Thies CLIMA Ultrasonic Anemometer 2D Operating Instructions Manual

Ultrasonic Anemometer 2D
Operating Instructions 4.3800.00.940
1. Range of Application
The Ultrasonic Anemometer 2D is designed to detect the horizontal components of wind speed and wind direction in two dimensions as well as the virtual temperature. Due to its very short measurement intervals, the instrument is ideal for the inertia-free measurement of gusts and peak values. In certain weather situations the accuracy of the air temperature measurement (virtual-temperature) surpasses that one of the classic method where the temperature transmitter is used in a weather and thermal radiation shield. The measured data are available as analogue signals and as a data telegram via a serial interface. The ultrasonic transducers as well as its carrying arms are automatically heated so that the measuring results, in case of critical ambient temperatures, are not affected by icing rain or snow.
2. Mode of Operation
The Ultrasonic Anemometer 2D consists of 4 ultrasonic transducers, in pairs of 2 which are opposite each other at a distance of 200 mm. The two measurement paths thus formed are vertical to each other. The transformers act both as acoustic transmitters and acoustic receivers. The respective measurement paths and their measurement direction are selected via the electronic control. When a measurement starts, a sequence of 4 individual measurements in all 4 directions of the measurement paths is carried out at maximum possible speed. The measurement directions (acoustic propagation directions) rotate clockwise, first from south to north, then from west to east, from north to south and finally from east to west. The mean values are formed from the 4 individual measurements of the path directions and used for further calculations. A measurement sequence takes approx. 10 msec at +20°C.
1 -12 021235/10/01
3. Measurement Principle
3.1 Wind speed and direction
The speed of propagation of the sound in calm air is superposed by the speed components of an air flow in wind direction.
N
Wind from NNE
A wind speed component in the direction of the propagation of the sound supports the speed of propagation, thus leading to an increase in the speed. A
Y - component
wind speed component opposite to the direction of propagation, on the contrary, leads to a reduction of the speed of propagation.
W
E
The speed of propagation resulting from the superposition leads to different propagation times of the sound at different wind velocities and directions over a
X - component
fixed measurement path. As the speed of sound is very dependent on the air temperature, the propagation time of the sound is measured on both of the measurement paths in both directions. In this way, the influence of the temperature-
S
dependent speed of sound on the measurement result can be eliminated.
By combining the two measuring paths which are at right angles to each other, one obtains the measurement results of the sum and the angle of the wind speed vector in the form of rectangular components.
After the rectangular speed components have been measured, they are then transformed by the µ-processor of the anemometer into polar co-ordinates and output as sum and angle of wind speed.
3.2 Acoustic-Virtual Temperature
As previously mentioned, the speed of the propagation of sound shows a radix dependency on the absolute air temperature, but is rather independent of air pressure, and only slightly dependent of humidity. Thus these physical properties of gases can be used to measure air temperature at constant and known chemical composition. It is a measurement of gas temperature which is made without thermal coupling to a solid state sensor.
The advantages of this measured variable is, on the one hand, its inertia free reaction to the actual gas temperature, and, on the other hand, the avoidance of measurement errors such as those which occur when a solid state temperature sensor is heated up by radiation.
Due to the low dependency of the speed of propagation of the sound on the air humidity, the “Virtual Temperature” refers to dry air (0% humidity) under the same pressure conditions as that one actually measured.
The deviation of the measured “acoustic-virtual temperature”, compared with the real air temperature, is linear-dependent from the absolute humidity content of the air. The part of water vapour in the air increases proportionally the sonic speed, as H only half of the mass of the remaining air-molecules (O
and N2).
2
The rise of the sonic speed leads to an apparent (virtual) rising of the measured temperature in humid air compared with dry air of the same temperature. The deviation of the measured virtual temperature in humid air, compared with real air temperature, can be corrected according to the following correlation, when the value of absolute humidity is given:
Tr = Tv – Tv * 0,135 K * m3 / g * H
abs
and Tr represents the real air temperature, T absolute humidity in grams H
O per m³ of air.
2
the measured acoustic-virtual temperature and H
v
2 -12 021235/10/01
O-molecules have approx.
2
the
abs
4. Technical Data
Wind Speed
Meas. range 0...65 m/s, the analogue outputs are scaled to 60 m/s ! Accuracy
± 0.1 m/s , at the range 0 ... 5 m/s resp. ± 2 % rms from meas. value , at > 5 m/s
Wind Direction
Virtual Temperature

Data output digital

Resolution 0.1 m/s Meas. range 0...360°
Accuracy
± 1.0°
Resolution 1°
Meas. range - 40 .... + 70 °C
Accuracy
± 0.5 K
Resolution 0.1 K Interface RS 485 / RS 422
Baud rate 1200, 2400, 4800, 9600, 19200 selectable Output
Instantaneous values of speed, direction and temperat.
Gliding mean values 1sec.; 10sec.; 1min.; 2min.; 10min. Output rate 1 per 100 msec up to 1 per 25.5 sec, selectable Status identification Heater status, Path disturbance, temperature deviation
path to path > 8 Kelvin
analogue
Output 0 ... 20 mA / 0 ... 10 V or 4 ... 20 mA / 2 ... 10 V
Only wind velocity and wind direction

General

Output
Load at current output max. 400
Load at voltage output min. 4000
Instantaneous values of wind speed and direction
Gliding mean values 1sec.; 10sec.; 1min.; 2min.; 10min. Update rate 1 per 100 msec Resolution 12 bit
Internal meas. rate 400 measurements per second, at 25 °C Temp. range - 40 ... + 70 °C Supply voltage electronics, 12 ... 24 V AC/DC ± 10%, max. 3 VA heater , 24 V AC/DC ± 10%, max. 70 VA Protection IP 65 Icing acc. to THIES STD 012001 Corrosion No corrosion after 3 month of salt fog and condensation EMV EN 55022 5/95 class B; EN50082-2 2/96 Model V4A Stainless steel for housing and sensor arms Mounting to a mast tube 1
½ ”, for ex. DIN 2441 Type of connection 16 pole plug connection in the shaft Weight approx. 2.5 kg
5. Plug Connection Assignment Scale Drawing
Pin-No. Function Remark 1 (A) 2 (B) 3 (C) 4 (D) 5 (E) 6 (F) 7 (G) 8 (H) 9 (I) 10 (K) 11 (L) 12 (M) 13 (N) 14 (O) 15 (P) 16 (R)
Analogue output current WV 0 / 4 – 20 mA Analogue output current WD 0 / 4 – 20 mA Analogue Ground AGND Analogue output voltage WV 0 / 2 – 10 V Analogue output voltage WD 0 / 2 – 10 V TX+ serial interface RX+ serial interface GND serial interface RX- serial interface TX- serial interface Power electronics 12 ... 24V AC/DC Power electronics 12 ... 24V AC/DC Power heater 24 V AC/DC bridged with PIN 14 Power heater 24 V AC/DC bridged with PIN 13 Power heater 24 V AC/DC bridged with PIN 16 Power heater 24 V AC/DC bridged with PIN 15
Mounting shaft for mast tu be 1½“ 40 mm dept h
3 -12 021235/10/01
Ø 70
275 200
16 pol. plug in the shaft
422
5.1 Remarks concerning Power Supply of Instrument:
The connecting cables for the heating (13 u. 14; 15 u. 16) must be bridged on the supply side in order to guarantee the complete heating power! The electronics is additionally supplied uncoupled via diodes through the heating connections 13,14, and 15,
16. If the heating voltage exceeds the supply voltage the heating voltage takes on the supply of the electronics.
6. Interface Description

6.1 Telegram forms

6.1.1 Telegram VD (STX)xx.x xxx*xx(CR)(ETX)

Z. NR. FUNCTION 1 STX (HEX 02) 2 101 Wind speed 3 100 Wind speed 4 “.” Decimal point 5 10-1 Wind speed 6 space (HEX 20) 7 102 Wind direction 8 101 Wind direction 9 100 Wind direction 10 * (HEX 2A) Check sum identifier 11 High Byte check sum in HEX 12 Low Byte check sum in HEX 13 CR (HEX 0D) Carriage return 14 ETX (HEX 03)
6.1.2 Telegram VDT (STX)xx.x xxx xxx.x x*xx(CR)(ETX)
Z. NR. FUNCTION 1 STX (HEX 02) 2 101 Wind speed 3 100 Wind speed 4 “.” (HEX 2E) Decimal point 5 10-1 Wind speed 6 Space (HEX 20) 7 102 Wind direction 8 101 Wind direction 9 100 Wind direction 10 Space (HEX 20) 11 + or - sign 12 101 Temperature 13 100 Temperature 14 “.” (HEX 2E) Decimal point 15 10-1 Temperature 16 Space (HEX 20) 17 High Byte status byte 18 Low Byte status byte 19 * (HEX 2A) Check sum identifier 20 High Byte Check sum in HEX 21 Low Byte Check sum in HEX 22 CR (HEX 0D) Carriage return 23 ETX (HEX 03)
4 -12 021235/10/01
Loading...
+ 8 hidden pages