INSTALLATION INSTRUCTIONS
Elastimold
655VS / K655VS Deadbreak Vault Stretcher
CONTENTS: Vault Stretcher, 2--Cable Adapters, 2--Compression Lugs, 2--Insulating Plugs, Lubricant, Stud Prepack,
The 655VS and K655VS connectors are designed to: 1) provide fully shielded, fully submersible deadfront cable connections
to high voltage apparatus and 2) provide a means to splice and tap 600--ampere systems. The 655VS and K655VS are rates
on 15kV and 25kV class systems respectively.
Installation Instructions, Crimp chart.
DANGER
All apparatus must be de--energized during installation
or removal of part(s).
Do not touch or move energized products in the work
area.
These instructions do not attempt to provide for every
possible contingency.
Failure to follow these instructions will result in
damage to the product and serious or fatal injury.
This product should be installed only by competent
personnel trained in good safety practices involving
high voltage electrical equipment. These instructions
arenot intended as a substitute for adequate training or
experience in such safety practices.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ABB OFFICE.
All apparatus must be installed and operated in
accordance with individual user, local and national
work rules and electrical standards.
For loadbreak products follow operating instructions.
All deadbreak connectors must be de--energized before
operating. All 200A deadbreak connectors must be
mechanically secured with bails when connected.
If this product is supplied with a protective shipping
cover(s), remove this shipping cover(s) and replace
with the appropriate HV insulated cap(s) or
connector(s) before submerging or energizing the
circuit.
Inspect parts for damage, rating and compatibility with
mating parts.
Excess distortion of the assembled product may result
in its failure.
Limited Warranty:
1. ABB Installation Products Inc. warrants that its products will be free from defects in materials or workmanship for a period
of two (2) years, except for tools which are warranted separately (see warranty accompanying those products).
Fisher Piercet products and Elastimoldt Reclosers are warranted for three years; and Joslynt VBT and VBU capacitor
switches arewarranted for four years or 40,000 operations whichever occurs first. Upon prompt notification of a warranted
defect, ABB Installation Products Inc. will, at its option, repair, replace or refund the defective product.
2. In no event shall ABB Installation Products Inc. be liable for any consequential, indirect, incidental or special damages,
whether under contract, warranty, tort, negligence, strict liability or otherwise. ABB Installation Products Inc. will not be
liable for providing temporary power, removal, working access, installation, transportation to or from any repair facility,
or reimbursement for labor costs, or for any other expenses arising out of the removal or reinstallation of its products.
Liability for breach of warranty is limited to the cost of repair, replacement or refund of the warranted product only.
3. Misuse, misapplication or modification of ABB Installation Products Inc. products immediately voids all warranties.
THE WARRANTIES AND REMEDIES CONTAINED HEREIN ARE EXCLUSIVE AND ARE IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED.
IMPORTANT
1. Check contents of package to ensure they are complete
and undamaged.
2. Check all components to ensure proper fit with cable
and/or mating products.
3. Read entire installation instructions before starting.
4. Have all required tools at hand and maintain cleanliness
throughout the procedure.
IS--0356
IS--655VS
Revision: B
Date: June 1, 2021
Page 1 of 6

IS--0356
IS--655VS
Revision: B
Date: June 1, 2021
Page 2 of 6
STEP1
For concentric neutral cable, overlap both cables and cut to 14” (355mm) from center line of joint and bend back the
concentric neutral wires.
14”
(355mm)
Joint Centerline
Concentric Neutral Wires
(Where Applicable)
14”
(355mm)
STEP2
Clean the outer surface of the cable a distance of 24” (610mm) or up to the bent back neutrals.
STEP3 CABLE PREPARATION
Follow the STEPS A, B or C applicable to the cable being prepared.
A. 20MA or 21MA GROUNDING DEVICE OR 600ECS JACKET CABLE SEAL
Refer to the Installation Instructions supplied with those products for removal of cable outer jacket, shield connection and
grounding.
B. UNISHIELD* AND LEAD SHEATH CABLE
Refer to the Installation Instructions supplied with the 10TL cable shield adapter for cable preparation.
*Unishield is a trademark of General Cable Technologies Corporation.

C. JACKETED AND NON-- JACKETED CABLE
Remove the outer jacket (where applicable) and prepare cable as shown.
IS--0356
IS--655VS
Revision: B
Date: June 1, 2021
Page 3 of 6
1. NON---JACKETED CONCENTRIC
NEUTRAL WIRES
Semi--- con Shield
Bind
Tape Marker
Cable Insulation
9---3/4”(248mm)
10---3/4”(273mm)
12---3/4”(324mm)
3. JACKETED FLAT METALLIC TAPE SHIELD
Flat Metallic
Tape Shield
Outer
Jacket
Tape Marker
Semi--- con Shield
Cable Insulation
9---3/4”(248mm)
10---3/4”(273mm)
Flat Metallic Tape Shield
and Vinyl Tape Location
2. JACKETED SHIELD WIRES
Shield Wires
Outer
Jacket
Tape Marker
Semi--- con Shield
Cable Insulation
9---3/4”(248mm)
10---3/4“(273mm)
12---3/4”(324mm)
4. JACKETED FABRIC TAPE SHIELD
Fabric Tape
Shield
Outer
Jacket
Tape Marker
Tape Retainer
Cable Insulation
9---3/4”(248mm)
10---3/4”(273mm)
12---3/4”(324mm)
12---3/4”(324mm)
5. JACKETED LONGITUDINALLY
CORRUGATED SHIELD
Tape Marker
Longitudinally
Corrugated Shield
Outer
Jacket
Flush
Semi--- con Shield
Cable Insulation
9---3/4”(248mm)
10---3/4”(273mm)
12---3/4”(324mm)

IS--0356
IS--655VS
Revision: B
Date: June 1, 2021
Page 4 of 6
STEP4 CABLE ADAPTER
Bevel the end of the cable insulation at a 45_ angle, approximately 1/4” (6mm) back. Thoroughly clean, then lubricate cable
insulation always working toward semi--- con shield. Install cable adapter, small end first, until it is flush with the edge of the
tape marker.
Edge
Bevel
Cable Adapter
Tape Marker
Cable Insulation
Clean and
Lubricate
STEP5 CONDUCTOR
Remove any protruding cable insulation by cutting it even
with the end of the cable adapter. Do not cut or nick the
cable adapter or the conductor. The length of exposed
conductor should be between 4--- 3/8” -- 4 -- 1 1/16”
(111mm--- 119mm). Otherwise redo assembly.
Cable Adapter
4---3/8”--4--11/16”
(111mm---119mm)
Even with Cable Adapter
Bare
Conductor
STEP6
Copper Conductor: Fully insert conductor into compression Lug.
Aluminum Conductor: Wire brush conductor and immediately fully insert conductor into compression lug.
Measure the “CheckDimension” before crimping. Dimensionshould be less than 6--- 1/2”. Otherwise redo assembly. Before
making the first crimp, align the flat portions of the compression connector by using a 5/8” bolt as a temporary locater while
crimping. Hold the compression connector in the proper position and make the first crimp connection 3--- 1/2” from the open
end of the compression fitting at the mark indicated on the connector.
Check Dimension Before Crimping Typ.
Start Crimping Here
5/8” Bolt and Nut
3 1/2”
Typ
Start Crimping Here
STEP7
Rotate each successive crimp 180_ to prevent bowing.Carefully wipe excess inhibitor from theoutside of the connector and
from the cable insulation. Check to ensure that the connector end is6 ---1/2” to 7--- 1/4” . Remove sharp flash, if any, from the
crimp before inserting into the vault stretcher body.
6---1/2” to 7---1/4”
(165 to 184mm)
6---1/2” to 7---1/4”
(165 to 184mm)

IS--0356
IS--655VS
Revision: B
Date: June 1, 2021
Page 5 of 6
STEP8
1. Lubricate the inside of the vault stretcher body and the outside of the cable adapter. Using a rotating motion, slip the
body onto the cable adapter. Make sure the compression lug is aligned to seat with the inside mating portion of the
vault stretcher. The compression lug should be pushed into the vault stretcher until it cannot advance further. The
base of the adapter should still be aligned with the marking tape.
2. To insert the opposite cable into the other side of the vault stretcher, the vault stretcher and compression lug must be
pushed sideways until the compression lug enters the open end of the vault stretcher body.
3. Slowly push both units toward their final alignment, making sure the lubricated adapter is sliding into proper position
in the vault stretcher. Check the location of the compression lug through the viewing hole of the vault stretcher. When
compression lug is fully seated, make sure that both cable adapters are still flush with tape markers. If not, reposition
cable adapters. Remove tape markers.
Lubricate
Flush
Marking Tape
(Remove)
Flush
Marking Tape
(Remove)
STEP9
NOTE: A special stud (650VSA) 1/2” longer than the standard stud must be used with the vault stretcher.
1. DO NOT connect or disconnect mating products while energized. DO NOT energize while disconnected. Remove
protective caps from the vault stretcher and the mating part. Hand tighten stud, supplied with vault stretcher, into one
mating part. Clean and lubricate the vault stretcher and the mating part with lubricant supplied.(Keep surfaces
of vault stretcher and mating part clean).
2. Clean and lubricate the mating part for the opposite end of the vault stretcher. Insert the mating part into the elbow.
Engage the threads and hand tighten. Torque mating part according to the instructions supplied with the mating part.
All mating parts must be operated in accordance with their operating instructions.
2---5/8” (67mm)
Special Conversion Stud
Loadbreak
Reducing
Tap Plug
Connecting
Clean
&
Lubricate
Plug
Clean
&
Lubricate
Deadbreak
Insulating
Plug
Reducing
Tap Plug
Reducing
Tap Well
Clean
&
Lubricate
Insulating Plug or
Apparatus Bushing
Clean & Lubricate

IS--0356
IS--655VS
Revision: B
Date: June 1, 2021
Page 6 of 6
STEP 10
If an insulating plug is used as a mating part, clean and
lubricate inner surface of the voltage detection cap and
place on elbow. Pushdown hard until cap snaps into place.
Clean & Lubricate
Clean
STEP 11 GROUNDING CONCENTRIC NEUTRAL CABLE
Insert one end of a piece of wire with ampacity at least equivalent to No. 14 AWG copper through grounding eye and twist to
make a small loop. Repeat for other grounding eye. DO NOT damage the eyes. Connect wires to ground using suitable
connectors.