Thomas & Betts FPS-HL User Manual

FPS-HL
EMERGENCY
LIGHTING EQUIPMENT
INSTRUCTION MANUAL
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C. power is supplied to the unit.
2. CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electri­cal shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by disconnecting the unit connector.
4. DO NOT USE OUTDOORS. The FPS-HL is for use with grounded, UL Listed, indoor fixtures except in heated air outlets or hazardous locations.
5. The FPS-HL requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C. lead.
6. Do not mount near gas or electric heaters.
7. The FPS-HL should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
8. The FPS-HL mounts on top of the fixture or adjacent to the fixture on an optional T-bar mounting bracket.
9. The FPS-HL will cold strike and operate
circline, T8 through T12 fluorescent lamps, including energy saving and long 4 pin compact lamps for 90 minutes.
10. The FPS-HL operates lamps as follows:
One 2–8, or two 2–4 lamps for 90 minutes at reduced light output. One 2–4lamp for 90 minutes at full light output.
11. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
12. Do not use this equipment for other than intended use.
13. Install in accordance with the National Electrical Code and local regulations.
14. Installation and servicing should be performed by qualified personnel.
15. Lighting fixture manufacturers, electricians and end users need to ensure product system compatibility before final installation.
one
2′–8 or
two
2′–4 instant start, rapid start, U shape or
®
SAVE THESE INSTRUCTIONS
INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the FPS-HL unit connector is disconnected.
1. LAMPS OPERATED
The FPS-HL can be used with most 2–8lamps. Refer to the chart below for the type of lamp(s) operated and the number of lamps to be operated in emergency mode. Contact Customer Service with questions about specific lamps.
NOITPOEPYTPMAL
YCNEGREME
NOITAREPO
SDAELROTCELESPMAL*
GNIRIW
SMARGAID
thW/nrBnworBteloiV
12′ 4- enilcriC,21-T/8-TpmaLenOXX 8,7,6,5,4,3,2,1
28 XAIB,21-TpmaLenOX X7,6,5,4,2,1
32′ 4- enilcriC,21-T/8-TpmaLowTXX01,9
*The lamp programming wires each have a 3 position shorting P-nut connector. Select the proper wire combination from the chart above for the desired lamp(s) used. Cut and strip one of the selected wires (3/8) and plug it into the P-nut of the second wire.
2. MOUNTING THE FPS-HL
Remove the ballast channel cover. Mount the FPS-HL on the fixture top in a position that does not interfere with the existing A.C. ballast or any other hardware. Extend the flex conduit to a convenient location on top of the fixture and punch a 7/8 hole. Feed the wires and flex connector down through the hole in the fixture and secure in place with the flex connec­tor nut. An optional T-bar mounting kit is available to mount the FPS-HL above the ceiling tile adjacent to the emergency fixture. To order the optional T-bar mounting kit (part number TBMK-160) contact Customer Service.
When battery packs are remote mounted, the remote distance can not exceed 1/2 of the distance from ballast to lamp specified by the A.C. ballast manufacturer. For example, if the A.C. ballast manufacturer recommends no more than 25 remote distance, then the battery pack should not exceed 121/2′. Under no circumstances should the battery pack exceed a distance of 50 from the lamp.
3. WIRING
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.
4. INSTALLING THE CHARGE INDICATOR
Recessed Troffer Fixture
hole (1/2 knockout). Insert the 7/8 bushing into the hole. Push the plastic tube through the bushing. Disconnect the leads from the LED housing and route the leads down the plastic tube. Reconnect the leads to the housing, observing the proper polarity (Red lead to positive (+) red tab). Push the entire assembly back into the tube until the lens collar rests against the plastic tube. The plastic tube should be adjusted so that the Charge Indicator is within ¼ of the fixture lens. The Charge Indicator must be visible after installation. Refer to
Strip Fixture
tion. Allow for proper clearance inside the fixture and drill or punch a 1/2hole. Disconnect the leads from the LED housing. Push the LED housing into the 1/2 hole until it is firmly locked in place. Reconnect the leads, observing the proper polarity (Red lead to positive (+) red tab). Refer to
– Select a convenient location on the side of the fixture so the Charge Indicator can be seen after installa-
Illustration 1 Recessed Troffer Fixture
BALLAST CHANNEL
COVER
7/8" BUSHING
CHARGE INDICATOR LAMP
– Select a convenient location with proper clearance in the ballast cover and drill or punch a 7/8
Illustration 1
Illustration 2
.
.
Illustration 2 Strip Fixture
FPS-HL
FLEX CONDUIT
PLASTIC TUBE
FIXTURE LENS
Page 2
FPS-HL
OBSERVE PROPER POLARITY
FLEX CONDUIT
FIXTURE
WHITE/RED
CHARGE INDICATOR LIGHT
LEAD
+ RED
+ RED LEAD
5. INSTALLING THE TEST SWITCH
The test switch should be mounted on the ballast channel cover of a recessed troffer, or on the side of a strip fixture, preferably adjacent to the charge indicator. Drill or punch a 1/2 mounting hole.
6. WIRING THE A.C. INPUT
A. The FPS-HL and A.C. ballast B. The FPS-HL requires an
cap the unused lead.
C. When the FPS-HL is used with a switched fixture, the A.C. input to the FPS-HL must be connected ahead of the fixture
switch. Refer to
Illustration 3
Illustration 3 Switched Fixture Unswitched Fixture
must
be on the same branch circuit.
unswitched
A.C. power source of either 120 or 277 volts. Select the proper voltage lead and
for switched and unswitched fixture wiring diagrams.
WHITE
BLACK
(277V) ORG
(120V) BLK
(COMM) WHT
Select proper voltage lead. Cap unused lead.
A.C. BALLAST
FPS-HLFPS-HL
HOT A.C. LINE
COMMON
WALL SWITCH
TEST SWITCH
Select proper voltage lead. Cap unused lead.
WHITE
BLACK
(277V) ORG
(120V) BLK
(COMM) WHT
A.C. BALLAST
HOT A.C. LINE
COMMON
TEST SWITCH
7. LABELS
Attach the appropriate labels adjacent to the Test Switch and Charge Indicator. Annotate Re-lamping label for lamp type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone attempting to service the fixture.
8. COMPLETING INSTALLATION
When the installation is complete, switch the A.C. power on and join the FPS-HL unit connector.
OPERATION
Normal Mode A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The FPS-HL is in the standby charging mode. The Charge Indicator will be lit providing a visual indication that the battery is being charged.
Emergency Mode The A.C. power fails. The FPS-HL senses the A.C. power failure and automatically switches to the
gency Mode
stored, the FPS-HL switches the system back to the
. One or two lamps are illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. power is re-
Normal Mode
and resumes battery charging. See page 1 of the Instruction
Manual.
Emer-
TESTING & MAINTENANCE
Initial Testing Allow the unit to charge approximately 1 hour, then conduct a short discharge test. Allow a 24 hour charge before conducting a one hour test.
The FPS-HL is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety Code, outlines the following schedule:
Monthly – Insure that the Charge Indicator light is illuminated. Conduct a 30 second discharge test by depressing the Test Switch. One lamp or two lamps should operate at full or reduced output, depending on your configuration.
Annually – Insure that the Charge Indicator light is illuminated. Conduct a full 1
as intended for the duration of the test.
Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Consult Customer Service for current warranty information.
Page 3
1
/2 hour discharge test. The unit should operate
TYPICAL WIRING DIAGRAMS
For wiring diagrams of ballasts not shown, consult our Customer Service.
1. ONE LAMP RAPID START BALLAST
SWITCHED OR UNSWITCHED
BLACK WHITE
RED RED
A.C.
Ballast
*LAMP
*AC / EMERGENCY
BLUE BLUE
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
UNIT
EMERGENCY
FPS-HL
BALLAST
CHARGE
INDICATOR
VIOLET
BROWN
ORG (277V)
BLK (120V) WHITE
BRN/WHT
LINE
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS, LAMP OPERATION SECTION FOR VARIOUS OPTIONS.
2. TWO LAMP RAPID START BALLAST
SWITCHED OR UNSWITCHED
BLACK WHITE BLUE
A.C.
YELLOW
Ballast
YELLOW
LAMP
*LAMP
*AC / EMERGENCY
BLUE
RED RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
UNIT
EMERGENCY
FPS-HL
BALLAST
VIOLET
CHARGE
INDICATOR
BROWN
ORG (277V)
BLK (120V) WHITE
BRN/WHT
LINE
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS, LAMP OPERATION SECTION FOR VARIOUS OPTIONS.
3. THREE LAMP RAPID START BALLAST
SWITCHED OR UNSWITCHED
BLACK WHITE
BLUE
BLUE YELLOW YELLOW
A.C.
Ballast
LAMP
*LAMP
LAMP
*AC / EMERGENCY
BLUE/WHT BLUE/WHT
RED RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
UNIT
EMERGENCY
FPS-HL
BALLAST
CHARGE
INDICATOR
VIOLET
BROWN
ORG (277V)
BLK (120V) WHITE
BRN/WHT
LINE
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTION LEADSREFER
TO INSTALLATION INSTRUCTIONS, LAMP OPERATION SECTION FOR VARIOUS OPTIONS.
5. TWO LAMP INSTANT START BALLAST
SWITCHED OR UNSWITCHED LINE
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER TO INSTALLATION INSTRUCTIONS, LAMP OPERATION SECTION FOR VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
BLACK
WHITE
A.C.
Ballast
LAMP
*LAMP
*AC / EMERGENCY
BLUE
RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
UNIT
EMERGENCY
FPS-HL
BALLAST
CHARGE
INDICATOR
VIOLET
BROWN
ORG (277V)
BLK (120V) WHITE
BRN/WHT
6. TWO LAMP INSTANT START BALLAST
SWITCHED OR UNSWITCHED
BLACK WHITE
RED
A.C.
Ballast
LAMP
*LAMP
*AC / EMERGENCY
BLUE
BLUE
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
EMERGENCY
FPS-HL
UNIT
INDICATOR
BALLAST
CHARGE
VIOLET
BROWN
ORG (277V)
BLK (120V) WHITE
BRN/WHT
LINE
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER TO INSTALLATION INSTRUCTIONS, LAMP OPERATION SECTION FOR VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
7. THREE LAMP INSTANT START BALLAST
SWITCHED OR UNSWITCHED
BLACK WHITE
RED
A.C.
Ballast
LAMP
LAMP
*LAMP
*AC / EMERGENCY
BLUE
BLUE
BLUE
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
UNIT
EMERGENCY
FPS-HL
BALLAST
CHARGE
INDICATOR
VIOLET
BROWN
ORG (277V)
BLK (120V) WHITE
BRN/WHT
LINE
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER TO INSTALLATION INSTRUCTIONS, LAMP OPERATION SECTION FOR VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
4. ONE LAMP INSTANT START BALLAST
SWITCHED OR UNSWITCHED
BLACK
WHITE
RED
A.C.
Ballast
*LAMP
*AC / EMERGENCY
BLUE BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
EMERGENCY
FPS-HL
BALLAST
UNIT
INDICATOR
CHARGE
VIOLET
BROWN
ORG (277V)
BLK (120V) WHITE
BRN/WHT
LINE
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER TO INSTALLATION INSTRUCTIONS, LAMP OPERATION SECTION FOR VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
9. TWO LAMP RAPID START BALLAST W/2 LAMP EMERGENCY OPERATION
SWITCHED OR UNSWITCHED
BLACK WHITE
YELLOW YELLOW
Rev. 021903 68160-006
A.C.
Ballast
*LAMP
*LAMP
*AC / EMERGENCY
BLUE BLUE
RED RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
EMERGENCY
FPS-HL
UNIT
INDICATOR
BALLAST
CHARGE
VIOLET
BROWN
ORG (277V)
BLK (120V) WHITE
BRN/WHT
LINE
UNSWITCHED
COMMON
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS, LAMPS OPERATION SECTION FOR VARIOUS OPTIONS
8. FOUR LAMP INSTANT START BALLAST
BLACK WHITE
YELLOW
YELLOW
A.C.
Ballast
LAMP
LAMP
LAMP
*LAMP
*AC / EMERGENCY
BLUE BLUE
RED
RED
BLUE
BLUE/WHT
RED/WHT
RED
YELLOW
CONNECTOR
COMMON
EMERGENCY
FPS-HL
BALLAST
UNIT
INDICATOR
CHARGE
VIOLET
BROWN
ORG (277V)
BLK (120V) WHITE
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR UNTIL
BRN/WHT
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER TO INSTALLATION INSTRUCTIONS, LAMP OPERATION SECTION FOR VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
10. TWO LAMP INSTANT START BALLAST W/2 LAMP EMERGENCY OPERATION
Page 4
BLACK WHITE
RED
A.C.
Ballast
*LAMP
*LAMP
*AC / EMERGENCY
BLUE
BLUE
BLUE
BLUE/WHT
RED/WHT
YELLOW
CONNECTOR
COMMON
RED
UNIT
EMERGENCY
BALLAST
FPS-HL
CHARGE
INDICATOR
ORG (277V)
BLK (120V) WHITE
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
VIOLET
BROWN
BRN/WHT
DO NOT MATE CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.
LAMP SELECTOR LEADSREFER
TO INSTALLATION INSTRUCTIONS, LAMP OPERATION SECTION FOR VARIOUS OPTIONS.
CONNECT BLU/WHT AND RED/WHT
WIRES TOGETHER
SWITCHED OR UNSWITCHED LINE
UNSWITCHED
COMMON
SWITCHED OR UNSWITCHED LINE
UNSWITCHED
COMMON
Loading...