Input
Normal
Input
Normal
Input
Thermal Output
Cap a city
Size 800Size 1200Size 400
Thermal Output
Cap a city
Minimum
Input
Minimum
Input
Normal
Input
Normal
Input
Thermal Output
Cap a city
Thermal Output
Cap a city
2
®
burner assembly (U.S.
Minimum
Input
Minimum
Input
Patent No. 6,889,686) designed to provide controlled flame stability without lifting or
flashback with either natural or propane gas.
The burner can be removed as a unit for inspection or service; see Maintenance
Section for removal instructions.
14. Electrical
Supply and
Connections
Supply Wiring
All electrical wiring and connections, including electrical grounding MUST be made
in accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition) or ,
in Canada, with CSA Standard C22.1. In addition, the installer should be aware of
any local ordinances or gas company requirements that might apply.
Check the rating plate on the heater for the supply voltage and current requirements.
A dedicated line voltage supply with disconnect switch should be run directly from
the main electrical panel to the heater. All external wiring must be within approved
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 13
14. Electrical
Supply and
Connections
(cont’d)
conduit and have a minimum temperature rise rating of 60°C. Conduit must be run so
as not to interfere with the heater access panel.
CAUTION: Route wires so that they do not contact the flue wrapper
or venter housing. When running electrical conduit, be car eful that
it is clear of all access panels.
Supply Wiring
(cont’d)
Disconnect Switch
FIGURE 9 - Built-in
Disconnect Switch
24V Control Wiring
Connections
The heater is equipped with a built-in, non-fusible, lockable disconnect switch (FIGURE 8). If a fusible disconnect is required, it must be field supplied. The built-in
disconnect switch requires copper wiring with ampacity based on 60°C maximum
temperature rating at the line side terminals.
WARNING: To prevent injury or death due to electrocution or
contact with moving parts, lock disconnect switch open. See Hazard
Levels, page 2.
WARNING: If you turn off the power supply , turn off the gas. See
Hazard Levels, page 2.
Model LDAP supply wiring enters above and connects directly to the disconnect
switch (See FIGURE 1A or 1B in Paragraph 7 and FIGURE 9). A circuit board (See
FIGURE 13 in Paragraph 20) is located in the control compartment of each heat
section. The circuit boards are polarity sensitive. It is advisable to check the electrical
supply to be certain that the black wire is the “hot” wire and that the white wire is the
neutral wire. The supply connection made to “L1” on the disconnect switch must be
the “hot” wire.
Each heat section in the heater has a terminal strip for 24-volt thermostat connections. The terminal strip is located on the outside of the cabinet at the front of each
heat section (See FIGURE 1A or 1B in Paragraph 7). W ires from the terminal strip(s)
are factory wired to the circuit board(s).
15. Thermostat
and
Connections
Use either an optional thermostat available with the heater or a field-supplied 24-volt
thermostat. Install according to the thermostat manufacturer's instructions, paying
particular attention to the requirements regarding the location of the thermostat.
Make sure that the heat anticipator setting on the thermostat is 0.6 amps (or in accordance with the amperage value noted on the wiring diagram of your heater).
Make thermostat connections at the terminal strip on the front of the heater. The strip
has seven terminals, R, G, C, Y1, Y2, W1, and W2. Refer to the wiring diagram on
the heater.
IMPORTANT:All heaters MUST be operated by a 24-volt thermostat. Never
use a line voltage disconnect switch as a means of operating the heater. Operating by
means other than a 24-volt thermostat may result in the high limit control tripping
and may cause damage to the heater from excessive heat.
Connections for Reznor optional thermostats are shown in FIGURE 10 for LDAP
400; in FIGURE 11 for LDAP 800; and in FIGURE 12 for LDAP 1200.
• Option CL1 - Single-Stage Thermostat, 40-80°F
• Option CL2 - Single-Stage Thermostat with Fan Switch, 40-80°F
• Option CL3 - Single-Stage Thermostat, 40-90°F
• Option CL7 - Two-Stage Thermostat (for use with optional two-stage gas valve
on Size 400 or for staging heat sections on Sizes 800 and 1200)
• Option CL18 - Two-Stage Thermostat with Fan Switch (for use with optional
two-stage gas valve on Size 400 or for staging heat sections on Sizes 800 and
1200)
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 14
FIGURE 10 - Thermostat
Connections for Model
LDAP 400 with Option CL1,
CL2, CL3, CL7, or CL18
LDAP 400 THERMOSTAT WIRING
FIELD WIRING
NOTES:
1) Set the anticipator at 0.6 amps.
2) Set thermostat first stage anticipator at
0.6 amps and second stage anticipator at
0.2 amps.
3) Jumper thermostat terminals RH to RC.
4) Jumper thermostat terminals RH to RC
and G to W1.
5) Set thermostat first stage anticipator at
maximum amps and second stage
anticipator at 0.6 amps.
Multiple Heater
Control - Option
CL31 and Option
CL32
If the heater was ordered with a multiple heater control option, one thermostat can be used
to control multiple heaters. The option will control a maximum of six Size 400 heaters, a
maximum of three Size 800 heaters, or a maximum of two Size 1200 heaters.
The option includes a 40 VA transformer that replaces the standard transformer in the
”master” heater and a relay assembly that attaches to the “slave” heater. Option CL31
provides for control of two heaters. If control of additional heaters is desired, Option CL32
which is the relay assembly only must be added to each of the “slave” heaters.
The option packages are shipped separately and include complete instructions for installation and wiring.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 16
UNIT #3
Y2
TERMINAL STRIP
Y2
UNIT #3
TERMINAL STRIP
Y2
UNIT #3
16. Combustion
Air Proving
[Pressure
Switch(es)]
The combustion air proving switch is a pressure sensitive switch that monitors air
pressure to ensure that proper combustion airflow is available. The switch is a single
pole/normally open device which closes when a differential pressure is sensed between the venter housing and the flue collection box. Each section in the heater has a
pressure switch. (For switch location, see FIGURE 22, page 33.) In addition, heaters
with more than one heat section (Size 800 and Size 1200) have a main pressure switch
which senses the negative pressure in the main venter housing.
NOTE: For high altitude,
follow instructions in
Paragraph 5 to change heat
On startup when the heater is cold, the sensing pressure is at the highest level, and as
the heater and flue system warm up, the sensing pressure becomes less. After the
system has reached equilibrium (about 20 minutes), the sensing pressure levels off.
section pressure switch(es).
The main combustion air
pressure switch (Sizes 800
and 1200 only) does not need
to be changed for a high
altitude installation.
Pressure Switch Settings
Sea Level Pressure Switc h Settings (Ap plies to elevatio ns up to 6000ft /1830M)
Main P ressure Switch
St a rt-up Cold
Model
LDAP
40011.80 to 1.50 1.05 to 0.850.650.83Yellow 197028
800-1.30 to -1.00 -0.85 to -0.65-0.15-0.33Gray20544521.90 to 1.60 1.10 to 0.900.650.83Yellow 197028
1200 -1.40 to -0.90 -0.97 to -0.59-0.15-0.33Gray20544532.40 to 1.90 1.55 to 1.000.650.83Yellow 197028
St a rt-up Cold
Model
LDAP
40011.75 to 1.45 1.00 to 0.800.600.78Lt. Blue 197029
800-1.25 to -0.95 -0.80 to -0.60-0.15-0.33Gray20544521.85 to 1.55 1.05 to 0.850.600.78Lt. Blue 197029
1200 -1.35 to -0.85 -0.92 to -0.54-0.15-0.33Gray20544532.35 to 1.85 1.50 to 0.950.600.78Lt. Blue 197029
If a restriction or excessive flue length or turns cause the sensing pressure to be outside the switch setpoint, the pressure switch will function to shutoff the burner . If the
main combustion air pressure switch opens, it will interrupt the electric supply to all
gas valves. If a heat section pressure switch opens, it will interrupt the electric supply
to the gas valve in that heat section. The burner(s) will remain off until the system has
cooled and/or the flue system resistance is reduced.
The Table below lists the approximate water column differential pressure settings of
the heat section pressure switch(es) and the negative pressure readings of the main
pressure switch.
Heat Section Pressure Sw it ch (es)
Setpoint
High Altitu de Pr essur e Switc h Set tings, Units Abo ve 6000ft/ 1830M
Setpoint
OFF
OFF
Setpoint
ON
Setpoint
ON
Label
Color
Label
Color
Switch
Part No.
Switch
Part No.
Qty
Qty
Start-up
Cold
Start-up
Cold
Equilibrium
Hot
Heat Section Pressure Sw it ch (es)
Equilibrium
Hot
Differential Pressure (in. w.c.)
Setpoint
OFF
Setpoint
OFF
Setpoint
ON
Setpoint
ON
Label
Color
Label
Color
Switch
Part No.
Switch
Part No.
DANGER: Safe operation of this heater requir es proper venting flow . NEVER bypass combustion
air proving switch(es) or attempt to operate the heater without the venter running and the pr oper
flow in the vent system. Hazardous conditions could result. See Hazard Intensity Levels, page 2.
17. Limit Control
Each heat section is equipped with a temperature activated auto reset limit control.
The control is factory set and is non-adjustable. If the setpoint is reached, the limit
control will interrupt the electric supply to the gas valve in that heat section. This
safety device provides protection in the case of motor failure or lack of airflow due to
a restriction at the inlet or outlet. (For location, see FIGURE 22, page 33.)
CAUTION: The auto reset limit control will shut down the heater
until the cause is corrected. Do not bypass the limit control;
hazardous conditions could result. See Hazard Intensity Levels, page
2.
18. High Limit
Control
Each heat section is equipped with a temperature activated, manually reset high limit
control. The high limit control is located at the top of each heat section. It is factory
set and is non-adjustable. If the setpoint is reached, the high limit control acts to
interrupt the electric supply to the gas valve in that heat section. If the high limit
control activates, identify and correct the cause before resetting the switch. Refer to
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 17
18. High Limit
Control
(cont’d)
the Maintenance Section for information on probable causes . (For location, see FIGURE 22, page 33.)
DANGER: If a manual reset high limit control activates, identify
and correct the cause before r esetting the switch. Never bypass the
high limit control; hazardous conditions could result. See Hazard
Intensity Levels, page 2.
19. Adjustable
Air Destratification Fan
Control
20. Ignition
System
An adjustable fan control is located on top of the first heat section. It is adjacent to the
circulating air fan and motor and controls the fan motors in all heat sections. The
purpose of the fan control is to energize the fan motor(s) when the ambient air temperature around the heater reaches the setting on the control. The fan motor(s) will be
de-energized when the fan control is satisfied. The fan(s) re-circulates the heated air
near the ceiling down to the floor level (destratification) and improves heat recovery .
A call for heat by the thermostat overrides the air destratification fan control.
Set the adjustable fan control for the desired temperature setting for energizing the
circulating air fan(s). The fan control setting should be set 5 to 10°F higher than the
wall-mounted thermostat setting. The heater is factory wired to energize the fan(s) at
medium speed when energized by the adjustable fan control. For lower mounting
heights it may be desirable to operate the fan(s) at low speed. Switching the blue
(medium speed) and red (low speed) fan motor wires on each heat section will change
the fan motor(s) speed. Refer to the wiring diagram for the wire locations.
T o manually override the fan control, the heater may be tuned off at the circuit breaker
in the main electrical panel, or a field-installed electrical box with a SPST switch can
be located near the wall thermostat with the switch wired in series with the fan control.
The air destratification can also be a benefit in the summer time. Using the fan(s) in
the summer time can improve working conditions by alleviating stagnant air conditions and creating a cooling effect for the occupants.
Each heat section in this heater is equipped with a direct spark integrated control
module (circuit board). The module monitors the safety devices and controls the
operation of the fan and venter motors and the gas valve between heat cycles.
FIGURE 13 – DSI
Integrated Control
Module (circuit
board) in Each
Heat Section
Supply
Voltage
Connections
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 18
Spark
Transformer
x
Plug
Control
Fuse
Thermostat
Connections
Dip
Switch
Fan/Blower
Off
Delay
Status
Lights
LED
Lights
Normal Heat
Cycle Operating
Sequence
NOTE: All LED Flash
Codes are on page 38.
Swit ch Settng Chart for Fan
OFF Delay (See SW1 on W.D.)
TIMESW1SW2
90 secOFFON
120 secOFFOFF
160 secONOFF
45 secONON
1) Call for Heat - The thermostat calls for heat by energizing the “W” terminal. The
control checks to see that the limit and high limit switches are closed and the heat section
pressure switch is open and the main combustion air pressure switch (Sizes 800 and
1200) is open. If the limit or high limit switch is open, the control responds as defined in
the “Abnormal Heat Cycle, Limit Switch Operation”. If the heat section pressure switch
or main combustion air pressure switch are closed, the control will do four flashes on the
green LED and wait indefinitely for the heat section pressure switch or main combustion
air pressure switch to open. If the heat section pressure switch and main combustion air
pressure switch are open, the control proceeds to prepurge.
2) Prepurge - The control energizes the heat section venter motor and main venter motor
(Sizes 800 and 1200) and waits for the heat section pressure switch and main combustion
air pressure switch to close. If the heat section pressure switch or main combustion air
pressure switch does not close within 30 seconds of the heat section venter motor and
main venter motor energizing, the control will do two flashes on the green LED. The
control will leave the heat section venter motor and main venter motor energized indefinitely as long as the call for heat remains and the heat section pressure switch or main
combustion air pressure switch is open.
When the heat section pressure switch and main combustion air pressure switch are proven
closed, the control begins the prepurge time. If flame is present any time while in prepurge,
the prepurge time is restarted. If flame is present long enough to cause lockout, the control responds as defined in “Fault Modes, Undesired Flame”.
The control runs the heat section venter motor and main venter motor for a 20 second
prepurge time, then proceeds to the ignition trial period.
3) Ignition T rial Period - The control energizes the spark and main gas valve. The venter
remains energized. If flame is sensed during the first 16 seconds, the spark is de-energized and the control proceeds to heat fan on delay. If flame has not been sensed during
the first 16 seconds, the control de-energizes the spark output and keeps the gas valve
energized for an additional one second flame proving period. If flame is not present after
the flame proving period, the control de-energizes the gas valve and proceeds with ignition re-tries as specified in “Abnormal Heat Cycle, Ignition Re-try”. If flame is present,
the control proceeds to the fan on delay.
4) Fan On Delay - The control waits for 30 seconds from the time the gas valve opened
and then energizes the fan motor. The gas valve, heat section venter motor, and main
venter motor remain energized. The control proceeds to steady heat mode.
5) Steady Heat - Control inputs are continuously monitored to ensure limit, high limit,
heat section pressure switch, and main combustion air pressure switch are closed, flame
is established, and the thermostat call for heat remains. When the thermostat call for heat
is removed, the control de-energizes the gas valve and begins post-purge and fan off
delay timing.
6) Post Purge - The heat section venter motor and main venter motor outputs remain on
for a 45 second post-purge period after the thermostat is satisfied.
7) Fan Off Delay - The fan motor is de-energized after a fan off delay as selected by the
dip switches. Timing begins when the thermostat is satisfied. Delay times are as in the
table on the left. The factory default when shipped is 120 seconds.
Abnormal Heat
Cycle Functions
Interrupted Thermostat Call for Heat - If the thermostat demand for heat is removed
before the flame is recognized, the control will run the heat section venter motor and
main venter motor for the post purge period and de-energize all outputs.
If the thermostat demand for heat is removed after successful ignition, the control will
de-energize the gas valve, run the heat section venter motor and main venter motor through
post purge, and run the fan motor on heat speed for the selected delay off time.
Ignition Retry - If flame is not established on the first trial for ignition period, the control
de-energizes the gas valve and the heat section venter motor and main venter motor
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 19
20. Ignition
System
(cont’d)
Abnormal Heat
Cycle Functions
(cont’d)
remain energized for an inter-purge period of 10 seconds. The spark and gas valve are
then re-energized, and the control initiates another trial for ignition.
If flame is not established on the second trial for ignition, the control de-energizes the gas
valve, energizes the fan motor on heat speed, and the heat section venter motor and main
venter motor remain energized. The fan motor is shut of f after the longest selectable fan
delay time (160 seconds). When the fan motor de-energizes, the spark and gas valve are
re-energized and the control initiates another trial for ignition. (This fan delay is a selfhealing feature for an open auxiliary limit switch).
If flame is not established on the third trial for ignition period, the control de-energizes
the gas valve, and the heat section venter motor and main venter motor remain energized
for an inter-purge period of 10 seconds. The control then re-energizes the gas valve and
spark and initiates another trial for ignition.
If flame is not established on the fourth trial for ignition (initial try plus 3 re-tries), the
control de-energizes the gas valve and goes into lockout. The control goes to one flash on
the green LED to indicate ignition failure lockout.
Limit and High Limit Switch Operation - The high limit and limit switch are ignored
unless a call for heat is present (W energized). If the high limit or limit switch are open
and a call for heat is present, the control de-energizes the gas valve and turns the fan
motor on heat speed and runs the heat section venter motor and the main venter motor.
When the switch re-closes or the call for heat is lost, the control runs the heat section
venter motor and main venter motor through post purge and runs the fan motor through
the selected fan off delay. The control will return to normal operation after fan off delay
is completed.
Heat Section Pressure Switch (all sizes) and Main Combustion Air Pressure Switch
(Sizes 800 and 1200) - If the heat section pressure switch or main combustion air pres-
sure switch opens before the trial for ignition period, the heat section venter motor and
main venter motor will run through the heat section pressure switch and main combustion air pressure switch recognition delay (2 seconds), the gas valve will be de-energized,
and the heat section venter motor and main venter motor will run through the postpurge
time. The control will re-start the heat cycle at the heat section pressure switch and main
combustion air pressure switch proving state if the call for heat still exists.
Heat section pressure switch or main combustion air pressure switch opening for less
than 2 seconds during the trial for ignition period shall not interrupt the heat cycle. (Gas
valve will de-energize while the heat section pressure switch and main combustion air
pressure switch is open.)
If the heat section pressure switch or main combustion air pressure switch opens after a
successful ignition, the control will de-energize the gas valve. If flame is lost before the
end of the 2 second pressure switch recognition delay , the control will respond to the loss
of flame. If the heat section pressure switch and main combustion air pressure switch
remains open for 2 seconds and the flame remains, the control de-energizes the gas valve,
the heat section venter motor and main venter motor runs through postpurge, and the fan
motor runs on heat speed through the selected fan off delay. When the fan off delay is
over, the fan motor is de-energized, and a heat cycle is begun if the call for heat still
exists.
Continuous Fan
Operation
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 20
When the thermostat calls for continuous fan (G) without a call for heat, the fan motor is
energized after a .25 second delay. NOTE: This brief on delay is to allow the “G” terminal to energize slightly before “Y” and an external changeover relay to switch from “G”
to “W” without causing momentary glitches in the fan motor output. The fan remains
energized as long as the call for fan remains without a call for heat.
If a call for heat (W) occurs during continuous fan, the fan will de-energize.
A call for fan is ignored while in lockout.
Fault Modes
Undesired Flame - If flame is sensed longer than 20 seconds while the gas valve is deenergized, the control shall energize the heat section venter motor , the main venter motor ,
and the fan motor on heat speed. When flame is no longer sensed, the heat section venter
motor and main venter motor will run through postpurge, and the fan motor will run
through the selected heat fan off delay time. The control will do a soft lockout, but will
still respond to open limit and flame. The FLAME (yellow) LED shall flash rapidly when
lockout is due to undesired flame.
Gas Valve Relay Fault - If the control senses the gas valve as energized for more than
one second when the control is not attempting to energize the gas valve, or the gas valve
is sensed as not energized when it is supposed to be energized, then the control will
lockout with the green LED off. The control assumes either the contacts of the relay
driving the gas valve have welded shut, or the sensing circuit has failed. The heat section
venter motor is forced off to open the heat section pressure switch to stop gas flow unless
flame is present.
If the gas valve was sensed as closed when it should be open, and has not de-energized
after the heat section venter motor and main venter motor was shutoff for 15 seconds,
then the heat section venter motor and main venter motor are re-energized to vent the
unburned gas.
Lockout
21. Gas V alve(s)
• Size 400 has 1 valve.
• Size 800 has 2 valves.
• Size 1200 has 3 valves.
Soft Lockout - The control shall not initiate a call for heat or call for continuous fan while
in lockout. The control will still respond to an open limit and undesired flame. Lockout
shall automatically reset after one hour. Lockout may be manually reset by removing
power from the control for more than one second or removing the thermostat call for heat
for more than one and less than 20 seconds.
Hard Lockout (Green LED - steady off) - If the control detects a fault on the control
board, the status LED will be de-energized, and the control will lockout as long as the
fault remains. A hard lockout will automatically reset if the hardware fault clears.
Power Interruption - During a momentary power interruption or at voltage levels below
the minimum operating voltage (line voltage or low voltage), the system will self-recover
without lockout when voltage returns to the operating range.
Power interruptions of less than 80mS shall not cause the control to change operating
states. Power interruptions greater than 80mS may cause the control to interrupt the current operating cycle and re-start. Power interruption during a heat cycle may trip the
manual reset high limit switch.
The main operating gas valve(s) is powered by the 24-volt control circuit through the
thermostat and safety controls. The gas valve is of the diaphragm type providing
regulated gas flow preset at the factory. (For location, see FIGURE 22, page 33.)
WARNING: The operating valve is the prime safety shutoff. All gas
supply lines must be free of dirt or scale before connecting the heater
to ensure positive closure. See Hazard Levels, page 2.
22 Fan Motor(s)
• Size 400 has 1 fan motor.
• Size 800 has 2 fan motors.
• Size 1200 has 3 fan motors.
Each heat section in the heater has a fan motor. Each fan motor(s) is equipped with
thermal overload protection of the automatic reset type. Should the motor(s) refuse to
run, it may be because of improper current characteristics. Make certain that the correct voltage is available at the motor(s).
Fan Motor Wiring
White = Neutral
Black = High (Heat Speed)
Blue = Medium (Destratification Speed, Factory Wired)
Red = Low (Optional Destratification Speed, Field Wired)
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 21
23. Wiring
Diagrams
• Operating Sequence, Notes, Codes, Keys, etc. for ALL three typical wiring
diagrams (FIGURES 14, 15, and 16 on pages 23, 24, and 25), pages 22-23.
• FIGURE 14 - Model LDAP 400, page 23.
• FIGURE 15 - Model LDAP 800, page 24.
• FIGURE 16 - Model LDAP 1200, page 25.
CAUTION: If any of the original wire as supplied with the appliance must be replaced, it must be replaced
with wiring material having a temperature rating of at least 105°C, except for limit control, high limit
control, and sensor lead wires which must be 150°C. See Hazard Levels, page 2.
Operating Sequence, Notes, Codes, Keys, etc for ALL three typical wiring
diagrams (FIGURES 14, 15, and 16) on pages 23-25.
Operating Sequence
Wiring Diagram
NOTES
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 22
1. Set thermostat at lowest setting. With Opt CL2 or CL18, set fan switch at
“AUTO” position.
2. Turn on the manual gas valve(s).
3. Turn on power to the heater.
4. Set thermostat at desired setting.
5. Thermostat calls for heat, energizing the venter motor(s).
6. Main combustion air pressure switch (Sizes 800 and 1200) and heat section
pressure switch(es) close, firing heat section(s) (Unit fires at low fire when
using two-stage thermostat).
7. Burner flame is sensed, and in 30 seconds the fan motor(s) is energized.
8. High stage of thermostat calls for heat, firing all heat sections at full rate (on
heaters with a two-stage thermostat).
9. With Opt CL2 or CL18, set fan switch at “ON” position for continuous fan
operation.
10.If the flame is extinguished during main burner operation, the integrated
control system closes the main valve of that heat section and must be reset by
interrupting power to the control circuit (see lighting instructions).
1. The following controls are field-installed options: Thermostat
2. Dotted wiring installed by others.
3. CAUTION: If any of the original wiring as supplied with the appliance must be
replaced, it must be replaced with wiring material having a temperature rating of
at least 105°C, except for sensor lead wire and limit wiring which must be
150°C.
4. Use 18 gauge wire for all wiring on the heater.
5. Line and fan motor branch wire sizes should be of a size to prevent voltage
drops beyond 5% of supply line voltage.
6. Size 400, see thermostat wiring diagram in FIGURE 10, page 15. Size 800, see
thermostat wiring diagram in FIGURE 11, page 15. Size 1200, see thermostat
wiring diagram in FIGURE 12, page 16.
7. The control transformer has a dual voltage primary.
For 230V heaters, the black lead goes to the “240” terminal. Cap the “208”
terminal.
For 208V heaters, the black lead goes to the 208” terminal. Cap the “240”
terminal.
8. When providing or replacing fuses in the fusible disconnect switch, use dual
elements time delay fuses and size according to 1.25 times the maximum total
input amps.
9. The line side of the lockable disconnect switch must be connected to the incoming power supply such that the voltage between Terminal L1 and Ground is the
greater value.
g
Wiring
Color
Codes
Black - BK
Brown - BR
Red - R
Orange - O
Yellow - Y
Green - G
Switch Set tng Ch art for Fan
OFF Delay (See SW1 on W.D.)
TIMESW1SW2
90 secOFFON
120 secOFFOFF
160 secONOFF
45 secONON
Fan Motor Wiring
White = Neutral
Black = High (Heat Speed)
Blue = Medium (Destratification Speed, Factory Wired)
Red = Low (Optional Destratification Speed, Field W ired)
th
150 ft (46M)75 ft (23M)18 Gauge
250 ft (76M)125 ft (38M)16 Gauge
350 ft (107M)175 ft (53M)14 Gauge
Field Control Wiring
Distance from Unit
to Control
Mi nimum Recommended
Wire Gauge
FIGURE 14 – T ypical Wiring Diagram for Model LDAP 400 (Reference W . D. 189374, Rev 2)
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
208 OR 230/1/60
N
See NOTE 6 on Page 22.
HONEYWELL
ALT.
TWO STAGE
GAS VALV E
MV
LOW
C
HIGH
O
HI
HONEYWELL
ALT.
SINGLE STAGE
GAS VALV E
GAS VALVE
BL
CUSTOMER'S FUSIBLE
DISCONNECT SWITCH
(SEE NOTES on page 22.)
GRD
G
L1L3
C
Y1
W
B
L1
PR
Y
R
O
HONEYWELL
TWO STAGE
GAS VALV E
O
STG
STG
Y2
G
W1
R
W2
TERMINAL STRIP
BL
BR
BL
BR
LOCKABLE
MANUAL
RESET
HIGH LIMIT
CONTROL
R
PRESSURE
Y
LO
LOW
C
HIGH
HI
ON/OFF
L3T3
L2T2
BL
8
BL
8
RR
SWITCH
BL
STG
BR
FLAME
STG
ELECTRODE
FLAME
T1L1
LIMIT
CONTROL
GROUND
DISCONNECT
Y
BK
R
R
Y
Y
BL
BR
R
BR
P3-2
P3-3
P3-4
P3-5
P1-8
P1-3
P1-6
P1-5
P1-4
P1-2
P1-7
P3-1
P1-9
ADJUSTABLE
DESTRAT
FAN CONTROL
B
BL
BK
Y
SEE CHART AT TOP OF PAGE FOR
G
W
R
C
SWITCH SETTINGS
DSI CONTROL
R
SW1
LINE VOLTAGE
(SEE NOTE 7 on page 22.)
B
BL
RBLR
108
BR
Y
NEUTRALL1SECCOM
L1
FUSE
3.0 AMP
ATO OR ATC
M1
NEUTRAL
NEUTRAL
EAC/BLO
TEST
OKFLAME
LED
LED
GY
NEUTRAL
SPARK
TRANSFORMER
IND
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 23
COM
40 VA. CONTROL
BR
Y
TRANSFORMER
FAN
PERMISSIVE
RELAY CONTACTS
O
PR
425
BK
R
W
Y
BK
BK
W
SPARK GAP
N
GRD
SCREW
PR
DESTRAT RELAY
PRB
C
24
20uF CAPACITOR
REMOTE MOUNTED
BR/W
BK
FAN
MOTOR
R
28
CR
3Y1
VENTER
MOTOR
W
BR/W
4uF CAPACITOR
REMOTE MOUNTED
R
31
315CR 1
16
W
33
CR
G
G
CONTACTS
BR
G
B
W
BK
BK
BR
11
GRD
G
GRD
G
BR
7
BR
7
BR
7
BR
7
REMOTE DESTRAT
RELAY CONTACTS
BL
YB
DESTRAT
RELAY COIL
22
REMOTE
DESTRAT
RELAY COIL
21
Y
L3
PR
B
24
BL
F
FAN PERMISSIVE
RELAY COIL
22 - 23
23. Wiring Diagrams (cont’d)
FIGURE 15 – T ypical W iring Diagram for Model LDAP 800 (Refer ence W.D. 189375, Rev 2)
6
7
8
208 OR 230/1/60
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
N
L1
BK
L1
L1
BK
L1
L1
L1
L1
BK
L1
CUSTOMER'S FUSIBLE
SWITCH
GRD
G
GG
BK
BK
BK
BK
BK
BL
8
BL
8
BL
8
BL
8
BL
8
BL
BK
SEE NOTE 6 ON PAGE 22.
BL
BL
8
(SEE NOTES on page 22.)
#1 VENT PERMISSIVE
RELAY CONTACTS
2
MAIN COMBUSTION AIR
PRESSURE
CBLNO
ADJUSTABLE
FAN CONTROL
G
PR
W1
Y
R
R
W2
C
Y2
Y1
TERMINAL STRIP
UNIT #1
DISCONNECT
4
SWITCH
DESTRAT
MANUAL
RESET
HIGH LIMIT
CONTROL
R2R
PRESSURE
SWITCH
Y
LOCKABLE
DISCONNECT
L3 T3
L3 T2
T1L1
PR
R
LIMIT
CONTROL
#1 HEAT PERMISSIVE
RELAY CONTACTS
Y
GAS VALVE
BL
FLAME
ELECTRODE
FLAME
GROUND
ON/OFF
Y
BK
LINE VOLTAGE
(See NOTE 7 on page 22.)
BK
BL
O
O
9
O
O
9
R
R
10
R
R
10
BK
L1
Y
P3-1
G
P3-2
W
P3-3
P3-4
R
R
P3-5
C
P1-8
R
P1-3
R
P1-6
Y
P1-5
Y
4
P1-4
BL
BR
P1-2
P1-7
R
BR
P1-9
CONTROL
BL
B
#2 VENT PERMISSIVE
RELAY CONTACTS
BK
24
COM
Y
40 VA. CONTROL
TRANSFORMER
BR
BL
SW1
SEC
SEE CHART PAGE 23 FOR
SWITCH SETTINGS
3.0 AMP
ATO OR ATC
TEST
OK
FLAME
LED
G
#1DSI
LED
BR
Y
PR
FUSE
A
BR
COM
BK
PR
A
PR
Y
NEUTRAL
M1
NEUTRAL
NEUTRAL
EAC/BLO
IND
NEUTRAL
SPARK
TRANSFORMER
Y
L1
#1 FAN
PERMISSIVE
RELAY CONTACTS
O
4
R
W
Y
BK
BK
W
J
W
SPARK GAP
LINE VOLTAGE
(See NOTE 7 on page 22.)
BK
BL
G
N
G
GRD
SCREW
PR
#1 DESTRAT
RELAY CONTACTS
PR
PR
C
2
5
BK
20uF CAPACITOR
2
REMOTE MOUNTED
BK
BR/W
G
BK
BL
FAN
MOTOR
R
W
BK
36
Y
CR
3
1
BK
VENTER
MOTOR
W
BK
BR
BR/W
4uF CAPACITOR
REMOTE MOUNTED
G
BL
2
GR
H
GRD
G
W
R
3
COM
3BR1
42
CR
Y
40 VA. CONTROL
TRANSFORMER
BR
21
O
CR
3
23
CR
#1 REMOTE DESTRAT
RELAY CONTACTS
PR
2
BL
BL
F
BK
BK
1
W
BK
1
R
BL
4
BR
3
45
MAIN
VENTER MOTOR
& CAPACITOR
20
O
CR
3
BR
BR
22
CR
1
BR
1
1CR33
BR
Y
L3
Y
L3
Y
L3
BR
7
BR
7
#1 HEAT
BR
1
BR
7
BR
7
BR
BR
7
7
PERMISSIVE
RELAY COIL
7
38
#2 HEAT
PERMISSIVE
7
RELAY COIL
62
#1 DESTRAT
7
RELAY COIL
30
#2 DESTRAT
RELAY COIL
54
7
Y
L3
Y
#1 FAN
PERMISSIVE
RELAY COIL
30 - 31
#1 VENT
PERMISSIVE
RELAY COIL
13
#1 REMOTE
DESTRAT
RELAY COIL
7
29
Y
Y
L3
The above control wiring is
repeated in the second heat section.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 24
FIGURE 16 – T ypical Wiring Diagram for Model LDAP 1200 (Reference W . D. 189376, Rev 2)
ON/OFF
RELAY CONTACTS
4
2
LINE VOLTAGE
PRESSURE
SWITCH
NOC
DESTRAT
PR
Y
R
MANUAL
RESET
HIGH LIMIT
CONTROL
R
PRESSURE
SWITCH
Y
Y
W
TERMINAL STRIP
UNIT #1
LOCKABLE
DISCONNECT
L3
T3
L3 T2
T1
L1
PR
BK
COM
40 VA. CONTROL
TRANSFORMER
BR
LIMIT
CONTROL
RR
#1 HEAT PERMISSIVE
RELAY CONTACTS
24
GAS VALVE
BL
FLAME
ELECTRODE
FLAME
GROUND
Y
BK
BK
PR
A
PR
PR
SW1
3.0 AMP
TEST
FLAME
LED
Y
A
ATO OR ATC
COM
FUSE
A
Y
40 VA. CONTROL
TRANSFORMER
BR
R
BR
NEUTRAL
NEUTRAL
EAC/BL
NEUTRAL
SPARK
TRANSFORMER
27
3BR1
CR
Y
NEUTRALL1 SECCOM
L1
M1
IND
#3 VENT PERMISSIVE
RELAY CONTACTS
Y
9
OO
9
9
10
R
10
R
10
R
R
Y
Y
BL
BR
R
BR
PRPRPR
42
LINE VOLTAGE
(SEE NOTE 7 on page 22.)
BK
BL
O
O
OO
RBLR
R
R
BL
BK
P3-1
P3-2
P3-3
P3-4
P3-5
P1-8
P1-3
P1-6
P1-5
P1-4
P1-2
P1-7
P1-9
SEE CHART PAGE 23 FOR
Y
G
W
R
C
#1DSI
SWITCH SETTINGS
OK
LED
G
CONTROL
LINE VOLTAGE
(SEE NOTE 7 on page 22.)
BK
BL
24
31
CR
26
R
31
CR
PR
#1 FAN
PERMISSIVE
RELAY CONTACTS
O
425
R
W
Y
BK
BK
W
SPARK GAP
PR
BK
J
W
RELAY CONTACTS
PR
C
20uF CAPACITOR
REMOTE MOUNTED
BR/W
BK
MOTOR
R
3Y1
VENTER
MOTOR
W
BR/W
4uF CAPACITOR
REMOTE MOUNTED
COM
BR
BR
G
N
G
GRD
SCREW
#1 DESTRAT
BL
24
BR
G
GRD
BL
FAN
W
40
BK
CR
BK
H
BK
BR
WBK
B
Y
40 VA. CONTROL
TRANSFORMER
BR
O
R
GRD
G
#1 REMOTE DESTRAT
BL
G
46
CR
W
3
348CR11
BR
23
31
CR
25
BR
31
CR
RELAY CONTACTS
PR
2
4
BL
F
BK
13
MAIN
VENTER MOTOR
& CAPACITOR
O
BR7BR
BR
BL
GG
22
31
CR
BR
BR
7
BR
CUSTOMER'S FUSIBLE
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
208 OR 230/1/60
GRD
G
N
L1
BK
L1
L1
BK
BK
L1
L1
BK
L1
L1
L1
L1
L1
DISCONNECT SWITCH
(SEE NOTES on page 22.)
BK
#1 VENT PERMISSIVE
RELAY CONTACTS
BK
2
BK
BK
4
PR
#2 VENT PERMISSIVE
BK
(SEE NOTE 7 on page 22.)
BK
87
8
8
8
8
8
BL
B
B
BL
BL
BLBR
BLBR
MAIN COMBUSTION AIR
BLO
ADJUSTABLE
FAN CONTROL
BL
G
W1
R
W2
C
Y2
See NOTE 6 on Page 22.
Y1
Y
L3
Y
L3
Y
L3
Y
L3
BR
7
7
#1 HEAT
PERMISSIVE
RELAY COIL
BR
7
42
#2 HEAT
PERMISSIVE
BR
RELAY COIL
7
7
7
7
64
#3 HEAT
PERMISSIVE
RELAY COIL
86
#1 DESTRAT
BR
RELAY COIL
7
34
#2 DESTRAT
RELAY COIL
56
#3 DESTRAT
RELAY COIL
78
BR
7
Y
L3
#1 FAN
PERMISSIVE
RELAY COIL
34 - 35
#1 VENT
PERMISSIVE
RELAY COIL
12
#1 REMOTE
DESTRAT
BR
RELAY COIL
7
33
8
L3
The above control wiring is
repeated in the second and third heat sections.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 25
24. V enting
Model LDAP heaters are certified as Category III heaters.
WARNING: Each heater requires its own individual vent pipe run
and vent cap. Manifolding of vent runs can cause recirculation of
combustion products into the building. Failure to comply could
result in severe personal injury or death and/or property damage.
Venting must be in accordance with local codes and the National Fuel Gas Code
Z223.1 or CSA B149.1 and B149.2, Installation Code for Gas Burning Appliances
and Equipment. Local requirements supersede national requirements.
These power-vented heaters are designed to operate safely and efficiently with either
a horizontal or vertical vent. Comply with the specific requirements and instructions.
If this heater is replacing an existing heater, be sure that the vent is sized properly for
the heater being installed and that the existing vent is in good condition. A properly
sized vent system is required for safe operation of the heater. An improperly sized
vent system can cause unsafe conditions and/or create condensation. Do not vent into
an existing gravity vent or chimney .
Installation should be done by a qualified agency in accordance with these instructions. The qualified service agency installing this system is responsible for the installation.
Venting
Requirements
2) V ent Pipe Diameter
and Length
1) T ype of Vent Pipe
The type of vent pipe is determined by whether the vent is horizontal or vertical.
Horizontal• Vent pipe approved for a Category III appliance, OR
• Appropriately sealed 26-gauge or heavier galvanized
steel or equivalent single-wall pipe
Vertical• Vent pipe approved for a Category III appliance, OR
• Appropriately sealed 26-gauge or heavier galvanized
steel or equivalent single-wall pipe
OR, if at least 75% of the equivalent length of the vent run is vertical
• Double-wall (Type B) vent pipe
V ent pipe diameters and maximum vent lengths in the table apply to both HorizontalandVertical vents. Add all straight sections and equivalent lengths for elbows. The
total combined length must not exceed the Maximum V ent Length.
• Use only one diameter of vent pipe on an installation.
• Minimum vent length is 3 feet (1M).
• Minimum of 1 ft (0.3M) of vertical vent required on venter outlet before installing
an elbow.
Model
LDAP
Size
400
800
1200
1
Includes one 9 0° elbow at venter outl et.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 26
Venter
Outlet
Diameter
inchesmminchesmmfeetMfeetMfeetM
6152
8203
8203
Vent Pip e
Diameter
61524513.7154.67.52.3None
71786018.382.441.26" to 7" (152 to 178mm) Increaser
82035015.2154.67.52.3None
102544513.751.52.50.88" to 10" (203 to 254mm) Increaser
82035015.2154.67.52.3None
102544513.751.52.50.88" to 10" (203 to 254mm) Increaser
Vent Length
Maximum
1
Eqivalent
Straight Length
for 90° Elbow
Equiv a lent
Straight Length
for 45° Elbow
Field-S upplied Taper Type
Connection Required at the Venter
Outlet
3) V enter (Flue)
Outlet
Venter Outlet Attachment Requirements:
Model
LDAP
Size
400
800
1200
Venter O utlet
Diameter
inchesmm
6152
8203
8203
Depending on the size of vent pipe
as determined in Step No. 2, attach
either the vent pipe directly to the
venter collar or a taper-type enlarger .
Follow instructions in Requirement No. 4. below to make
the connection for the type of pipe being used.
Taper-type
Pipe
Airflow
Diameter
Increaser
4) Joints and Sealing
FIGURE 17A Attaching DoubleWall (Type-B) Vent
Pipe to the Venter
Outlet
A double-wall pipe
run is allowed only if
at least 75% of the
vent length is vertical.
Figure 17A - STEP 1
Slide the
double-wall
pipe over
the collar
so that the
collar is
inside the
inner pipe.
Provide field-supplied vent pipe as specified in Requirement No. 1.
• If using single wall, 26-gauge or heavier galvanized pipe, secure slip-fit connec-
tions using sheetmetal screws or rivets. Seal pipe joints either with tape suitable for
550°F (such as Option FA1, P/N 98266) or high-temperature silicone sealant.
• If using Category III vent pipe, follow pipe manufacturer's instructions for join-
ing pipe sections. When attaching Category III pipe to the venter outlet or the vent
cap, make secure, sealed joints following a procedure that best suits the style of
Category III pipe being used.
• If installing a double-wall (T ype B) terminal pipe, follow the instructions in FIG-URE 17C to join the double-wall pipe to a single-wall or Category III vent pipe
run. To attach the vent cap, follow instructions in FIGURE 17B.
• If using double-wall (Type B) vent pipe in the vent pipe run (at least 75% of the
equivalent vent length must be vertical), follow the pipe manufacturer's instructions for joining pipe sections. For attaching double-wall pipe to the heater, see
FIGURE 17A. To attach the vent cap, see FIGURE 17B.
Figure 17A - STEP 2
DoubleWall
Pipe
Venter
Collar
To secure the connection,
spaced equal distance around
the pipe, drill and insert three
3/4” long sheetmetal screws
through the pipe and into the
collar. Do not over tighten the
screws.
Fill inside the pipe, around the collar, with
silicone sealant being sure there are no gaps.
FIGURE 17B - Attaching Double-Wall (Type B) Pipe to a Vent Cap
Figure 17B - STEP 1
Place a continual 3/8” bead of
silicone sealant around the
circumference of the vent cap collar.
This will prevent any water inside
the vent cap from running down the
double-wall pipe.
Figure 17B - STEP 2
Insert the collar on the vent cap inside the
inner wall of the double-wall pipe. Insert as
far as possible. Add additional silicone sealant
to fully close any gaps between the vent cap
and the double-wall pipe. This is necessary to
prevent water from entering the double-wall
pipe.
Do STEP 2
immediately
following
STEP 1.
Figure 17B - STEP 3
Secure the vent cap to the
double-wall pipe by drilling
and inserting a
3/4” long sheetmetal screw
into the vent cap collar. Do
not over tighten screw.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 27
quip
24. V enting
(cont’d)
Venting
Requirements
(cont’d)
4) Joints and Sealing
(cont’d)
FIGURE 17C - Attaching
Double-Wall (Type B)
Terminal Pipe to a Single
Wall or Category III Vent
Pipe Run
Figure 17C -
On the single-wall pipe or Category
III pipe, place a continual
1/4 inch bead of silicone sealant
around the circumference.
STEP 1
Do STEP 2 immediately after
STEP 1.
SingleW all or
Category
III Vent
Pipe
Figure 17C - STEP 3
Spaced equally around the double-wall
pipe, drill three small holes below the
sealant ring. Insert 3/4 inch long
sheetmetal screws to secure the joint. Do
not over tighten screws.
Figure 17C -
Insert the pipe with the sealant into the
inner pipe of the double-wall pipe until
the bead of sealant contacts the inner
pipe creating a sealed joint.
Double-
Wall
Pipe
STEP 2
Vent
Pipe
with
Sealant
5) V ent System
Support
6) Condensation
7) V ent T erminal
(Pipe and V ent
Cap)
Support horizontal vent runs every six feet (1.8M). Support vertical runs of Type
“B” double-wall or Category III vent pipe in accordance with the requirements of
the pipe manufacturer. Support single-wall pipe in accordance with accepted industry practices. Do not rely on the heater for support of either horizontal or vertical
vent pipe. Use non-combustible supports on vent pipe.
Any length of single-wall vent pipe exposed to cold air or run through an unheated
area or an area with an ambient temperature of 45°F or less must be insulated along
its entire length with a minimum of 1/2" foil-faced fiberglass, 1-1/2# density insulation. Where extreme conditions are anticipated, install a means of condensate
disposal.
The vent terminal pipe must be either Category III vent pipe or double-wall (Type
B). Heaters must be equipped with a Reznor vent cap, a Type L Breidert Air-xhauster® vent cap or equivalent. A different style vent cap could cause nuisance
problems or unsafe conditions. The vent cap must be the same diameter as the vent
pipe.
See the clearance table below and FIGURE 18 for requirements of a horizontal
vent terminal. See FIGURE 19 for requirements of vertical vent termination.
Horizontal Vent Terminal Clearances
A vent cap is required. Maintain a minimum
clearance of 12 inches (305mm) from the wall
to the vent terminal cap for stability under
wind conditions.
Products of combustion can cause discoloration of some building finishes and deterioration of masonry materials. Applying a clear
silicone sealant that is normally used to protect concrete driveways can protect masonry
materials. If discoloration is an esthetic problem, relocate the vent or install a vertical vent.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 28
Structure
Forced air inlet within 10 ft (3.1M)3 ft (0.9M) above
C ombusti on a ir inl e t of another a ppliance 6 ft (1 .8M)
Door, window, or gravity air inlet (any
bui lding ope ning)
El e c t ric meter , gas me t e r*, gas re gulator*,
and relief e
G as regulator *U.S. - 3 ft (0.9M); Canada - 6 ft (1.8M)
Adj oining building or par apet6 ft (1.8M)
Adjacent public walkways7 ft (2.1M) above
Grade (ground level)1 ft (3 05mm ) above**
*Do not t erminate the ven t direc tly above a ga s meter or servi c e regula tor.
** C on sider lo cal snow depth conditions. The vent must be at least 6” (15 2m m) higher tha n
anticipat e d snow depth.
ment
M inimum Clearances for Vent Termination
Location ( all directions unless sp ecified)
4 ft (1.2M) horizontally
4 ft (1.2M) below
1 ft (3 05mm ) above
U.S. - 4 ft (1.2M) horizontally
Canada - 6 ft (1.8M) horizontally)
FIGURE 18 - Horizontal Vent Terminal
)
)
NOTE: Read all measurements; drawing is not proportional.
*Follow the instructions in FIGURES 16B and 16C, pages
26 and 27, to join a double-wall vent terminal section to a
single-wall vent run and to the vent cap.
Roof or Building Overhang
Wall
12
( 305 mm)
6 (152mm)
minimum
Double-Wall* or Category III
Terminal Vent Pipe
Vent Run
(Comply
with Requirements
No. 1) & 2)
on page 25.)
Pitch flue pipe down toward
outlet 1/4 per foot for condensate drainage. (NOTE: Slope
applies to entire horizontal vent run.)
A clearance thimble is required when flue pipe extends through combustible
materials. Follow the requirements of the thimble and/or the vent pipe manufacturer.
FIGURE 19 - Vertical Vent Terminal
NOTE: Read all measurements; drawing is not proportional.
3 ft (1M)
minimum
6 ft (1.8M) minimum
Reznor (Option CC1)
or Equivalent Vent Cap note positions of vent cap
openings (shaded areas)
Parapet or Adjoining Building
6 ft (1.8M)
minimum
Double-Wall* or Category III
Terminal Vent Pipe*
Parapet or Adjoining Building
*Follow the instructions in FIGURES 16B
and 16C, pages 26 and 27, to join a doublewall vent terminal section to a single-wall
vent run and to the vent cap.
Roof Flashing
6 (152mm) minimum
Reznor (Option CC1)
or equivalent vent cap
Vertical flue extension must
be 6 (152mm) higher than
anticipated snow depth but
no less than 2 ft (610mm) above
the roof.
Roof pitched
from
0 to 45°
A clearance thimble is required when
flue pipe extends through combustible
materials. Follow the requirements
of the thimble and/or the vent pipe
manufacturer.
Vent Pipe (Comply with Requirements
No. 1
and 2) on page 25.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 29
25. Check
Installation
and Startup
Check the
installation prior
to startup:
Check to be sure that all screws used to hold shipping brackets were re-installed
in the heater cabinet.
Check suspension. Heater must be secure and level.
Check clearances from combustibles. Requirements are in Paragraph 8.
Check vent system to be sure that it is installed according to the instructions in
Paragraph 24.
Check piping for leaks and proper gas line pressure. Bleed gas lines of trapped
air. See Paragraph 12.
Check electrical wiring. Be sure all wire gauges are as recommended. Verify that
fusing or circuit breakers are adequate for the load use.
Check polarity. Verify that line voltage exists between the black “L1” and earth
ground.
If installed in California, verify that California Warning Label is displayed
Heater
Startup and
W arnings:
WARNINGS: For your safety, read before operating. If you do
not follow these instructions exactly, a fire or explosion may
result causing property damage, personal injury, or loss of life.
• This appliance does not have a pilot. It is equipped with an ignition
device which automatically lights the burner(s). Do not try to light the
burner(s) by hand.
• Before operating, smell all around the appliance area for gas. Be sure to
smell next to the floor because some gas is heavier than air and will settle
on the floor.
WHA T T O DO IF YOU SMELL GAS
• Open windows.
• Don’t touch electrical switches.
• Extinguish any open flame.
• Immediately call your gas supplier.
• Use only your hand to turn the gas control ON/OFF knob on the gas
valve. Never use tools. If the valve ON/OFF knob will not turn by hand,
do not try to repair it. Call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
• Should overheating occur, or the gas supply fail to shut off, turn off the
manual gas valve to the appliance before shutting off the electrical
supply.
• Do not use this appliance if any part has been under water. Immediately
call a qualified service technician to inspect the appliance and to replace
any part of the control system and any gas control which has been under
water.
Operating
Instructions and
Operating Sequence
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 30
1. Set thermostat at lowest setting.
2. Turn off all electric power to the appliance.
3. This appliance is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand. Open the access door(s) and
locate the gas control (ON/OFF) knob on the gas valve(s). (See FIGURE 20.)
4. Turn each gas control knob(s) clockwise to "OFF".
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the
floor. If you smell gas, STOP! and follow the steps in the WARNINGS printed
above or on the Operating Label on the heater. If you do not smell gas, proceed
to the next step.
6. Turn the gas control knob(s) counterclockwise to "ON".
7. Close the access door(s).
8. Turn on the electric power to the heater.
9. Set the thermostat to the desired setting.
FIGURE 20 - Gas Valve
ON/OFF Control Knob
Top View
Gas Control
Knob
(shown in the
ON position)
Gas
Flow
Side View
Gas
Flow
Check installation
after startup:
Place the "Owner's Envelope"
containing the Limited
Warranty, this booklet, and
any control or optional
information in an accessible
location near the heater.
Follow the instructions on the
envelope.
NOTE: If the appliance does not operate, follow the instructions "To Turn Off Gas
to Appliance" printed below (and on the Operating Label on the heater) and call
your service technician.
10. Thermostat calls for heat, energizing the venter motor(s).
11. The main combustion air pressure switch (Sizes 800 and 1200) and each heat
section pressure switch close, firing the heater.
12. Burner flame is sensed and in 30 seconds after the gas valve is energized, the
fan motor(s) is energized.
13. If the flame is extinguished during the main burner operation, the integrated
control system closes the main valve and must be reset by interrupting power
to the control circuit. (See lighting instructions on the heater.).
TO TURN OFF GAS TO THE APPLIANCE
1) Set thermostat to lowest setting
2) If service is to be performed, turn off all electric power to the appliance.
3) Open the access door(s).
4) Turn the gas control knob(s) clockwise to "OFF". Do not force.
5) Close the access door(s).
Vent System Testing Procedure
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in
the National Fuel Gas Code, ANSI Z223.1 or CSA B149.1 and B149.2,
Installation Code for Gas Burning Appliances and Equipment, and this
manual. Determine that there is no blockage or restriction, leakage, corrosion
or other deficiencies that could cause an unsafe condition.
3. In so far as practical, close all building doors and windows and all doors
between the space where the heater is and other spaces of the building. Turn
on exhaust fans so they shall operate at maximum speed. Do not operate a
summer exhaust fan.
4. Light the heater following the lighting instructions. Adjust the thermostat for
continued operation. Verify that combustion products are venting properly.
After determining that the heater vents properly, return doors, windows, and
exhaust fans to their previous conditions. If improper venting is observed, the
venting system must be corrected.
With the heater in operation, measure valve outlet gas pressure. If operated at
high altitude, adjust outlet gas pressure for altitude. See information and instructions in Paragraph 12.
Using the thermostat, turn the heater off and on, pausing two minutes between
each cycle. Observe for smooth ignition.
DANGER: The gas burner in this gas-fir ed equipment is designed and equipped to provide safe controlled
complete combustion. However , if the installation does not permit the burner to receive the proper supply
of combustion air, complete combustion may not occur. The result is incomplete combustion which
produces carbon monoxide, a poisonous gas that can cause death. Safe operation of indirect-fired gas
burning equipment requires a properly operating vent system that vents all flue pr oducts to the outside
atmosphere. FAILURE TO PROVIDE PROPER VENTING WILL RESULT IN A HEALTH HAZARD
WHICH COULD CAUSE SERIOUS PERSONAL INJURY OR DEATH.
Always comply with the combustion air requirements in the installation codes and in Paragraph 9.
Combustion air at the burner should be regulated only by manufacturer-provided equipment. NEVER
RESTRICT OR OTHERWISE ALTER THE SUPPLY OF COMBUSTION AIR TO ANY HEATER.
Heaters installed in a confined space must be supplied with air for combustion as requir ed by Code and
in Paragraph 9 of this heater installation manual. MAINTAIN THE VENT SYSTEM IN
STRUCTURALLY SOUND AND PROPER OPERATING CONDITION.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 31
OPTIONAL
ACCESSORIES
All Model LDAP heaters have discharge louvers but are available with additional
louvers and/or nozzle discharge air options. Optional louver and discharge nozzles
are shipped separately for field installation. Model LDAP 800 and 1200 heat sections
have independent airflow and do not require the same discharge options. Each package includes illustrated installation instructions.
26. 4-Way
Discharge
Louvers,
Option CD32
27. Nozzles
FIGURE 21A - One heat
section with Option CD58,
60° Nozzle
Standard individually adjustable louvers are installed in
the nozzle discharge.
Option CD32 consists of additional louvers that are installed perpendicular to the
standard individually adjustable louvers. By installing the optional perpendicular louvers, the two sets of louvers can be adjusted to direct airflow in any of the four
directions, enabling the installer to select and increase or decrease the coverage area.
Option CD57 is a 30° discharge nozzle. Option CD58 is a 60° discharge nozzle.
Option CD59 is a 30° discharge nozzle with 4-way louvers. A nozzle may be installed
at each discharge air opening in any direction. NOTE: Do not install 4-way louvers
with a 60° nozzle.
Nozzles should be attached after the unit is suspended. Follow the installation instructions in the nozzle package.
FIGURE 21B Nozzle
Dimensions
Option CD58,
60° Nozzle
Option CD57,
30° Nozzle
24-3/8
(618mm)
14-1/8
(360mm)
Option CD59, 30° Nozzle
with 4-Way Louvers
16-1/2
(419mm)
MAINTENANCE
AND SERVICE
WARNING: If you turn off
the power supply, turn off
the gas. See Hazard Levels,
page 2.
28. Maintenance
Schedule
NOTE: If replacement
parts are required, use only
factory-authorized parts.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 32
The material contained in the MAINTENANCE AND SERVICE Section of this
manual is designed to aid a qualified service person in maintaining and servicing this
equipment. This heater will operate with a minimum of maintenance. To ensure long
life and satisfactory performance, a heater that is operated under normal conditions
should be inspected and cleaned at the start of each heating season. If the heater is
operating in an area where an unusual amount of dust or soot or other impurities are
present in the air, more frequent maintenance is recommended.
When any service is completed, be careful to reassemble correctly to ensure that no
unsafe conditions are created. When re-lighting, always follow the lighting instructions
on the heater.
Maintenance Schedule - The following procedures should be carried out at least
annually . Refer to illustrations and follow the instructions in Paragraphs 29-42.
• Clean all dirt, lint, and grease from all combustion air openings and the venter
assemblies.
• Clean all dirt, lint, and grease from all fan blades, fan guards, and motors.
• Check all heat exchangers both internally and externally .
• Check all burners for scale, dust, or lint accumulation. Clean if needed.
• Check gas valve(s) to ensure that gas flow is being shutoff completely.
• Check the vent system for soundness. Clean openings. Replace any parts that
do not appear sound.
• Check the wiring for any damaged wire. Replace damaged wiring. (See
Paragraph 14 for replacement wiring requirements.)
FIGURE 22 - Location of Controls
Venter Motor
24V Thermostat
Terminal Board
Destrat Relay
Remote Destrat Relay
Vent Permissive Relay
(Models 800 and 1200)
Limit Control
Terminal Boards
Fan
Motor
Heat Section Pressure Switch
Venter Motor Capacitor
Fan Motor Capacitor
High Limit Control
and Adjustable Destrat
Fan Control
Disconnect Switch
Transformer
Gas Valve
DSI Control (Circuit Board)
Fan Permissive Relay
Flame Sensor
29. Heat
Exchanger
Maintenance
30. Burner
Maintenance
Burner Removal
Instructions
(Refer to
FIGURE 23.)
CAUTION: Use of eye
protection is
recommended.
Burner Assembly
Ignitor
Heat Permissive Relay
(Models 800 and 1200)
2
Each section of this heater is equipped with a TCORE
Patent No. 6,889,686). Size 400 has one; Size 800 has two; and Size 1200 has three.
Remove any external dirt or dust accumulation. V isually check each heat exchanger
for cracks and holes. If a crack or hole is observed, replace the heat exchanger.
NOTE: Inspection of the lower portion of the heat exchanger is done with the burner
removed. See the Burner Service section below for information on inspecting the
lower portion of the heat exchanger.
Each section of this heater is equipped with a TCORE
6,889,686). Size 400 has one; Size 800 has two; and Size 1200 has three.
Inspect each burner/control compartment annually to determine if cleaning is neces-
sary . If there is an accumulation of dirt, dust, and/or lint, clean the compartment and
follow the instructions below to remove and clean the burner.
1. Outside the cabinet, shut the gas supply off at the manual valve ahead of the
union.
2. Turn off electric supply.
3. Disconnect the gas supply at the union outside of the cabinet.
4. Remove the access panel.
5. Disconnect the Gas Train and Move It Out of the Way - At the gas valve,
mark and disconnect the wires. Disconnect the union on one or both sides of the
gas line inside of the heater. Carefully remove the burner orifice and orifice
adapter locking nut. Slide the orifice adapter out through the bracket on the
burner.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 33
®
heat exchanger (U.S.
2
®
burner (U.S. Patent No.
30. Burner
Maintenance
(cont’d)
FIGURE 23 - Burner Removal
• Size 400 has 1 burner.
• Size 800 has 2 burners.
• Size 1200 has 3 burners.
Burner Removal Instructions (cont’d)
6. Remove Burner Assembly
a) Locate the three upper burner body supports. At each support, remove the
one screw that attaches it to the burner shield.
b) Holding the venturi tube, slide the entire burner assembly slightly upward to
disengage the burner from the supports on the bottom. Then rotate the open
end of the venturi tube outward toward the access door opening. Carefully
pull the burner assembly out of the cabinet.
Disconnect union(s). (On Size 400 or
the most downstream heat section in
a Size 800 or 1200, there will be one
union to disconnect. The first heat
section in Sizes 800 and 1200 and the
second heat section in Size 1200 will
have two unions to disconnect.)
Burner Shield
Burner Body Support -
Remove the three screws
attaching the burner
assembly to the burner
shield.
Inspect and Clean
the Burner
NOTE: If any of the burner
components are damaged or
deteriorated, replace the burner
assembly.
Inspect the Lower Portion
of the Heat Exchanger
(with burner assembly
removed)
Gas Valve - Mark and disconnect
the wires.
Remove orifice adapter locking nut.
Remove the burner orifice and
Burner
Assembly
With the burner assembly removed, shine a flashlight on the burner ribbons. Look for
carbon buildup, scale, dust, lint, and/or anything that might restrict flow through the
spaces between the burner ribbons. Holding the burner assembly so that any foreign
material will fall away from the burner, use a stif f bristle brush to loosen and remove
any foreign material(s). If the burner is excessively dirty, remove one of the burner
end caps. Remove the four screws that hold the end cap to the burner housing. Lightly
tap the end cap to remove it.
Clean all foreign material from the burner and venturi. After the burner is thoroughly
clean, replace the end cap making certain that it is tight against the burner housing.
At the burner flame entrance of each tube, shine a bright light into each heat exchanger section. With the light shining into the heat exchanger, observe the outside
for visible light. Repeat this procedure with each heat exchanger section. If any light
is observed, replace the heat exchanger.
To remove burner assembly,
lift and rotate outward.
slide out through the bracket.
Venturi Tube (part of the burner
assembly)
Re-Install the Burner
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 34
Instructions to Re-Install the Burner (Refer to FIGURE 23.)
1. Attach the Burner Assembly - Holding the venturi tube, slide the entire burner
assembly into position. Align the supports on the bottom with the slots in the
burner shield; sliding the supports into the slots. On the top, re-attach each
burner body support to the burner shield.
1/8 inch
(3.2mm)
2. Attach the Gas Train - Slide the gas train so that the orifice adapter is through
the bracket. Fasten the gas train to the bracket with the locking nut. Install the
gas orifice. Re-connect the wires to the gas valve. Re-connect the union(s)
inside of the control compartment.
3. Reconnect the gas supply at the union outside of the cabinet. Turn on the gas
supply and leak test the connections with leak detecting solution.
4. Close the access panel.
5. Turn on the electric. Check for proper operation.
31. Burner
Orifice(s)
32. Ignition
System
A burner orifice usually only needs to be replaced when installing a gas conversion
kit. If ordering replacement orifice(s) only, give BTUH content and specific gravity
of gas, as well as the model and serial number of the heater. When removing or
replacing a burner orifice, use two wrenches being careful not to damage the venturi
tube and/or the bracket.
DSI Integrated Control Module (circuit board) - See FIGURE 24. The module
monitors the operation of the heater including ignition. The only replaceable component is the 3 amp Type ATC or ATO fuse. If the fuse is blown, the problem is most
likely an external overload. Correct the problem and replace the fuse.
FIGURE 24 - DSI
Integrated Control
Module (Circuit
Board)
Only replaceable
part is a Type ATC
or ATO 3 amp fuse
(Color Code
Violet), P/N 201685
Do not attempt to disassemble the control module. However, each heating season check the
lead wires for insulation deterioration and good
connections. Size 400 has one control module; Size 800 has two control modules; and Size
1200 has three control modules.
Proper operation of the direct spark ignition
system requires a minimum flame signal of 1.0
microamps as measured by a microampmeter.
For further information and check out procedure on the direct spark ignition system, refer
to Paragraph 19 and the Troubleshooting Flow
Chart in Paragraph 43.
CAUTION: Due to high
voltage on the spark
wire and electrode, do
not touch when
energized. See Hazard
Levels, page 2.
Ignitor
Flame Sensor
33. Heat Section
Venter Motor
and Wheel
Ignitor - Refer to FIGURE 22 and locate the ignitor. Disconnect the wire; remove
the screw and the ignitor. Clean the ignitor assembly with an emery cloth.
Spark gap must be maintained to 1/8". See FIGURE 25.
FIGURE 25 - Ignitor
showing required
Spark Gap
measurement
IMPORTANT: When re-assembling, the brown ground wire must remain attached
to the ignitor.
CAUTION: Due to high voltage on the spark wire and electrode,
do not touch when energized. See Hazard Levels, page 2.
Flame Sensor - Refer to FIGURE 22 and locate the flame sensor. Disconnect the
wire; remove the screw and the flame sensor. Clean with an emery cloth.
Remove dirt and grease from the motor casing, the venter housing, and the venter
wheel. Venter motor bearings are permanently lubricated. Follow these instructions
for replacement of the venter motor and wheel assembly. Keep all hardware removed to be used in re-assembling and installing the replacement parts.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 35
33. Heat Section
Venter Motor
and Wheel
(cont’d)
FIGURE 26 - Venter Wheel
Position on Shaft - applies
to all heat section venter
assemblies
Replacement Instructions
1. Turn off the gas and disconnect the electric power.
2. Open the burner/control compartment access panel.
3. Disconnect the three venter motor wires at the DSI control, capacitor wires at
the capacitor, and ground screw (located on the control panel).
4. Holding the venter motor, remove the six screws that attach the venter motor
mounting plate to the venter housing. Remove the motor and wheel assembly
from the heater.
5. Re-assemble with the replacement venter motor and
wheel assembly. See FIGURE 26.
6. Follow the wiring diagram to connect the venter wires.
7. Replace the access panel. Restore power to the heater
and turn on the gas. Light, following the instructions on
the lighting instruction plate. Check for proper opera-
7/16 (11mm) inside
tion.
34. Main Venter Motor and Wheel (Models 800 and 1200 only)
The main venter motor and wheel is located on the top of the first heat section of a
Model LDAP 800 and 1200. The vent system attaches to the collar on the top of the
Venter
Motor
main venter housing.
Remove dirt and grease from the motor casing, the venter housing, and the venter
wheel. Venter motor bearings are permanently lubricated.
Follow the instructions in Paragraph 33 for replacement of the venter motor and wheel
assembly. Keep all hardware removed to be used in re-assembling and installing the
replacement parts. See FIGURE 27 for venter wheel and motor spacing.
Main Combustion
Air Pressure
Venter Housing
Switch
FIGURE 27- Venter Motor
and Wheel Spacing on
Main Venter (Size 800 and
1200)
35. Fan Motor(s),
Fan Blades,
and Guard(s)
FIGURE 28- Fan Blade
Position on the Shaft
Fan
Blade
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 36
3
(76mm)
Fan
Motor
Remove dirt and grease from each motor, fan guard, and blades. Use care when
cleaning the fan blades to prevent causing misalignment or imbalance. Check that the
hub of the fan blades is secure to the shaft.
Follow these instructions for replacement of the fan guard, fan motor and/or fan blades.
Repeat the procedure for each heater section.
1. If the heater is installed, turn off the gas and disconnect the electric power.
2. Open the access door and disconnect the fan motor wires, capacitor wires at the
capacitor, and ground screw.
3. Remove the assembled parts (the fan guard, the motor and the fan blade).
4. Disassemble and replace whatever parts are needed and reassemble using
whatever part(s) are being replaced and the original parts.
Be sure the fan blade is in the proper position on the shaft; refer to the illustration
in FIGURE 28.
Position the assembly on the heater. Attach the fan guard.
Rotate the fan blade to check for adequate clearance. If adjustment is required,
loosen the mounting screws, re-position the fan guard, and tighten the screws.
Wheel
1-1/4 (32mm)
Main Venter
Motor
Screw
Flat Washer
Hex Nut
Exhauster Motor Base Assy
Motor Wire
and Cable Assy
Rotate the fan blade and re-check for adequate clearance. Repeat this procedure
until the assembly is positioned properly .
5. Reconnect the fan motor wires according to the wiring diagram and close the
access panel.
6. When finished with all sections, restore power to the heater and turn on the gas.
Light, following the instructions on the lighting instruction plate. Check for proper
operation.
36. Operating
Gas V alve(s)
W ARNING: The
operating valve is the
prime safety shutoff. All
gas supply lines must be
free of dirt or scale
before connecting to the
heater to ensure
positive closure. See
Hazard Levels, page 2.
NOTE: Operational pressure
settings and instructions for
checking pressure settings are
in Paragraph 12.
Carefully remove external dirt accumulation and check the wiring connections. Size
400 has one valve; Size 800 has two valves; Size 1200 has three valves.
The combination gas valve must be checked annually to ensure that the valve is
shutting off gas flow completely .
Instructions:
1) Locate the 1/8” NPT pressure tap on the combination valve.
FIGURE 29 - Pressure Tap for Checking Gas Flow Shutoff
Single-Stage Valve
1/8” Outlet
Pressure Tap
2) With the manual valve turned off to prevent flow to the gas valve, connect a manometer to the 1/8” outlet pressure tap in the valve. NOTE: A manometer (fluidfilled gauge) is recommended.
3) Turn the manual valve to the ON position and the heater OFF. Use your finger to
fully block the main burner orifice for several seconds. Observe the manometer
with the orifice blocked, and if any pressure is indicated, the gas valve is leaking. A
leaking gas valve must be replaced before the heater is placed back in
operation.
Two -Stage Valve (optional
on Model LDAP 400 only)
1/8” Outlet
Pressure Tap
37. Combustion
Air Pressure
Switch(es)
Main
Combustion
Air Pressure
Switch Models 800
and 1200
Heat Section
Pressure
Switch
See FIGURE 22, page 34, for location of the heat section
pressure switch. If it is determined that a pressure switch
needs replacing, use only the factory-authorized replacement
part that is designed for the model and size of heater being
serviced.
Size 400 has one pressure switch; Size 800 has two heat section pressure switches and a main combustion air pressure
switch; and Size 1200 has three heat section pressure switches
and a main combustion air pressure switch. The main combustion air pressure switch is located on the top of the first
heat section (see the illustration in Paragraph 34, page 36).
NOTE: A heater operating above 6000 ft elevation requires
high altitude heat section pressure switch(es). See Paragraph
5.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 37
38. Limit
Control
If it is determined that the automatic reset limit control needs replacing, use only a factory-authorized replacement part that is designed for the size of heater.
For approximate limit location, see FIGURE 22, page 34.
39. High Limit
Control
40. T ransformer
41. Adjustable
Fan Control
42. Vent System
A manual reset high limit control is located at the top of each heat
section. Do not reset high limit control without correcting the problem. If it is determined that the limit control needs replacing, use
only a factory-authorized replacement part that is designed for the
size of heater.
See FIGURE 22, page 34, for location. Use a voltmeter to verify
that there are 24 volts output from the transformer. If the transformer is not functioning, it must be replaced. Use a replacement
transformer identical to the factory-installed model.
See FIGURE 22, page 34, for location. Check the wiring connec-
tions and the adjustment knob.
If it is determined that the destratification fan control needs replacing, use only a factory-authorized replacement part that is designed for the heater.
Check the complete vent system at least once a year. Inspection should include all
joints, seams, and the vent terminal cap. Clean openings. Replace any defective parts.
43. T roubleshooting
Check the Lights on
the DSI Integrated
Control Module
(Circuit Board)
IMPORTANT: When using a
multimeter to troubleshoot the
24 volt circuit, place the meter’s
test leads into the 5 or 9 pin
connectors located on the
ignition control. Do not remove
connectors or terminals from
the electrical components.
Doing so can result in misinterpreted readings due to the
ignition control board’s fault
mode monitoring circuits.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 38
The integrated circuit board monitors the operation of the heater and includes two
LED signal lights that indicate normal operation and various abnormal conditions. If
the heater fails to operate properly , check this signal to determine the cause and/or to
eliminate certain causes. See operating sequence in Paragraph 19.
Do not attempt to repair the DSI integrated control module; the only field replaceable
component is the fuse.
Steady On Nor mal Operation - No call for heat. Stea dy On Flame is sensed.
Fast Fl ash Norm al Operati on - Call for heat.Sl ow F lash Weak flame ( c ur r ent bel ow
1 FlashSystem L oc kout (failed to detec t or
2 FlashMain combustion air pr e ssure
3 FlashLimit or hi gh limit sw itch open.
4 FlashMain combustion air pr e ssure
Ste a dy Off Blown fuse; N o power; or Def ective
Control Status - GREEN L ED Cod esFlame Status - YELLOW LED Codes
1.0 microamps ±50%)
Fast Flash
sustain f lame)
switch or he a t sec tion pressure
switch does not cl ose with 30
seconds of vent e r being e ne rgized.
switch or he a t sec tion pressure
switch i s closed before venter is
energized.
board
U ndesired f lame (valve
open and no cal l for heat).
DSI Integrated
p
p
g
p
g
p
p
g
g
prop
p
)
b)
b)
)
)
) Sp
) Sp
)
g)
g)
prop
)
p
p
p
g
)
b)
)
y
p
p
b)
b)
)
b
)
Control Module
(Circuit Board) Trial
Troubleshooting
Flowchart
Trial for
Ignition
Call for Heat
Is there a
spark across gap at
ignitor?
YES
YESNO
Does gas
ignite?
NO
Check wiring and/or
24VAC transformer
output.
Is there
spark voltage at
control?
NO
Is there
24V P1-2 to power
control?
YES
YESNO
Check high
voltage wire
continuity.
Replace control
module.
Is there
minimum flame current
at the control
module?
NO
Check connections to
flame sensor or
moisture in bulkhead
connector.
YES
Replace control
Check gas pressure and
supply voltage. If either
are low, correct and
module.
YES
repeat startup.
Clean
flame
sensor.
flame current at the flame
YES
Is there minimum
sensor?
NO
Is the flame sensor
corroded?
YES
NO
Is the sensor
located in flame
correctly?
YES
Replace flame
sesnsor.
NO
Repositon flame
sensor.
General T roubleshooting
PROBLEMPROBABLE CAUS EREMEDY
Ven ter mo tor will
not start
Burner will1.
ht2.
not li
ower to unit.
No
1.
No 24 volt
2.
Inte
3.
No
4.
Inte
5.
Defective venter motor.
6.
Manual valve not o
Ai r in t he
Gas pressure too hi gh or too low.
3.
No S
4.
Loose wir e connections.a) Be certain all wire connections are solid.
a
ow er to int egrate d circuit board.
rated circuit board fuse blown.
ow e r to venter motor.
rated circui t board defective.
en.
as line.
ark:
Transformer failure.
Incorrect spark gap.c
c
ark cable shorted to ground.d) Replace worn or grounded spark cable.
d
ark electrode shorted to ground.e) Replace if ceramic spark electrode is cracked or grounded.
e
Burner not grounded.f) Mak e c e rtain integrated circuit board is grounded to ignitor.
f
C ircuit board not grounded.
h.) Unit not proper ly grounded.h.) Make c ertain unit is properly fie ld grounded to earth ground and
Integrate d circui t board fuse blown.i) Corr ect cause. Replace fuse (type ATC or ATO, 32V DC , 3 A).
i
j.) F a ulty intergr a te d circuit board.j) If 24 volt is available to the integrat ed c ircuit board and all other causes
L oc kout device interru
5.
Combustion air
6.
not c losin
Fault
7.
Main valve not o
8.
.a
combustion a ir proving switch.
ting control circui t by above causes.5. Reset l oc kout by interrupting control at the thermostat or main power.
roving switch
erating.
a) Def ective valve.a) If 24 vol t i s measured at the valve connections and val ve remains
Loose wir e connections
Integrated circuit board does not power main valve.
9.
Loose wir e connections.a) Check and tighten all wiring connections.
a
b) F lame sensor gr ounded.
c) Incorrect gas pressure.c) Supply pressure should be 5" - 14" w.c. for natural gas or 11" - 14"
d
Cr acked ceramic at sensor.d) Repla ce sensor.
Turn on power; check supply fuses or main circuit break e r.
1.
Turn up thermostat; check control transfor mer output.
2.
Corr ect cause. Replace fus e (type ATC or ATO, 32VD C , 3 A).
3.
Tighten connecti ons at ci rcuit board and/or motor ter minals.
4.
Replace intergra t ed ci rcuit bo a rd.
5.
Re
6.
Open manual valve.
1.
Bleed gas line (initial startup only).
2.
Suppl y pressure should be 5" - 14" w. c . for nat ural gas or 11" - 1 4"
3.
w.c. for
4.
Be s ure 24 volts is available.
Maintain spark gap at 1/8".
Make certain integrate d circui t board is grounded to furnace chassis.
erly phased (L1 to hot lead L2 to neutral).
have been eliminated, re
6.
Make sure unit is properly vente d.
R e move obstructions from vent.
Replace faulty tubing to pressure switch.
c
Repla ce combustion air proving switch.
7.
8.
closed, re
Check and tighten all wiring connections.
9.
) Be certain flame sensor lead is not grounded or insulati on or c e ramic is
not cracked. Repl ace as required.
w.c. for propane gas.
YESNO
Is gas flowing?
Is the ignitor
position correct in the
gas flow?
Replace gas valve.
NO
Reposition spark
ignitor.
Check wiring and
connections to gas
valve.
lace venter m otor. S ee Paragraph 32.
ane gas.
lace board.
lace valve.
Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 39
YES
YES
24VAC at the gas
Is there 24VAC from
gas valve output on control
module to chassis?
Replace ignition
control module.
Is there
valve?
NO
NO
General Troubleshooting (cont’d)
g
g
)
b)
)
y
p
p
p
y
prop
p
g
p
g
p
g
g
PROBLEM (cont'd)PROBABLE CAUSE (cont'd)REMEDY (cont'd)
Burner cy cle on a nd off
No heat (Heater
Operating)
Fa n or venter motor w ill
not run
F an or venter motor t u rn s
on and off while b urner is
operating
F an or venter motor cu t s
out on overload
1 . G as pressure too high or too low.1. Supply pressure should be 5" - 14" w. c . for na t ural ga s or 1 1" - 1 4"
w. c . for propane gas.
2 . Burner not
3 . Circuit bo ard not
4 . Faulty integr a t ed circ uit board4. If 24 volt is ava ila ble to the integrate d c ircuit board and all other
5 . C ombustion air pr oving swi tc h(es) not
closing.
6. Fault
7 . Fl a me sensor grounded.7 . Be certa in flam e sensor l e ad i s not grounded or insulation or cera mic
8. Cracked ceramic at sensor.8. Re
9. Incorrect
1. Incorrect valve outlet
2. C
cling on limit control.2. Check air throughput.
3. Im
1. Circuit o
2. Defective inte
3. Defective motor. 3. Re
1 . Motor overload device cycling on a nd off. 1. Check motor load against motor rating plate. Repl a c e motor if need e d.
1 . Low or hi
2. Defective motor.2. R e
3. Poor airflow. 3. Clean motor, fan, fan
4. Defective bearin
rounded2 . Make cert ain int egra t ed c ircuit board i s groun ded t o ignitor.
rounded.3 . Make cert ain int egra t ed c ircuit board i s grounded to furnace chassis.
causes have been el im inated, replace board.
5.
a
Make sure unit is properly vented.
Remove obstructions from vent.
Replace faulty tubing to pressure switch.
c
combustion air proving switch.6. Repl ace combustion a ir proving switch.
i s not cracked. R e place as re quired.
lace s ensor.
olarity.9. R everse l ine volt l ea ds to i ntegra t ed c ircuit board.
re ssure or orif ice.1. Check valve outlet pressure. See Rating plate for manifold pressure.
er thermostat location or adjustment. 3. See thermostat manufacturer' s i nstructions.
en.1. C heck wi ri ng and conne ctions.
rated circuit board.2 . Repl ace board.
lace motor.
h voltage supply.1. Correct electric supply.
lace motor.
or lubrication. 4. L ub r icate bea rings (motor permitting) or replace motor.
uar d, fil te r, and coils.
FOR SERVICE OR REPAIR, FOLLOW THESE STEPS IN ORDER:
FIRST:Contact the Installer
Name __________________________________________________________
Address_________________________________________________________