Thomas & Betts FPT449, FPT450 Installation Manual

Page 1
INSTALLATION INSTRUCTIONS
FLUSH-FLOOR POKE-THROUGH
FITTING SINGLE DUPLEX POWER
Cat. No. FPT449 & FPT450
WARNING
ELECTRICAL HAZARD!
BE SURE POWER IS OFF!
IMPORTANT NOTES:
1. This ush POKE-THROUGH system is designed to maintain the hourly rating of concrete oors having ratings of 1 to 4 hours, when installed in accordance with these installation instructions.
2. To maintain re resistance classication rating either of the following must be installed:
a) A complete Thomas & Betts service tting,
including the service tting base and service tting cover.
or
b) An abandonment kit, Catalog No. FPT415.
INSTALLATION INSTRUCTIONS
3. See product category "outlet boxes and ttings" classication for re resistance standards. This can be found in the current Underwriters Laboratories, Inc." Fire Resistance Directory," which includes a listing for the re resistance classication of the Thomas & Betts Modular Poke-Through System.
4. All installations of UL listed Poke-Through service ttings have the following restrictions:
"Minimum of 2 ft. on center and not more than
one device per 65 sq. ft. of oor area in each span."
5. This through-oor tting will mount several types of Thomas & Betts UL listed service ttings which will accommodate different combinations of power, telephone and data. Determine location and orientation of mounting screw holes for the specic service tting chosen prior to installation. CONSULT THE ENCLOSED ADDENDUM FOR MORE DETAILS.
CARPET
LARGE OPENING THIS SIDE FOR TELE/DATA CABLES
STEP 1
WHITE AREA INDICATES CARPET REMOVED FROM CONCRETE SURFACE TO INSTALL POKE-THROUGH
STEEL 27 C.I. JUNCTION BOX
SMALL OPENING THIS SIDE FOR POWER CABLES
PLASTIC POWER TUBE
LOCATING BRACKE
T FLUSH TO CONCRETE FLOOR
CONCRETE FLOOR
NOTE: It may be necessary to move or remove carpeting to allow proper installation of through-oor tting.
a) Core or bore a 3" diameter hole
through oor.
IMPORTANT: See Note 4 above.
b) Insert through-oor tting into hole
and orient plastic power tube into desired position. Make certain location bracket is ush with concrete oor.
NOTE: Careful consideration must be given to nal pedestal location and orientation prior to engagement of retainer clips to ensure desired nal pedestal installation.
IMPORTANT: Not for use on bare concrete or oor coverings less than 1/4” thick.
TA01584 C
Page 1 of 4
Page 2
POWER WIRE ATTACHED TO DEVICE AND MOUNTING PLATE
PUTTY BOTH SIDES
a) Ensure that all electrical power is
disconnected and that wires are de-energized. Feed power wires into power side of Poke-Through. Leave max. 4" of wire above oor.
b) Fill inside of Poke-Through device
with putty supplied. Press rmly into place around all wires. Use all putty material supplied.
STEP 2
REPLACE 1/4” CARPET
MOUNTING PLATE
a) Replace 1/4” thick carpet..
b) Cut 5-1/4” hole in carpet over
Poke-Through.
c) Feed tele/data and power wire(s) into
mounting plate as shown.
d) Attach mounting plate to
Poke-Through with screws furnished.
5-1/4” CUT HOLE IN CARPET
STEP 3
TA01584 C Page 2 of 4
Page 3
a) To ensure scrub-water exclusion, apply a continuous bead of
silicone sealant around mounting plate underneath cover.
b) Attach cover and gasket to mounting plate with three at head
screws furnished.
COVER
GASKET
MOUNTING PLATE
SEALANT
STEP 4
SEE LAST PAGE FOR REPLACEMENT INSTRUCTIONS
WARRANTY: Thomas & Betts sells this product with the understanding that the user will perform all necessary tests to determine the suitability of this product for the user's intended application. Thomas & Betts warrants that this product will be free from defects in materials and workmanship for a period of two (2) years following the date of purchase. Upon prompt notication of any warranted defect, Thomas & Betts will, at its option, repair or replace the defective product or refund the purchase price. Proof of purchase is required. Misuse or unauthorized modication of the product voids all warranties.
Limitations and Exclusions: THE ABOVE WARRANTY IS THE SOLE WARRANTY CONCERNING THIS PRODUCT, AND IS
IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED. LIABILITY FOR BREACH OF THE ABOVE WARRANTY IS LIMITED TO COST OF REPAIR OR REPLACEMENT OF THE PRODUCT, AND UNDER NO CIRCUMSTANCES WILL THOMAS & BETTS BE LIABLE FOR ANY INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
© 2011 Thomas & Betts. All Rights Reserved
Thomas & Betts Corporation
Memphis, Tennessee
www.tnb.com
TA01584 C
Page 3 of 4
Page 4
REPLACEMENT INSTRUCTIONS
FOR OTHER T&B FIRE-RATED PEDESTALS
WARNING
ELECTRICAL HAZARD!
BE SURE POWER IS OFF!
a) Remove receptacle and cover plate assembly by
removing screws on top, see Figure 1R
b) Disconnect power and ground cables from
receptacle.
REMOVE AND DISCARD
POKE-THROUGH MOUNTING SCREWS
LOCATING BRACKET
POWER DIVIDER
a) Loosen Poke-Through mounting screws
3-4 full turns.
b) Remove locating bracket by rotating
clock-wise and lifting out. NOTE: It may be necessary to move or remove carpeting during retrot installation.
c) Tighten mounting screws.
STEP 2R
REINSTALL SCREWS
a) Reinstall screws into Poke-Through device
as shown.
b) If carpeting was removed in Step 2R,
replace carpet now.
c) Install oor pedestal according to
instructions supplied with pedestal.
GROOVES
STEP 1R
TA01584 C Page 4 of 4
STEP 3R
Loading...