Thinget XC3 Series Installation Manual

THINGET
XC3 Series Programmable Controller
Installation Guide Functions
-Dry and no dew - Insulate voltage: Up to DC 500V
-Fr from corrosive gases and dusts - Anti noise: 1000 V 1uS pulse per minute
-Don’t install he unit in areas subject to -Ambient temperature: 0~60 C Liquid chemicals -Ambient humidity: 5~95% (no dew) Wiring -COM1: RS232, connect with host machine, HMI program or debug
-Far from the high voltage, power supply or -COM2: RS232/RS485, connect with network or aptitude instrument Cable with high current -COM3: BD board COM port RS232/RS485
-Never over voltage, make sure the polarity of -Installation:can use M3 screw to fix or install directly on
DIN46277
Power supply is correct -Grounding: The third type grounding (cant public ground with strong
power system)
Power Specification
-to avoid voltage decrease please use cable thicker than 2mm
- Even appear power cut within 10ms; PLC can still go on working. But if long time power cut or abnormal power decrease, PLC will stop working, output will also appear OFF status, when recover power supply, the PLC will auto to work.
- Connect the grounding terminals of basic units and extend modules together, then ground.
Output Specification Input Specification
Terminal arrangement
1-Input Terminals 2- BD expansion 3-Input Label 4-COM port 5-COM port 6-COM port's cover board 7-Output label 8-Output terminals 9-Screws 10-Input indicate LED 11-Extension port 12-Programming status indicate LED 13-Output indicate LED
Rated Voltage AC 100V~240V Voltage allow bound AC 90V~265V Rated frequency 50/60 Hz Allow momentary power-cut time
Interrupt time<0.5AC cycle,alternation>1sec
Impact current Max 40A 5ms below/AC100V
Max 60A 5ms below/AC200V Max power consumption 12W Power for sensor use 24V DC max400mA
Transistor Output
Relay output Items
Below DC5~30V Below
AC250V,DC30V
Interior power
Optical coupling insulation
Mechanism insulation
Circuit insulation
Indicate lamp LED Action denote
0.8A 3A Resistance
load
12W/DC24v 80VA Inductive
load
1.5W/DC24V 100W Lamp load
Max Load
DC5V 2mA Mini load
Below 0.2ms 10ms OFF to
ON
Below 0.2ms 10ms ON to
OFF
Response time
DC24V
Input signal's voltage
7mA/DC24V
Input signal's current
Up to 4.5mA
Input on current
Law than 1.5mA
Input off current
About 10ms
Input response time
Contact input or NPN open collector transistor
Input signal's format
Photo-electricity coupling insulation
Circuit insulation
LED light when input ON
Input action's display
Com Port Definition
Com Port 1: Com Port2:
Connection of programmable cable is the following
4: RXD
5: TXD
8: GND
Input / Output Example
Overall Dimension
XC3 series 14 points main unit (including 16 points expansion) XC3 other types
L2 (mm)L1 (mm)XC3 Other types 139131XC3 24/32 points main unit,32 points expansion
207.4199.4XC3 48/60 points main unit
2: PRG 4: RxD
5: TxD 6: VCC
8: GND