IS---274 J2,J3,J4---5(1)
IS---0799
September 2010
Page 1 of 2
Installation Instructions
274J2(1), J3(1), J4(1)-- 5
Two--, Three-- , and Four--Point Loadbreak Junctions
CONTENTS: Loadbreak Junction with Holdown Brackets and Hardware (as required), Shield Plate, Installaion Instructions.
The two --- , three--- , and four--- way loadbreak junctions are used for sectionalizing, looping, tapping or for apparatus change
out. These junctions provide interconnected apparatus interfaces for Elastimold 25kV class (15.2kV phase ---to ---ground
and 26.3kV phase---to--- phase) loadbreak connectors. A yellow band provides indication of fullelbow seating and also provides vents for improved switiching performance. This product is identified by a round yellow marker supplied with this kit.
Remove the adhesive backed marker and attached it to the mounting surface when it will be visable to operator.
DANGER
All apparatus must be de--energized during installation
or removal of part(s). For loadbreak products follow
operating instructions. All deadbreak connectors must
be de--energized before operating. All 200A deadbreak
connectors must be mechanically secured with bails
when connected.
All apparatus must be installed and operated in
accordance with individual user, local, and national
work rules. These instructions do not attempt to
provide for every possible contingency.
Do not touch or move energized products.
Excess distortion of the assembled product may result
in its failure.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.
Inspect parts for damage, rating and compatibility with
mating parts.
This product should be installed only by competent
personnel trained in good safety practices involving
high voltage electrical equipment. These instructions
are not intended as a substitute for adequate training or
experience in such safety practices.
Failure to follow these instructions will result in
damage to the product and serious or fatal injury.
If this product is supplied with a protective shipping
cover(s), remove this shipping cover(s) and replace
with the appropriate HV insulated cap(s) or
connector(s) before submerging or energizing the
circuit.
IMPORTANT
1. Check contents of package to ensure they are complete
and undamaged.
2. Check all components to ensure proper fit with cable
and/or mating products.
3. Read entire installation instructions before starting.
4. Have all required tools at hand and maintain cleanliness
throughout the procedure.
Front Surface Mount Assembly Front Surface Through Mount Assembly
Yellow Seating Indicator and Vent Ring
Mounting Surface
Hold Down Bracket
Shield Bracket
Mounting Hardware
Junction
Attached Round Yellow Marker
IS---0799
IS---274 J2,J3,J4---5(1)
September 2010
Printed in U.S.A.
8155 T&B Boulevard, Memphis, Tennessee 38125
(800) 888--0211 Fax: (800) 888-- 0690

STEP 1
Determine the desired location of the junction assembly and drill holes as shown.
Front View Rear Mount
4.000
.375 Dia. Hole
IS---0799
September 2010
Page 2 of 2
2.000
1.125
2.500
4.000
J2
.375 Dia. Hole
3.00 Dia. Hole
J3
J4
2.500
STEP 2
Assemble loadbreak junction, shield plate and hold down brackets with supplied fasteners, attach to flat surface and tighten
all fasteners securely to ensure no movement during operation.
CAUTION
THE SHIELD PLATE, HOLD DOWN BRACKETS AND BLACK CONDUCTIVE RUBBER SHIELD MUST BE GROUNDED. IF
THE MOUNTING SURFACE IS CONDUCTIVE ANDGROUNDED, NO OTHER GROUND IS NECESSARY. FOR INSULATING
MOUNTING SURFACES A GROUNDING LUG (NOT PROVIDED) MUST BE ATTACHED WITH ONE OF THE MOUNTING
BOLTS AND A GROUND WIRE (14AWG MINIMUM) BE ATTACHED TO THE LUG AND A GROUND BUS.
STEP 3
Thoroughly wipe the bushing interface clean of any
contaminants and lubricate with the supplied lubricant.
Install the matingproducts to the bushinginsert following the
instructions supplied with the mating products.
Clean Bushing Interface/Elbow Connector
STEP 4 SEATING INDICATION
Complete assembly of an insulated cap or elbow is indicated
by no portion of the yellow band being visible when viewed
from the side.
Insulated Cap or Elbow
Interface and Lubricate Thoroughly