Thomas & Betts Elastimold 151SOP, Elastimold K151SOP Operating Instructions Manual

IS ---0235
R
IS ---151SOP
October 2000
Page 1 of 2
Operating Instructions
151SOP/K151SOP
Deadbreak Insulated Parking Bushing
Instructions
The 151SOP is designed to terminate t he female deadbreak connector interface of the 154LR or the 156LR Elbows (other products should not be used since the 151SOP bail is designed to secure elbows only) rated for 15kV class (8.3k V phase --­to---ground and 14.4kV phase --- t o phase) 200 ampere. The K151SOP provides the same function for the 25kV class (15.2kV p h a s e --- t o --- g r ou n d a n d 2 6 . 3 k V p h a s e --- t o --- p h as e ) 2 0 0 a m p e r e r at i n g .
DANGER
All apparatus must be de--energized during installation or removal of part(s). For loadbreak products follow operating instructions. All deadbreak connectors must be de--energized before operating.
All apparatus must be installed and operated in accordance with individual user, local, and national work rules. These instructions do not attempt to provide for every possible contingency.
Do not touch or move energized products by hand. Excess distortion of the assembled product may result
in its failure. Contact with solvents, transformer oil, motor oil and
similar substances will degrade jacket conductivity and insulation level if not immediately wiped off.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.
Inspect parts for damage, rating and compatibility with mating parts.
This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. These instructions arenot intended asa substitutefor adequate training or experience in such safety practices.
Failure to follow these instructions will result in damage to the product and serious or fatal injury.
If this product is supplied with a protective shipping cover(s), remove this shipping cover(s) and replace with the appropriate HV insulated cap(s) or connector(s) before submerging or energizing the circuit.
IMPORTANT
1. Check contents of package to insure it is complete and undamaged.
2. Check all components to insure proper fit with cable and/or mating products.
STEP 1
Remove protective shipping cap and clean the mating interface of the insulated parking bushing. Lubricate this surface. Use only the supplied lubricant or ELASTIMOLD approved lubricants. DO NOT SUBSTITUTE. Other lubricants may be harmful to this product and its mating products. Always replace the protective cap when the insulated parking bushing is not in use.
IS ---0235 IS ---151SOP October 2000
Printed in U.S.A.
Esna Park Drive, Hackettstown, New Jersey 07840 USA (908)852-- 1122 FAX: (908)813-- 2147
A Unit of Thomas & Betts Corporation
3. Read entire installation instructions before starting.
4. Have all required toolsat hand and observe cleanliness throughout the procedure.
Bail
Remove Shipping Cap
Clean and Lubricate
STEP 2
Attach hotstick to eye of insulated parking bushing carriage assembly. Slide carriage assembly into parking stand. Push bail out of way so it w ill not interfere with placement of elbow connector.
Parking Stand
October 2000
Page 2 of 2
Hotstick
IS ---0235
STEP 3
Follow the applicable instructions to make a voltage test before removing the elbow connector from the apparatus bushing. Remove elbow connector from apparatus bushing and place on insulated parking bushing. DO NOT REMOVE IF VOLTAGE TEST INDICATES CONNECTOR IS ENERGIZED.
Elbow Connector
STEP 4
BAIL MUST BE USED TO SECURE ELBOW.
Position the bail eyebolt directly over the bail locater on the elbow.Tightendownonbaillocaterbyturningeyeboltwith the hotstick in a clockwise direction. If entire assembly (insulated parking bushing and elbow) is to be removed from parking stand, attach hotstick to eye of carriage assembly, remove from parking stand and place where desired. To return elbow connector to apparatus bushing, simply reverse the operational sequence.
Bail Locator
Bail Eyebolt
To Ground
Esna Park Drive, Hackettstown, New Jersey 07840 USA (908)852-- 1122 FAX: (908)813-- 2147
A Unit of Thomas & Betts Corporation
Loading...