IS--0287
IS--3701A4
January 2010
Page 1 of 2
Installation Instructions
3701A4
Loadbreak Bushing Insert
CONTENTS: Loadbreak Bushing Insert, Lubricant, Installation Instructions.
The 3701A4 is designed to provide the apparatus interface for Elastimold 35kV class (21.1kV phase--to--ground) loadbreak
connections. This bushing provides a vent ring for improved switching performance and is identified by a white button installed
in one grounding eye.
DANGER
All apparatus must be de--energized during installation
or removal of part(s).
All apparatus must be installed and operated in
accordance with individual user, local, and national
work rules. These instructions do not attempt to
provide for every possible contingency.
Do not touch or move energized products.
Excess distortion of the assembled product may result
in its failure.
Inspect parts for damage, rating and compatibility with
mating parts.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.
This product should be installed only by competent
personnel trained in good safety practices involving
high voltage electrical equipment. These instructions
are not intended as a substitutefor adequate training or
experience in such safety practices.
Failure to follow these instructions will result in
damage to the product and serious or fatal injury.
If this product is supplied with a protective shipping
cover(s), remove this shipping cover(s) and replace
with the appropriate HV insulated cap(s) or
connector(s) before submerging or energizing the
circuit.
IMPORTANT
1. Check contents of package to ensure they are complete
and undamaged.
2. Check all components to ensure proper fit with cable
and/or mating products.
3. Read entire installation instructions before starting.
4. Have all required tools at hand and maintain cleanliness
throughout the procedure.
STEP 1
Inspect the apparatus bushing well to ensure it is dry and free from all contaminants. Remove the protective shipping cover
from the bushing insert. Lubricate the bushing well interface area of the bushing insert with the supplied lubricant or
ELASTIMOLD approved lubricants. DO NOT SUBSTITUTE. Other lubricants may be harmful to this product and its mating
products.
REMOVE
Cover
IS--0287
IS--3701A4
January 2010
Printed in U.S.A.
Lubricate
Lubricate
8155 T&B Boulevard, Memphis, Tennessee 38125
(800) 888--0211 Fax: (800) 888--0690
Shipping

IS--0287
January 2010
Page 2 of 2
STEP 2
Place the lubricated portion of the bushing insert in the
apparatus bushing well. Hand tighten the bushinginsert in a
clockwise direction until it bottoms.
Apparatus
White Button
Vent Ring
Bushing Well Clamped
(or Welded Type)
STEP 3
Push a length of copper wire (No. 14 AWG (2,5mm2) or equivalent) through one of the grounding tabs on the bushing insert.
Make a small loop and twist tight, taking care not to damage the grounding tab. Connect free end of electrostatic grounding
wire to the system ground using a suitable connector.
The electrostatic grounding wire should be installed in such a manner so as not to contact the bushing interface or adjacent
bushing interfaces or interfere with the placement of accessories on nearby parking stands.
This step provides assurance that the insulation shield on the bushing insert is grounded.
Bushing
Interface
Apparatus
To System Ground
STEP 4
Thoroughly wipe the bushing interface clean of any contaminants and lubricate with the supplied lubricant. Install the mating
products to the bushing insert following the instructions supplied with the mating products. If the bushing insert is not to be
immediately mated with an elbow connector, insulated cap or grounding elbow connector, replace the shipping
cover. Do not energize or submerge the apparatus with the shipping cover on the bushing insert. This is a protective
cover only, which is not insulated or water tight and only intended to keep the bushing surfaces clean during handling and
installation.
Clean Bushing Insert/
Elbow Connector
Interface and
Lubricate
Thoroughly
Apparatus
Insulated Cap or Elbow