Thomas & Betts furse ESP 120 D1, furse ESP 415 D1 Series, furse ESP 208 D1 Series, furse ESP 277 D1, furse ESP 240 D1 Installation Instructions Manual

...
Installation instructions
for mains wire-in protectors
ESP D1, D1R, D1/LCD and D1R/LCD variants
Installation instructions for mains wire-in protectors
Introduction
This document explains how to install Furse Electronic Systems Protectors for mains power supplies:
Single phase ESP 120 D1 | Single phase ESP 240 D1 | Single phase ESP 277 D1 | Three phase ESP 208 D1, D1R, D1/LCD & D1R/LCD | Three phase ESP 415 D1, D1R, D1/LCD & D1R/LCD | Three phase ESP 480 D1, D1R, D1/LCD & D1R/LCD
These instructions are prefaced by a summary of the Key points of installation. Each key point is explained in detail in the section entitled Installation.
WARNING: Incorrect installation will impair the
Contents
effectiveness of the ESP units
Key points of installation 3 Before installation 4 Installation 6 Installation check (LED units) 24 Neutral-earth warning light (LED units) 25 Status indication (LED units) 26 Status indication (LCD units) 26 LCD display settings 30 Remote indication 34 Maintenance 35 Application notes 36 Remote display cut-out template 39
Key points of installation
1
Install protectors very close to the power supply to be protected, either within the distribution panel or directly alongside it.
2
Mount units within a panel or WBX enclosure.
3
ESP D1 units can be installed in parallel or, for power supplies 125A, in-line (series) with the power supply.
4
Connect to phase(s), neutral and earth.
NOTE: Units must have a neutral connection.
5
Units installed at power distribution boards can be installed either:
on the load side of the incoming isolator, or
on the closest available outgoing way to the incoming supply
6
Provide a means of isolation for the ESP unit.
7
The connecting leads to phase/live terminals should be suitably fused (125A maximum) ensuring full discrimination with the immediate upstream supply fuse.
Page |3Page |2
Installation instructions for mains wire-in protectors
8
Connecting leads should be 10 mm2multi stranded cable for parallel/shunt installation. For series installation,
refer to section 6.
9
For parallel/shunt installation, keep the connecting leads as short as possible and ideally less than 25 cm (10 inches) in length. For series installation, keep earth lead as short as possible.
This may be better achieved with the equivalent D1R or D1R/LCD unit with remote display mounting flexibility.
10
Bind the connecting leads tightly over their entire length.
Before installation
1
Check that the voltage between neutral and earth does not exceed 10 volts.
If this voltage does exceed 10 volts, the installation is unsafe.
Find and rectify the cause of this fault before proceeding. (For delta supplies with no neutral, see page 13).
2
Make sure that the supply voltage is suitable for the unit.
Supply Rated Unit Voltage Voltage Range (V
)(V
ESP 120 D1
Phase to
RMS
RMS
Neutral/Earth 110/120/127 90-150
ESP 208 D1 Series
Phase to Phase 190/208/220 156-260
ESP 240 D1
Phase to Neutral/Earth 220/230/240 200-280
ESP 415 D1 Series
Phase to Phase 380/400/415 346-484
ESP 277 D1
Phase to Neutral/Earth 240/254/277 232-350
ESP 480 D1 Series
Phase to Phase 415/440/480 402-600
)
Page |5Page |4
Installation
1
Location
Protectors need to be installed very close to the power supply to be protected. Usually the protector will be installed at a power distribution panel either inside it (Figure 1) or right next to it (Figure 2).
ESP D1 protectors have been designed to fit onto a standard 35mm DIN rail (see 3 - DIN Installation) or within a Furse WBX D enclosure.
2
Enclose the ESP unit
The ESP unit has exposed terminals. For electrical safety, the unit must be installed within a panel or enclosure. For standard single and three phase units, where possible, install the unit within the power distribution panel behind a suitable viewing window.
Figure 1 ­ESP 415 D1/LCD installed on a DIN rail within a power distribution panel.
Installation instructions for mains wire-in protectors
Figure 2 - ESP 415 D1/LCD installed next to a power distribution panel in a suitable WBX D enclosure.
Alternatively, for three phase units, a remote display option is available. Units can be installed within the power distribution panel with the remote display mounted on the front of the panel (see 4 - remote display).
When mounting the units in existing metal panels or enclosures, ensure that the enclosure is securely bonded to the earth bar to which the ESP unit will be connected.
If it is not possible to install the unit within the distribution panel it should be mounted in a separate enclosure, see Figure 2, as close as possible to the distribution panel (see 12 & 13 - Length of connecting leads). Gland the enclosure onto the power distribution panel. Suitable enclosures are available from Furse.
Page |7Page |6
Installation instructions for mains wire-in protectors
3
DIN Installation
ESP D1 Series protectors have been designed with an innovative DIN foot for connection to standard 35mm DIN rails. This DIN foot, comprising spring loaded steel DIN mounts, enables rapid positioning of D1 protectors onto the rail.
Figure 3 - Reverse of 3 phase protector showing innovative spring loaded DIN foot.
The spring loaded steel DIN mounts pull down and out to lock into place ready for siting the protector. Position the D1 protector at the preferred location on the DIN rail and press the protector back to release the springs. The protector locks into place.
Figure 4 - Reverse of 3 phase protector showing spring loaded DIN foot locked onto DIN rail.
Page |8
4
Remote display
Three phase ESP D1R and D1R/LCD units include a remote mounting display to ensure optimum positioning of the unit along with quick and easy status checking.
The remote display should be mounted in a clearly visible position, typically on the front of the distribution panel (see Figure 5).
For remote display connection, ensure the cable is of sufficient length, and is unimpeded within the cabinet. Allow a minimum of 60 mm behind the front panel for the interconnection cable.
ESP D1R and D1R/LCD units are supplied with 1 m interconnection cable as standard, with a 4 m cable available as an option (contact Furse).
Figure 5 ­ESP 415 D1R/LCD remote display installed on the front of a power distribution panel.
Page |9
Installation instructions for mains wire-in protectors
S
PROTECTION
AC
E
Care should be taken against static discharge when handling the remote display unit - avoid contact with the exposed connector.
5
Parallel connection
ESP D1 protectors can be connected in parallel with the supply to be protected, or connected in-line (series), for power supplies ≤125A (see 6).
For parallel connection, the connecting leads do not carry the load current of the supply, only the current associated with suppressing the transient overvoltage.
I
T1
imp
I
20kA
n
T2 C
I
max
U
oc
125 AgL
4kA
B
40kA
DT3
6kV
Figure 6
- Parallel connection for single phase supplies.
LL1N1N
PATENT APPLIED
ESP 240D1
FOR
STATUS INDICATION
L N
GREEN
U
280V 47-63H
zac
c
GREEN & RED REDUCED
EN/IEC 61643
RED NO PROTECTION
WARNING: If lit / flashing disconnect unit & check Neutral to Earth voltage
STATUS
11
14
12
FULL PROTECTION
PROTECTION (replace unit)
!
Figures 6 & 7 show connection diagrams for single phase and three phase star power supplies.
Connecting leads to the unit need to be kept short in order to minimise additive inductive voltages.
Figure 7 - Parallel connection for three phase star (4 wire and earth) supplies.
6
Series connection
LL' L2 L2' L3 L3' NN'
PATENT APPLIED
FOR
EN/IEC 61643
STATUS
11
14
12
Enhanced
URGE
Mains
Protector
TIV
The twin terminal design of ESP D1 units enables installation in-line (series) with the power supply (for power supplies 125A). The supply cables should be suitably rated for the specific load current. The terminals of the ESP unit can receive up to 35 mm2stranded cable.
Any type of protector installed in parallel (shunt) with the supply will have additive inductive voltage on the connecting leads. This resultant voltage let-through the protector is hence seen by the equipment to be protected (see 5 and 12). Series installation eliminates the additive voltage associated with connecting leads on parallel installations.
PE
Page |11Page |10
Installation instructions for mains wire-in protectors
R
SURG
P
N
A
E
Ensure the power supply does not exceed 125A for series installations. The connecting leads to phase/live terminals should be suitably fused (125A maximum) ensuring full discrimination with the immediate upstream supply fuse.
Figure 8 shows the connection diagram for three phase star power supplies.
Figure 8 - Series connection for three phase star (4 wire and earth) supplies.
7
Connection to phase, neutral and earth
LL'L2 L2' L3 L3' NN'
PATENT
APPLIED
FOR
ESP 415D1
ROTECTIO
EN/IEC 61643
CTIV
STATUS
11
14
12
Connections are made to each supply conductor including earth. Terminals marked L, N, (single phase units) or L1, L2, L3, N, (three phase units) must be connected to phase/live, neutral and earth respectively.
Under no circumstances must the ESP unit be installed without connection to its neutral.
Where no neutral is present (eg delta supplies) the neutral (N) terminal on the ESP unit must be connected to earth in addition to the earth ( ) terminal. This will result in a greatly increased earth leakage current.
On some delta supplies the voltage between phase and earth/neutral may exceed the rating of the ESP unit.
Consequently, the supply’s phase to earth voltage must be checked before installing the ESP unit.
We recommend that you consult Furse ESP before installing ESP units on delta supplies.
Enhanced
E
Mains
Protector
PE
8
Connection point
(a) Protecting supplies feeding equipment in the building
The ESP unit is typically connected to the power supply at a power distribution board/panel, either:
(i) on the load side of the incoming isolator (Figure 9).
(ii) on the closest available outgoing way to the incoming
supply (ie the incoming isolator).
Page |13Page |12
Loading...
+ 14 hidden pages