DANGER
All apparatus must be de--energized during installation
or removal of part(s). For loadbreak products follow
operating instructions. All deadbreak connectors must
be de--energized before operating and must be
mechanically secured with bails when connected.
All apparatus must be installed and operated in
accordance with individual user, local, and national
work rules. These instructions do not attempt to
provide for every possible contingency.
Do not touch or move energized products by hand.
Excess distortion of the assembled product may result
in its failure.
Contact with solvents, transformer oil, motor oil and
similar substances will degrade jacket conductivity
and insulation level if not immediately wiped off.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.
Inspect parts for damage, rating and compatibility with
mating parts.
This product should be installed only by competent
personnel trained in good safety practices involving
high voltage electrical equipment. These instructions
arenot intended as a substitute foradequate trainingor
experience in such safety practices.
Failure to follow these instructions will result in
damage to the product and serious or fatal injury.
If this product is supplied with a protective shipping
cover(s), remove this shipping cover(s) and replace
with the appropriate HV insulated cap(s) or
connector(s) before submerging or energizing the
circuit.
IMPORTANT
1. Check contents of package to insure they are complete
and undamaged.
2. Check all components to insure proper fit with cable
and/or mating products.
3. Read entire installation instructions before starting.
4. Have all required tools at hand and maintain cleanliness
throughout the procedure.
IS---0006
IS---150TB --- 4
October 2000
Printed in U.S.A.
Esna Park Drive, Hackettstown, New Jersey 07840 USA
(908)852--- 1122 FAX: (908)813-- -2147
A Unit of Thomas & Betts Corporation

IS---0006
October 2000
Page 2 of 3
FOR 150T or K150T TEE CONNECTOR
STEP 1
Prepare the cables according to the installation
instructions packed wi th the EL ASTIMOLD
connectors. Slip a collar, large end first, onto each
connector. Now, Install the cables into the connector
and mate the connectors to the tee connector. Use a
vent rod when mating each interface. Vent rods are
supplied with the mating connectors.
Cable
Collar
Connector
Vent Rod
Tee
Connector
Connector
Vent Rod
Connector
Cable
Collar
STEP 2
A.) A gap of 3/32” (2,4 mm) or less between the
skirts of the connectors and the recess of the
tee connector assures proper installation.
B.) Unfold the three straps being careful not to
kink them. Slip two straps, one on each side,
under the two collars on the assembled tee
splice run. Allow 5/8” (15,9 mm) to
3/4” (19,1 mm) of one strap to extend
through the collar. Now, using pliers, bend
and form the straps around the collar as
illustrated at the right. Follow the same
procedure for the second strap on the same
collar. Push this assembly tight against the
connector.
C.) Push the opposite collar tight against the
opposite connector. Pull both straps toward
the opposite collar to assure a tight
assembly. Cut off the strap 5/8” (15,9 mm) to
3/4” (19,1 mm) past the collar. Bend and
form each of these straps around the collar
as previously instructed in step 2B.
Collar
Bend and Form Strap
Strap
3/32”
or
Less
Collar
Cable
3/32”
or
Less
Collar
Bend and Form Strap
5/8” to 3/4”
Bend and
Form Strap
Collar
Strap
Strap

STEP 3
Slip one end of the third strap under the collar located on the
tap leg of the tee splice assembly. As previously instructed,
bend and form the strap around the collar. Push the collar
tight against the connector. Now, bend the strap around the
tee connector, over the previously installed straps, and slip it
through the opposite side of the collar. Cut the strap 5/8”
(15,9 mm) to 3/4” (19,1 mm) past the collar. Note that the
strap will have to be placed to one side of the rubber
projection on the tee connector. T o assure a tight assembly,
pull the straps towards the tee connector and follow the
previous procedure used for securing the strap to the collar.
Rubber Projection
IS---0006
October 2000
Page 3 of 3
Third Strap
Bend and Form Strap
Collar
FOR 150S or K150S IN--LINE JUNCTIONS
For the 150S/K150S, only two of the three straps included in the assembly package are used.
STEP 1
Prepare the cables according to the installation instructions packed with the ELASTIMOLD connectors. Slip a collar, large end
first, onto each connector. Now, install the cables into the connectors and mate the connectors to the in--line junction. Use a
vent rod when mating each interface. Vent rods are supplied with the mating connectors.
Cable
Collar
Connector
Vent Rod
In---Line Junction
Vent Rod
Connector
STEP 2
A.) A gap of 3/32” (2,4 mm) or less between the skirts of the connectors and the recess of the in--line junction assures
proper installation.
B.) Unfold the two straps being careful not to kink them. Slip two straps, one on each side, under the two collars on the
assembled splice run. Allow 5/8” (15,9 mm) to 3/4” (19,1 mm) of one strap to extend through the collar. Now, using
pliers, bend and form the straps around the collar as illustrated below. Follow the same procedure for the second strap
on the same collar. Push this assembly tight against the connector.
C.) Push the opposite collar tight against the opposite connector. Pull both straps toward the opposite collar to assure a
tight assembly. Cut off the straps 5/8” (15,9 mm) to 3/4” (19,1 mm) past the collar. Bend and form each of these straps
around the collar as previously instructed in step 2B.
3/32” or Less
Bend and Form Strap
Bend and Form Strap
5/8” to 3/4”
Cable
Collar
Collar
Collar
Strap
Collar
Bend and
Form Strap
Strap
Strap