IS---600/900A J2,J3,J4
IS---0207
October 2009
Page 1 of 7
Installation Instructions
15/25/35kV, 600/900 AMPERE
Two---, Three--- and Four---Point Deadbreak Junctions
CONTENTS: The contents always include: 1 ---Deadbreak Junction, and 1---Installation Instruction plus Mounting Hardware
for the specific installations listed below.
A. Universal Mount: 1---Base Bracket, 1 ---Base Plate, 4 --- Universal Brackets, 1 ---Mounting Hardware Prepack.
B. 45_ Fixed Mount: 1---Base Bracket, 1 ---Base Plate, 2---45_ Mounting Brackets, 1 --- Mounting Hardware Prepack.
C. Flat Mount w/Base Bracket: 1---Base Bracket, 1 ---Base Plate.
D. Flat mount w/o Base Bracket: 1 ---Shield Plate, Hold Down Bracket(s) (as required).
SECTION A
Universal Mount 45_ Fixed Mount
SECTION B
Flat Mount with Base Bracket Flat Mount without Base Bracket
SECTION C
The two---, three--- and four---point deadbreak junctions have voltage and current ratings as indicated on the junctions and
are designed to interface with ELASTIMOLD deadbreak connectors for the purpose of sectionalizing, looping, tapping or for
apparatus change out. The deadbreak junctions are designed for mounting on any flat surface.
SECTION D
DANGER
All apparatus must be de--energized during installation
or removal of part(s). For loadbreak products follow
operating instructions. All deadbreak connectors must
be de--energized before operating. All 200A deadbreak
connectors must be mechanically secured with bails
when connected.
All apparatus must be installed and operated in
accordance with individual user, local, and national
work rules. These instructions do not attempt to
provide for every possible contingency.
Do not touch or move energized products.
Excess distortion of the assembled product may result
in its failure.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.
Inspect parts for damage, rating and compatibility with
mating parts.
This product should be installed only by competent
personnel trained in good safety practices involving
high voltage electrical equipment. These instructions
are not intended as a substitute for adequate training or
experience in such safety practices.
Failure to follow these instructions will result in
damage to the product and serious or fatal injury.
If this product is supplied with a protective shipping
cover(s), remove this shipping cover(s) and replace
with the appropriate HV insulated cap(s) or
connector(s) before submerging or energizing the
circuit.
IS---0207
IS---600/900A J2,J3,J4
October 2009
Printed in U.S.A.
8155 T&B Boulevard, Memphis, Tennessee 38125
(800) 888--0211 Fax: (800) 888-- 0690

IS---0207
October 2009
Page 2 of 7
Section A --- Universal Mount
STEP 1
Determine the desired location of the junction assembly. Using the base plate as a template, place it on the surface that
the junction is to be mounted and mark slot locations.
Base Plate
Mark Slot Location
Mark Slot Location
Mark Slot Location
Mark Slot Location
STEP 2
Attach two (2) universal brackets to flat surface using suitable fasteners and tighten securely to ensure no movement
during operation.
Universal Bracket
TOP VIEW
Universal Bracket
STEP 3
Attach the remaining two (2) universal brackets to the two (2) universal brackets mounted on the surface at desired angle
using the hardware supplied. Tighten securely.
Universal Bracket
Mounted to Surface
SIDE VIEW
Rotated 90_
Universal Bracket
Mounted at Desired Angle
3/8” Hex Head
Cap Screw
TOP VIEW
Universal Bracket
Mounted at Desired Angle
Universal Bracket
Mounted to Surface
Ext. Tooth
Lock Washer
3/8” Hex Nut

IS---0207
October 2009
Page 3 of 7
STEP 4
Assemble deadbreak junction to base bracket assembly and base plate using two (2) 1/2”” hex head cap screws,
two (2) 1/2” split lock washers, and two (2) 1/2” hex nuts attached to the center mounting holes on the bracket assembly.
Tighten securely.
Deadbreak Junction
1/2” Hex Head Cap Screw
Base Bracket Assembly
1/2” Split Lock Washer
1/2” Hex Nut
Base Plate
STEP 5
Attach the deadbreak junction assembly to the universal brackets using the hardware supplied. Tighten securely.
Be sure parking stand is in upright position.
1/2” Split Lock Washer
1/2” Hex Nut
1/2” Hex Head Cap Screw
STEP 6
The base bracket assembly and junction’s black conductive jacket must be grounded. A grounding lug is provided on the
base bracket for this purpose. It accommodates wire sizes of No. 2 solid to 1/0 stranded.
STEP 7
Operating Instructions
Go to page 7 of this installation instruction for operating instructions.

IS---0207
October 2009
Page 4 of 7
Section B --- 45
o
Fixed Mount
STEP 1
Determine the desired location of the junction assembly. Using the base plate as a template, place it on the surface that the
junction assembly is to be mounted and mark slot locations.
Base Plate
Mark Slot Location
Mark Slot Location
Mark Slot Location
Mark Slot Location
STEP 2
Attach the two (2) 45_ brackets to the surface using suitable fasteners and tighten securely to ensure no movement
during operation.
Side View
Rotated 90_
45_ Bracket45_ Bracket
Top
View
Fastener
Fastener
45_ Bracket
Fastener
STEP 3
Assemble deadbreak junction to base bracket assemblyand base plate using two (2)1/2” hex head cap screws, two (2) 1/2” split
lock washers and two (2) 1/2” hex nuts attached to the center mounting holes on the bracket assembly. Tighten securely.
Deadbreak Junction
1/2” Hex Head Cap Screw
Base Bracket Assembly
1/2” Split Lock Washer
1/2” Hex Nut
Base Plate

IS---0207
October 2009
Page 5 of 7
STEP 4
Attach the junction assembly to the 45_ brackets using the hardware supplied. Tighten securely. Be sure parking stand
is in upright position.
1/2” Hex Head Cap Screw
1/2” Split Lock Washer
1/2” Hex Nut
Mounting Surface
STEP 5
The base bracket assembly and junction’s black conductive jacket must be grounded. A grounding lug is provided on the
base bracket for this purpose. It accommodates wire sizes of No. 2 solid to 1/0 stranded.
STEP 6
Operating Instructions
Go to page 7 of this installation instruction for operation instructions.
Section C --- Flat Mount w/Base Bracket
STEP 1
Determine the desired location of the junction assembly. Using the base plate as a template, place the base plate on the
surface that the junction is to be mounted and mark all slot locations.
Base Plate
Mark Slot Location

IS---0207
October 2009
Page 6 of 7
STEP 2
Assemble deadbreak junction to base bracket assembly and base plate with suitable fasteners, attach to flat surface and
tighten all fasteners securely to insure no movement during operation. Make sure parking stand is in an upright position.
Junction
Base Bracket Assembly
Base Plate
UP
Parking Stand
Slots for 1/2” (13mm) Bolt
(Bolts Supplied by User).
Grounding Lug
STEP 3
The base bracket assembly and junction’s black conductive jacket must be grounded. A grounding lug is provided on the
base bracket for this purpose. It accommodates wire sizes of No. 2 solid to 1/0 stranded.
STEP 4
Operating Instructions
Go to page 7 of this installation instruction for operation instructions.

IS---0207
October 2009
Page 7 of 7
Section D --- Flat Mount w/o Base Bracket
STEP 1
Determine the desired location of the junction assembly. Using the hold down bracket(s) assembled on the junction as
a template, place the assembly on the surface that junction is to be mounted and mark all hole locations.
4.0”
Junction
Mark at Hole Locations
0.5”
5.0”
Hold Down Bracket
STEP 2
Assemble deadbreak junction, shield plate and hold down bracket(s) with suitable fasteners, attach to flat surface and
tighten all fasteners securely to ensure no movement during operation.
IMPORTANT: Conductive jacket of junction and shield plate must be grounded through contact with grounding
conductive mounting surface. If mounting surface is not grounded attach grounding lug to bracket bolt.
Hold Down Bracket
Shield Plate
Junction
Holes for 1/2” (13mm) bolt
(Bolts Suppled by User)
Operating Instructions
1. Remove all protective caps and clean the operating interfaces. Lubricate each interface with an ELASTIMOLD
approved lubricants. DO NOT SUBSTITUTE. Other lubricants may be harmful to this product or its mating product(s).
2. If all operating interfaces are not utilized, insulated caps must be installed on the unused bushing(s) before energization.
3. Do not use the protective shipping caps for this function as they are not insulated and are only intended to keep the
operating interfaces clean during handling and installation.