When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2.CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by
disconnecting the unit connector.
3.CAUTION – The integral, high temperature Ni-Cad battery is replaceable. To replace the battery, disconnect the unit connector and remove both switched and unswitched A.C. power to the fixture. Remove the
lid screw and open the lid to expose the battery. Unplug the battery connector and replace with part
number 44900-006 (14.4V Ni-Cad battery only). Recycle the used battery. The EPA certified RBRC
Battery Recycling Seal indicates voluntary participation in an industry program to collect and recycle
these batteries at the end of their useful life, when taken out of service in the United States or Canada.
The RBRC program provides a convenient alternative to placing used Ni-Cad batteries into the trash or the
municipal waste stream, which may be illegal in your area. Please call 1-800-822-8837 for information on
Ni-Cad battery recycling and disposal bans/restrictions in your area. Involvement in this program is part of
a commitment to preserving the environment and conserving natural resources.
4.DO NOT USE OUTDOORS. The FPS-HL is for use with grounded, UL Listed, indoor fixtures except in
heated air outlets or hazardous locations.
5.The FPS-HL requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the
unused A.C. lead.
6.Do not mount near gas or electric heaters.
7.The FPS-HL should be mounted in locations and at heights where it will not readily be subjected to
tampering by unauthorized personnel.
8.The FPS-HL mounts on top of the fixture or adjacent to the fixture on an optional T-bar mounting bracket.
9.The FPS-HL will cold strike and operate
circline, T8 through T12 fluorescent lamps, including energy saving and long 4 pin compact lamps for 90
minutes.
10.The FPS-HL operates lamps as follows:
One 2′–8′, or two 2′–4′ lamps for 90 minutes at reduced light output.
One 2′–4′ lamp for 90 minutes at full light output.
11.The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
12.Do not use this equipment for other than intended use.
13.Install in accordance with the National Electrical Code and local regulations.
14.Installation and servicing should be performed by qualified personnel.
15.Lighting fixture manufacturers, electricians and end users need to ensure product system compatibility
before final installation.
one
2′–8′ or
two
2′–4′ instant start, rapid start, U shape or
®
SAVE THESE INSTRUCTIONS
INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the FPS-HL unit connector is disconnected.
1.LAMPS OPERATED
The FPS-HL can be used with most 2′–8′ lamps. Refer to the chart below for the type of lamp(s) operated and the number of
lamps to be operated in emergency mode. Contact Customer Service with questions about specific lamps.
NOITPOEPYTPMAL
YCNEGREME
NOITAREPO
SDAELROTCELESPMAL*
GNIRIW
SMARGAID
thW/nrBnworBteloiV
12′ 4- ′enilcriC,21-T/8-TpmaLenOXX8,7,6,5,4,3,2,1
28′XAIB,21-TpmaLenOXX7,6,5,4,2,1
32′ 4- ′enilcriC,21-T/8-TpmaLowTXX01,9
*The lamp programming wires each have a 3 position shorting P-nut connector. Select the proper wire combination from
the chart above for the desired lamp(s) used. Cut and strip one of the selected wires (3/8″) and plug it into the P-nut of the
second wire.
2.MOUNTING THE FPS-HL
Remove the ballast channel cover. Mount the FPS-HL on the fixture top in a position that does not interfere with the
existing A.C. ballast or any other hardware. Extend the flex conduit to a convenient location on top of the fixture and punch
a 7/8″ hole. Feed the wires and flex connector down through the hole in the fixture and secure in place with the flex connector nut. An optional T-bar mounting kit is available to mount the FPS-HL above the ceiling tile adjacent to the emergency
fixture. To order the optional T-bar mounting kit (part number TBMK-160) contact Customer Service.
When battery packs are remote mounted, the remote distance can not exceed 1/2 of the distance from ballast to lamp
specified by the A.C. ballast manufacturer. For example, if the A.C. ballast manufacturer recommends no more than 25
remote distance, then the battery pack should not exceed 121/2′. Under no circumstances should the battery pack exceed
a distance of 50′ from the lamp.
3.WIRING
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance with the
National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.
′
4.INSTALLING THE CHARGE INDICATOR
Recessed Troffer Fixture
hole (1/2″ knockout). Insert the 7/8″ bushing into the hole. Push the plastic tube through the bushing. Disconnect the leads
from the LED housing and route the leads down the plastic tube. Reconnect the leads to the housing, observing the proper
polarity (Red lead to positive (+) red tab). Push the entire assembly back into the tube until the lens collar rests against the
plastic tube. The plastic tube should be adjusted so that the Charge Indicator is within ¼″ of the fixture lens. The ChargeIndicator must be visible after installation. Refer to
Strip Fixture
tion. Allow for proper clearance inside the fixture and drill or punch a 1/2″ hole. Disconnect the leads from the LED housing.
Push the LED housing into the 1/2″ hole until it is firmly locked in place. Reconnect the leads, observing the proper polarity
(Red lead to positive (+) red tab). Refer to
– Select a convenient location on the side of the fixture so the Charge Indicator can be seen after installa-
Illustration 1Recessed Troffer Fixture
BALLAST CHANNEL
COVER
7/8" BUSHING
CHARGE INDICATOR LAMP
– Select a convenient location with proper clearance in the ballast cover and drill or punch a 7/8″
Illustration 1
Illustration 2
.
.
Illustration 2Strip Fixture
FPS-HL
FLEX CONDUIT
PLASTIC TUBE
FIXTURE LENS
Page 2
FPS-HL
OBSERVE PROPER POLARITY
FLEX CONDUIT
FIXTURE
WHITE/RED
CHARGE
INDICATOR
LIGHT
LEAD
+ RED
+ RED
LEAD
5.INSTALLING THE TEST SWITCH
The test switch should be mounted on the ballast channel cover of a recessed troffer, or on the side of a strip fixture,
preferably adjacent to the charge indicator. Drill or punch a 1/2″ mounting hole.
6.WIRING THE A.C. INPUT
A. The FPS-HL and A.C. ballast
B. The FPS-HL requires an
cap the unused lead.
C. When the FPS-HL is used with a switched fixture, the A.C. input to the FPS-HL must be connected ahead of the fixture
switch. Refer to
Illustration 3
Illustration 3Switched FixtureUnswitched Fixture
must
be on the same branch circuit.
unswitched
A.C. power source of either 120 or 277 volts. Select the proper voltage lead and
for switched and unswitched fixture wiring diagrams.
WHITE
BLACK
(277V) ORG
➀
(120V) BLK
(COMM) WHT
Select proper voltage lead. Cap unused lead.
A.C. BALLAST
FPS-HLFPS-HL
HOT A.C. LINE
COMMON
WALL SWITCH
TEST SWITCH
➀
Select proper voltage lead. Cap unused lead.
➀
WHITE
BLACK
(277V) ORG
(120V) BLK
(COMM) WHT
A.C. BALLAST
HOT A.C. LINE
COMMON
TEST SWITCH
➀
7.LABELS
Attach the appropriate labels adjacent to the Test Switch and Charge Indicator. Annotate Re-lamping label for lamp
type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone
attempting to service the fixture.
8.COMPLETING INSTALLATION
When the installation is complete, switch the A.C. power on and join the FPS-HL unit connector.
OPERATION
Normal Mode – A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The FPS-HL is in the
standby charging mode. The Charge Indicator will be lit providing a visual indication that the battery is being charged.
Emergency Mode – The A.C. power fails. The FPS-HL senses the A.C. power failure and automatically switches to the
gency Mode
stored, the FPS-HL switches the system back to the
. One or two lamps are illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. power is re-
Normal Mode
and resumes battery charging. See page 1 of the Instruction
Manual.
Emer-
TESTING & MAINTENANCE
Initial Testing – Allow the unit to charge approximately 1 hour, then conduct a short discharge test. Allow a 24 hour charge
before conducting a one hour test.
The FPS-HL is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety Code,
outlines the following schedule:
Monthly – Insure that the Charge Indicator light is illuminated. Conduct a 30 second discharge test by depressing the Test
Switch. One lamp or two lamps should operate at full or reduced output, depending on your configuration.
Annually – Insure that the Charge Indicator light is illuminated. Conduct a full 1
as intended for the duration of the test.
“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Consult Customer Service for current warranty information.
Page 3
1
/2 hour discharge test. The unit should operate
TYPICAL WIRING DIAGRAMS
For wiring diagrams of ballasts not shown, consult our Customer Service.
1. ONE LAMP RAPID START BALLAST
SWITCHED OR
UNSWITCHED
BLACK
WHITE
RED
RED
A.C.
Ballast
*LAMP
*AC / EMERGENCY
BLUE
BLUE
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
➁
UNIT
EMERGENCY
FPS-HL
BALLAST
CHARGE
INDICATOR
VIOLET
BROWN
➂
ORG (277V)
BLK (120V)
WHITE
BRN/WHT
LINE
➀
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
➀
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
➁
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADS—REFER
➂
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
2. TWO LAMP RAPID START BALLAST
SWITCHED OR
UNSWITCHED
BLACK
WHITEBLUE
A.C.
YELLOW
Ballast
YELLOW
LAMP
*LAMP
*AC / EMERGENCY
BLUE
RED
RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
➁
UNIT
EMERGENCY
FPS-HL
BALLAST
VIOLET
CHARGE
INDICATOR
BROWN
➂
ORG (277V)
BLK (120V)
WHITE
BRN/WHT
LINE
➀
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
➀
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
➁
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADS—REFER
➂
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
3. THREE LAMP RAPID START BALLAST
SWITCHED OR
UNSWITCHED
BLACK
WHITE
BLUE
BLUE
YELLOW
YELLOW
A.C.
Ballast
LAMP
*LAMP
LAMP
*AC / EMERGENCY
BLUE/WHT
BLUE/WHT
RED
RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
➁
UNIT
EMERGENCY
FPS-HL
BALLAST
CHARGE
INDICATOR
VIOLET
BROWN
➂
ORG (277V)
BLK (120V)
WHITE
BRN/WHT
LINE
➀
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
➀
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
➁
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTION LEADS—REFER
➂
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
5. TWO LAMP INSTANT START BALLAST
SWITCHED OR
UNSWITCHED
LINE
➀
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
➀
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
➁
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
➂
LAMP SELECTOR LEADS—REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
➃
WIRES TOGETHER
BLACK
WHITE
A.C.
Ballast
LAMP
*LAMP
*AC / EMERGENCY
BLUE
RED
➃
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
UNIT
➁
EMERGENCY
FPS-HL
BALLAST
CHARGE
INDICATOR
VIOLET
BROWN
➂
ORG (277V)
BLK (120V)
WHITE
BRN/WHT
6. TWO LAMP INSTANT START BALLAST
SWITCHED OR
UNSWITCHED
BLACK
WHITE
RED
A.C.
Ballast
LAMP
*LAMP
*AC / EMERGENCY
BLUE
BLUE
➃
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
➁
CONNECTOR
COMMON
EMERGENCY
FPS-HL
UNIT
INDICATOR
BALLAST
CHARGE
VIOLET
BROWN
➂
ORG (277V)
BLK (120V)
WHITE
BRN/WHT
LINE
➀
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
➀
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
➁
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
➂
LAMP SELECTOR LEADS—REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
➃
WIRES TOGETHER
7. THREE LAMP INSTANT START BALLAST
SWITCHED OR
UNSWITCHED
BLACK
WHITE
RED
A.C.
Ballast
LAMP
LAMP
*LAMP
*AC / EMERGENCY
BLUE
BLUE
BLUE
➃
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
➁
UNIT
EMERGENCY
FPS-HL
BALLAST
CHARGE
INDICATOR
VIOLET
BROWN
➂
ORG (277V)
BLK (120V)
WHITE
BRN/WHT
LINE
➀
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
➀
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
➁
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
➂
LAMP SELECTOR LEADS—REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
➃
WIRES TOGETHER
4. ONE LAMP INSTANT START BALLAST
SWITCHED OR
UNSWITCHED
BLACK
WHITE
RED
A.C.
Ballast
*LAMP
*AC / EMERGENCY
BLUEBLUE
➃
BLUE/WHT
RED/WHT
RED
YELLOW
➁
CONNECTOR
COMMON
EMERGENCY
FPS-HL
BALLAST
UNIT
INDICATOR
CHARGE
VIOLET
BROWN
➂
ORG (277V)
BLK (120V)
WHITE
BRN/WHT
LINE
➀
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
➀
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
➁
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
➂
LAMP SELECTOR LEADS—REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
➃
WIRES TOGETHER
9. TWO LAMP RAPID START BALLAST
W/2 LAMP EMERGENCY OPERATION
SWITCHED OR
UNSWITCHED
BLACK
WHITE
YELLOW
YELLOW
Rev. 021903
68160-006
A.C.
Ballast
*LAMP
*LAMP
*AC / EMERGENCY
BLUE
BLUE
RED
RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
➁
CONNECTOR
COMMON
EMERGENCY
FPS-HL
UNIT
INDICATOR
BALLAST
CHARGE
VIOLET
BROWN
➂
ORG (277V)
BLK (120V)
WHITE
BRN/WHT
LINE
➀
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
➀
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
➁
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER
➂
TO INSTALLATION INSTRUCTIONS,
LAMPS OPERATION SECTION FOR
VARIOUS OPTIONS
8. FOUR LAMP INSTANT START BALLAST
BLACK
WHITE
YELLOW
YELLOW
A.C.
Ballast
LAMP
LAMP
LAMP
*LAMP
*AC / EMERGENCY
BLUE
BLUE
RED
RED
➃
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
➁
CONNECTOR
COMMON
EMERGENCY
FPS-HL
BALLAST
UNIT
INDICATOR
CHARGE
VIOLET
BROWN
➂
ORG (277V)
➀
BLK (120V)
WHITE
SELECT PROPER VOLTAGE
➀
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
➁
BRN/WHT
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
➂
LAMP SELECTOR LEADS—REFER
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
➃
WIRES TOGETHER
10. TWO LAMP INSTANT START BALLAST
W/2 LAMP EMERGENCY OPERATION
Page 4
BLACK
WHITE
RED
A.C.
Ballast
*LAMP
*LAMP
*AC / EMERGENCY
BLUE
BLUE
BLUE
BLUE/WHT
➃
RED/WHT
YELLOW
CONNECTOR
COMMON
RED
➁
UNIT
EMERGENCY
BALLAST
FPS-HL
CHARGE
INDICATOR
ORG (277V)
BLK (120V)
WHITE
SELECT PROPER VOLTAGE
➀
LEAD. CAP UNUSED LEAD.
VIOLET
BROWN
BRN/WHT
DO NOT MATE CONNECTOR UNTIL
➁
➂
INSTALLATION IS COMPLETE AND
AC POWER IS SUPPLIED.
LAMP SELECTOR LEADS—REFER
➂
TO INSTALLATION INSTRUCTIONS,
LAMP OPERATION SECTION FOR
VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
➃
WIRES TOGETHER
SWITCHED OR
UNSWITCHED
LINE
UNSWITCHED
COMMON
SWITCHED OR
UNSWITCHED
LINE
➀
UNSWITCHED
COMMON
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.