Thomas & Betts GP2250-2 Installation Manual

Page 1
INSTRUCTION SHEET
Ground Grid Connector
INSTRUCTIONS:
NOTE: Install these connectors on ground rods after the rods have
been driven to their nal depth.
1. Clean cable of all visible dirt with rough cloth or brush and provide a bright copper nish by wire brushing or similar process. Optional: use knurling tool 240-31565-94 on smooth ground rods.
3. Crimp using hydraulic tool 13100A, TBM14M, TBM14CR-LI, TBM15, TBM15CR-LI, or TBM15I and die as indicated on part. IF USING THE TBM15, TBM15CR-LI, or TBM15I TOOL, A DIE ADAPTER NO. 15500-TB IS REQUIRED.
GP250500-4 GP250500-2
GP2250-4 GP2250-2
Figure
2 1 2 1
250-500 MCM 250-500 MCM
2-250 MCM 2-250 MCM
HCat. Nos. Cable Range
4-7/32"
3-5/8"
4-7/32"
3-5/8"
Dies
15G121R (2) 15G121R 15G86R (1)
15G86R (1) T&B
(2)
(Crimped)
WARNING
DO NOT CRIMP ON HOT
ENERGIZED WIRES. DISCONNECT
POWER BEFORE INSTALLATION.
Y750/Y35/Y39 Y46Y45
U1011 (3) U1011 (3)
U997 (1) U997 (1)
Burndy Tools
S1011 (2) S1011 (2)
U997 (1) U997 (1)
(Crimped)
P1011 (2) P1011 (2)
U997 (1) U997 (1)
1-3/4”
T&B
2”
2X 1/2-13 UNC
3-1/4”
5-25/32”
CABLE RANGE
H
3/8”-16 UNC
Figure 1 Figure 2
WARRANTY
Limited Warranty Applies. Refer to: www.tnb.com/ecpwarranty for full warranty terms.
© 2014 Thomas & Betts. All Rigths Reserved.
TA02008 D Page 1 of 1
Thomas & Betts Corporation
Memphis, Tennessee
www.tnb.com