68-HP-FFMK
FURNITURE FEED MOUNTING KIT
Installation Instructions
IMPORTANT: Read all instructions before installing oor box, carpet plate or mounting kit.
FFMK
Ring
WARNING
RISK OF SHOCK, DISCONNECT
POWER BEFORE INSTALLATION.
68HP Furniture Feed Instructions
Table of Contents
Catalog Number
68-HP
68-HP-CI
68-HP-FFMK
and
68-HP-FFC-XXX
1.0 Activation and Floor Preparation
2.0 Power and Data Feed
3.0 Install Cover to Floor Box
4.0 Removal of Cover and FFMK Ring (Only when necessary)
SOLD SEPARATELY
68-HP-FFC-ALM
Aluminum Cover
68-HP-FFC-BRS
Brass Cover
68-HP-FFC-BLK
Black Cover
CAUTION
Floor Box should be installed by a qualied
electrician in accordance with national and local
electrical codes.
(3) Cover Screws
Voltage
Divider
FIGURE 1
68-HP-FFMK
Funiture Feed
Mounting Kit
SOLD SEPARATELY
68-HP
Series Floor Box
NOTE: 68-HP-FFMK can be
installed in either the
68-HP or 68-HP-CI
Floor Box.
68-HP 68-HP-CI
TA04574 B Page 1 of 4

1.0 Activation and Floor Preparation
(68-HP Floor Box shown in instructions)
Finished Floor Concrete
1.1 Floor box must already be set in concrete
according to instructions furnished with oor box.
1.2
Remove temporary cover from 68-HP or 68-HPCI oor box. Use a saw to cut top of box ush to
concrete oor surface (see Figure 2).
CAUTION
Box must be cut square and parallel with
concrete oor surface (see Figure 2).
1.3 Install oor covering and trim hole around oor
box opening to 7” diameter (see Figure 3).
1.4 Measure depth of oor box from nished oor to
bottom of the box. Use a saw to cut the voltage
divider so that when it is inserted in the oor box,
the top of the divider is 2-1/2” ±1/8” below the
nished oor surface (see Figures 4 and 5).
1.5
Place the voltage divider in box. The ribbed side of
the divider must face the power side. The letters
“HP” will be visible in bottom of the box when
divider is in correct orientation (see Figures 4 and 6).
Power Side Data Side
Ribbed side
of Voltage
Divider must
face Power
Side of box
FIGURE 4
Bottom of
Voltage Divider
MUST rest
on bottom of
Floor Box
Bottom
of Floor
Box
2-1/2”
±1/8”
Measure
depth of
box from
nished
oor (see
Step 1.4)
CUT
FIGURE 2
Edge of
Floor Box
See Sealant
Note 3.2.1
Temporary
Box Cover
See Sealant
Note 3.2.2
Trim hole in
Floor Covering
to 7” Diameter
FIGURE 5
Power
Side
Voltage
Divider
FIGURE 6FIGURE 3
Voltage
Divider
Keep this
side
When Divider is installed “HP”
must be visible at bottom of box.
For cut height,
See Step 1.4
Data
Side
TA04574 B Page 2 of 4

2.0 Power and Data Feed
2.1 Verify voltage divider is in oor box (see Step 1.5).
2.2 Secure 68-HP-FFC-XXX cover to FFMK ring using
(3) screws furnished with cover. See instructions
furnished with cover (see gure 7).
2.3 Do not lower FFMK ring and cover into oor Box
until power conductors and data cable are fed
through (see Steps 2.4, 2.5, and 2.6)
2.4 Floor Box and Cover must be grounded according
to local and national electric codes. Connect FFMK
ring ground wire to circuit ground wire. When
cast iron box (68-HP-CI) is used, connect circuit
ground wire to box ground. Note: 68-HP-CI ground
wire shown in instruction sheet furnished with box
(see Figure 8).
2.5 Remove cover plugs and pull power (electrical)
conductors and grounding wires up through power
side of oor box and through power side of FFMK
ring. Continue pulling conductors through 1”
threaded conduit hole in cover (see Figure 8).
2.6 Pull data cables up through data side of oor box
and through data side of FFMK ring. Continue
pulling data cables through 1-1/2” threaded
conduit hole in cover (see Figure 8).
(1) Plug
(3) Cover Screws
POWER
Cover
Screw holding
FFMK Ring
Retainer Clip
(see Step 4.1)
(1-1/2) Plug
DATA
FFMK
Ring
3.0 Install Cover to Floor Box
3.1 Verify voltage divider is in oor box. (see Step 1.5).
3.2 Applying sealant to floor:
3.2.1 Concrete and carpet: Apply moderate
amount of sealant or caulk directly to
concrete oor fully around box opening.
(about 1/8” from outside edge of box).
Use enough sealant to block water entry
(see Figure 3).
3.2.2 Tile, Wood and Linoleum: Apply moderate
amount of sealant directly on nished oor.
Fully surround 7” diameter opening in oor.
Use enough sealant to block water entry
(see Figure 3).
3.3 Carefully align guide ribs on FFMK ring with
divider and grooves in oor box. The 1” threaded
power conduit hole must be located over power
compartment in box. Lower FFMK ring and cover
assembly into box opening. Apply pressure to top
of cover to complete installation (see Figure. 8 and
9). Clean excess sealant from around cover edge.
3.4 Attach suitable conduit ttings. All unused ports in
cover are to be plugged with plugs furnished with
cover. Use thread sealer on all plugs and ttings to
block water entry (See Figure 9 and 10).
3.5 Figure 9 shows conduit ttings attached to cover.
Figure 10 shows plugs installed in cover.
4.0 Removal of Cover & FFMK Ring
(Only when necessary).
4.1 Remove the cover 68-HP-FFC-XXX. Remove the
(2) screws holding the retainer clips (see gure 7).
The FFMK ring can be lifted out of box when the
retainer clips are dis-engaged from the ring.
FIGURE 7
See Step 3.4
POWER
Threaded Hole
Ground Wire
see Step 2.4
Voltage Divider
Power Side
68-HP
Floor Box
FIGURE 8
1”
FFMK Ring
Ground Wire
see Step 2.4
DATA
1-1/2”
Threaded Hole
Align Ribs on
FFMK Ring with
Dividers and
Grooves in Box
(see Step 3.3)
Data Side
TA04574 B Page 3 of 4

FIGURE 9 FIGURE 10
WARRANTY: Thomas & Betts sells this product with the understanding that the user will perform all necessary tests to determine the suitability of this product for the user’s
intended application. Thomas & Betts warrants that this product will be free from defects in materials and workmanship for a period of ninety (90) days following the date of
purchase. Upon prompt notification of any warranted defect, Thomas & Betts will, at its option, repair or replace the defective product or refund the purchase price. Proof of
purchase is required. Misuse or unauthorized modification of the product voids all warranties.
Limitations and Exclusions: THE ABOVE WARRANTY IS THE SOLE WARRANTY CONCERNING THIS PRODUCT, AND IS IN LIEU OF ALL OTHER WARRANTIES
EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE,
WHICH ARE SPECIFICALLY DISCLAIMED. LIABILITY FOR BREACH OF THE ABOVE WARRANTY IS LIMITED TO COST OF REPAIR OR REPLACEMENT OF THE
PRODUCT, AND UNDER NO CIRCUMSTANCES WILL THOMAS & BETTS BE LIABLE FOR ANY INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Thomas & Betts Corporation
Memphis, Tennessee
www.tnb.com
TA04574 B Page 4 of 4
© 2010 Thomas & Betts. All Rights Reserved.