Thomas & Betts K655BE Installation Manual

Page 1
IS---0242
IS --- BE
Revision: 0
Page1of4
Installation Instructions: 15,25,35kV
600/900 AMP Deadbreak Bushing Extension
CONTENTS: Bushing Extension, Lubricant (DO NOT SUBSTITUTE), Installation Instruction, Stud Prepack
Thebushingextension with voltageand current ratingsasindicatedon theproduct whenusedwith the appropriatemating components, can provide: 1) a 600/900 ampere bushing extension, 2) a 200 ampere tap or 3) an insulated shielded and water---tight cap for a 600/900 ampere bushing.
DANGER
Allapparatusmust be de--energizedduring installation or removal of part(s).
All apparatus must be installed and operated in accordance with individual user, local and national work rules and electrical standards.
Do not touch or move energized products in the work area.
These instructionsdo not attempt to provide for every possible contingency.
Failure to follow these instructions will result in damage to the product and serious or fatal injury.
This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. These instructions arenot intendedasasubstitutefor adequatetrainingor experience in such safety practices.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATI BI LITY, CALL THE NEAREST ELASTIMOLDROFFICE.
For loadbreak products follow operating instructions. Alldeadbreakconnectors must bede--energizedbefore operating. All 200A deadbreak connectors must be mechanically secured with bails when connected.
If this product is supplied with a protective shipping cover(s), remove this shipping cover(s) and replace with the appropriate HV insulated cap(s) or connector(s) before submerging or energizing the circuit.
Inspect parts for damage, rating and compatibility with mating parts.
Excess distortion of the assembled product may result in its failure.
Limited Warranty:
1. T&B warrants that its products will be free from defects in materials or workmanship for a period of two (2) years, except for tools which are warranted separately (see warranty accompanying those products). Fisher PierceRproducts and ElastimoldRReclosers are warranted for three years; and Joslynt VBT and VBU capacitor switches are warranted for four years or 40,000 operations whichever occurs first. Upon prompt notification of a warranted defect, T&B will, at its option, repair or replace the defective product.
2. Inno event shall T&B be liableforany consequential,indirectorspecialdamages, nor will T&B beliablefor transportation, labor,or other charges arising out of the removal or reinstallation of its products. Liability for breach of warranty is limited to the cost of repair or replacement of the warranted product only.
3. Misuse, misapplication or modification of T&B products immediately voids all warranties.
THE WARRANTIES AND REMEDIES CONTAINED HEREIN ARE EXCLUSIVE AND ARE IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED.
IMPORTANT
1. Check contents ofpackagetoensurethey are complete
and undamaged.
2. Check all components to ensure proper fit with cable
and/or mating products.
IS---0242 IS --- BE
Date: August 2018 Printed in U.S.A.
860 Ridge Lake Blvd, Memphis, Tennessee 38120
(800) 888--0211 Fax: (800) 888--0690
3. Read entire installation instructions before starting.
4. Have all required tools at handand maintain cleanliness throughout the procedure.
Page 2
IS---0242
Revision: 0 Page2of4
STEP1
Remove protective caps from the bushing extension. Clean the entire bushing extension interface as noted and lubricate, with lubricant supplied or ELASTIMOLD approved lubricant. Keep mating surfaces of bushing and extension clean.
25kV BE
35kV BE
Clean and
Lubricate
STEP2
Clean the entire interface of a connecting plug, deadend plug, reducing tap plug, reducing tap well or elbow tap plug as noted and lubricate with the lubricant supplied or ELASTIMOLDapproved lubricant. Finger tighten the doubleended stud suppliedwiththe bushingextensioninto oneofthesematingproducts. Insertthis productintothebushingextension.While pushing the assembly onto the bushing, engage the threads and handtighten.
Connecting
Plug
Insulating
Plug
Reducing
Tap
Plug
Reducing
Tap
Well
Elbow
Tap
Plug
Link Op
Retainer
Sleeve/Pin
Contact
Clean
&
Lubricate
Clean
&
Lubricate
Clean
&
Lubricate
Page 3
IS---0242
Revision: 0
Page3of4
STEP3 Tighten assembly as follows:
FOR INSULATING PLUG, (K)650BIP, (K)675BIP, 750BIP, 775BIP
Use torque wrench and tighten to 50 to 60 foot---pounds of torque.
FOR EPOXY CONNECTING PLUG, (K)650CP, (K)675CP. REDUCING TAP PLUG, (K)650RTP, (K)675RTP or TAP WELL, (K)650RTW, (K)675RTW, Use torque wrench with an ELASTIMOLD 600SW spanner wrench and tighten to 40 to 48 foot---
pounds of torque.
FOR RETAINER SLEEVE/PIN CONTACT
Use600---ATand torqueto50to60 foot---poundsusinga suitabletoolattached tothehex. (Referto Linkinstructionsheetfor remaining assembly).
FOR ELBOW TAP PLUG, 750ETP
Use torque wrench with 600ATM and tighten exerting 50---60 foot---pounds of torque.
FOR RUBBER CONNECTING PLUG, 750CP, 775CP
Proceed as follows:
Assemble the components as shown. Handtighten the rubber connecting plug.
Rubber Connector Plug
750CP, 775CP
To provide a means of torquing the connecting plug, temporarily install and hand tighten a compression lug and insulating plug as shown.
Connector Plug
Compression
Lug
Insulating
Plug
Use a torque wrench on the insulating plug nut and tighten, to 50 to 60 foot---pounds of torque.
Torque
Wrench
To preventthe connectingplug fromlooseningwhen removingthe insulating plug, holdthe compressionlug and break the torque at the insulating plug. Remove compression lug and insulating plug.
hold compression lug here
Page 4
IS---0242
Revision: 0 Page4of4
STEP4
Clean the remaining interface of the connectingplug, reducing tap plug, reducingtap well or the elbow tap plug and lubri­cate with the lubricant supplied or ELASTIMOLD approved lubricant. Assemble the appropriate mating component accordingto the instructionssupplied with the product. For the insulating plug, assemble the protectivecap provided, as per its instructions.
STEP5
Connecta short length of #14 AWGcopper wire or equivalent tothegroundingeye of the bushing extension. Make a small loop and twist tightly taking care not to damage the eye. Connect this wire to ground using suitable connector.
Mating components assembled in STEP 4 which require a ground should also be connected to ground in this manner.
Mating
Product
To Ground
THOMAS & BETTS CORP. PROPRIETARY AND CONFIDENTIAL
BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINED IN IT, AS WELL AS THE SUBJECT MA TTERAND ALL PROPRIETARYAND NOVEL FEATURES DISCLOSED, ARE OWNED BY THOMAS & BETTS CORPORATION(”THE COMPANY” AND A MEMBEROF THE ABB GROUP) AND THATDEVICES EMBODYING SUCH FEATURESOR INFORMA TI ONDERIVED FROMTHESE DRAWINGSWILL NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN CONSENT OF THE COMPANY. THESE DRAWINGS ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSEDTO OTHERS WITHOUTTHE PRIOR EXPRESS WRITTEN CONSENT OF THE COMPANY. ALL DRAWINGS AND INFORMATI ON ARE TO BE RETURNED TO UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT. COPYRIGHT THOMAS & BETTS CORP . ALL RIGHTS RESERVED. ALL OTHER TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE OWNERS.