Thermsaver White Cased Oil Boiler Installation And User Manual

Installation
&
Users Guide
OIL HEATING SOLUTIONS
White Cased Oil Boiler
1
- BOILER OPERATION 3
- SWITCHING THE BOILER ON 3
- BOILER CONTROLS 4
- SWITCHING THE BOILER OFF 5
- BURNER LOCKOUT 5
- RESTARTING AFTER LOCKOUT 5
- RESTART 6
INSTALLATION
- REGULATIONS 7
- WATER CONNECTIONS 7
- BOILER LOCATION 8
- CONVENTIONAL FLUE INSTALLATION 9
- BALANCED FLUE INSTALLATION 10-18
- CONNECTING OIL SUPPLY 18-19
- ELECTRICAL CONNECTION/WIRING DIAGRAM 20
TECHNICAL DATA
- BOILER SPECIFICATIONS 21
- COMMISSIONING INSTRUCTIONS 22
- SERVICING INSTRUCTIONS 22
- FAULT FINDING 23
- PARTS LIST 24
- BURNER SETTINGS 25
Issue No.1 1/6/04
INTRODUCTION
Thank you for choosing the THERMSAVER oil boiler, please read the following carefully.
To the installer
This manual must be left with the householder by the installer who will instruct the user on the boiler operation.
To the user
Please read the user section of this manual to familiarize yourself with the boiler operation.
WARRANTY
WARRANTY FOR YOUR BOILER MUST MEET THE FOLLOWING
CONDITIONS OR YOUR WARRANTY MAY BE INVALID
Warranty on the Heat Exchanger: 5 Years Warranty on Burner and Controls: 2 years
CONDITIONS OF WARRANTY:
1.Boiler MUST BE installed by an OFTEC registered engineer ,if not permission will be
required by building control.
2.Boiler MUST BE commissioned after installation by an OFTEC registered engineer.
3.Boiler MUST BE serviced every 12 months after installation by an OFTEC registered
engineer.
4.Installer MUST COMPLETE an Installation/Commissioning Form, which will be found
along with your manual and this must then be returned to the address on the warranty form. Failure to return this form, may invalidate your warranty.
2
USER INSTRUCTIONS
3
BOILER OPERATION
The Boiler Control Thermostat responds to the temperature of the water within the boiler and switches power to the burner when heat is required. The burner has an independent control system which regulates the firing and (shut-off) of the burner.
Automatic firing of the burner will occur when the water temperature within the boiler falls below the control thermostat set point which will continue to run until the water temperature rises to the temperature (recommended) set on the boiler control thermostat.
SWITCHING THE BOILER ON
- Check there is water in the system.
- Check radiator valves are on.
- Turn on oil supply.
- Switch electrical supply to the boiler on (including time clock ) and then set the boiler control thermostat to recommended setting.
BOILER CONTROLS
BOILER CONTROL THERMOSTAT
The temperature of the water within the boiler is controlled and maintained by the Boiler Control Thermostat located on the boiler control panel.
TEMPERATURE SETTINGS:
The Boiler Control Thermostat has a range of 50˚C to 80˚C. The recommended setting for the boiler control thermostat is:
WINTER
Heating and hot water supply 80˚C
SUMMER
Domestic hot water supply 65˚C It is not recommended to operate the boiler with a thermostat setting of less than 60˚C,
as this will precipitate corrosion, thus reducing the life of the boiler.
MAINS INDICATOR: GREEN
The mains indicator will illuminate when the mains supply to the boiler is on.
HIGH LIMIT STAT INDICATOR: ORANGE
The high limit lockout will illuminate when the water within the boiler is or has overheated e.g. reached a temperature above that set on the high limit thermostat.
This indicates that the thermostat needs to be reset.
TO RESET THE BOILER
When the boiler has had time to cool, the manual reset button (coloured red) on the control panel will need to be pressed in to reset. If the high limit thermostat continues to trip, contact your installer as there may be a fault with the central heating system.
LOCKOUT INDICATOR: RED
The lock out indicator will illuminate when the burner has failed to fire, e.g. No fuel or an electrical fault.
PLEASE NOTE: Also the reset button on the burner will illuminate on the burner control box at the same time. Reset by pressing the reset button on the burner control box.
4
Reset Button
Burner Control Box
5
SWITCHING THE BOILER OFF
The boiler can be switched off at anytime using one of the following;
- Turn the boiler control thermostat to the OFF position
- Switch the mains (electrical supply) to OFF.
- Set the control system to OFF (e.g. Time clock). PLEASE NOTE: For longer periods of shutdown e.g. While away on holiday, switch OFF the
mains (electrical supply) and turn OFF the OIL supply. If shutdown occurs during cold weather ensure boiler is protected against frost damage.
BURNER LOCKOUT
The burner has an independent control system (Burner Control Box); this includes a flame detector (Photocell) which senses the presence of a flame. In the event of flame failure, the Burner Control Box activates a second re-ignition sequence. Should the Photocell not detect a flame presence within 15 seconds the burner goes to LOCKOUT and shuts down.
Continued LOCKOUTS are a result of a fault in the operation of the boiler and can be attributed to following examples:
- An interruption of the fuel supply .
- Electrical Supply fault e.g. Extreme low voltage.
- Failure of a Burner component.
- A fault within the heating system .
- Burner combustion not being correct. The Burner Reset button on the Control Box and the red Lockout Indicator on the boiler
control panel illuminates to indicate that a lockout has occurred. In the event of the Burner locking out, do not attempt to restart the Burner by pressing the
Rest Button on the Burner Control Box for at least 2 minutes. A Bi-metallic timer within the Control Box has a minimum cooling time of 45 seconds thus the 2 minute interval will ensure that this Bi-metallic timer has cooled and is therefore in a position where it may be reset
RESTARTING AFTER LOCKOUT
When lockout has occurred, inspect for any obvious causes e.g. oil leaks. Also check the fuel line from the tank to the boiler and that any oil shut off valve has not been inadvertently closed.
6
RESTART
- Check there is adequate oil in the storage tank.
- Check oil supply valves are open.
- Switch on heating system (e.g. Time clock).
- Depress the red Burner Reset Button on the Burner Control Box, which will be illuminated. Both Burner Reset Button (illuminated) and the lockout Indicator on the Control P anel will go out and the burner will commence the ignition start sequence. After 15 seconds the Burner should fire normally.
PLEASE NOTE: Should the Burner not start, both lockout indicator, on the Control Panel and Burner Reset Button will illuminate again.
- Wait at least 3 minutes and depress the Burner Rest Button again. Failure to start a second time indicates a fault requiring attention. In the event of a second failure to start:
- Switch off electrical supply.
- Call service engineer.
Burner Reset Button
7
REGULATIONS
The installation of oil fired boilers should comply with the following standards and codes of practice.
- BS5449 Forced circulation hot water heating systems for domestic use
- BS5410-Part1 Oil installations up to 45kw.
- BS7593 Water treatment of hot water central heating systems.
- BS7671 Electrical Regulations.
- Building Regulations Part L1 and J 2002 England and Wales, Part F Scottish Regulations and Technical Booklet L Northern Ireland.
- OFTEC Codes of Practice Published or Recommended.
After installing, the system it needs to be flushed with a cleanser like Fernox Heavy Duty Restore, for fast -acting removal of lime scale , black sludge (magnetite) and other deposits from the boiler and the central heating system. Then add a Fernox protector to give long term protection of the central heating system against internal corrosion and lime scale formation.
WATER CONNECTIONS
The boiler is supplied with two flow and two return connections. Connections may be diagonal as shown on diagram below. This arrangement gives more efficient flow through the boiler, however this is not essential as parallel connection gives satisfactor y operation.
8
BOILER LOCATION
Sound levels should be discussed with the householder, as some people may be sensitive to low noise levels in a small room, as it may appear more annoying than in larger rooms. Please Note installation should take into account of flue position (see diagram).
RECOMMENDED FLUE POSITION
RefMin. Position mm
A Directly below an opening, air brick, opening window etc. 600
B Horizontally to an opening , air brick, opening window etc. 600 C Below a gutter, eaves or balcony with protection. 75 D Below a gutter or a balcony without protection. 600
EFrom vertical sanitary pipework. 600
FFrom an internal or external corner. 600 G Above ground or balcony level. 600
HFrom a surface or a boundary facing the terminal. 600
JFrom a terminal facing the terminal. 1200
KVertically from a terminal on the same wall. 1500
L Horizontally from a terminal on the same wall. 750 M Above the highest point of an intersection with the roof. 600 NFrom a vertical structure on the side of the terminal. 750 O Above a vertical structure less than 750mm. 600
PFrom a ridge terminal to a vertical structure on the roof. 1500
Please Note where the terminal is within 1 metre of any plastic material, such material should be protected from the effects of the combustion products of the fuel.
IMPORTANT 35 SECOND CLASS D GAS OIL MUST NOT BE USED FOR BALANCED FLUES.
9
CONVENTIONAL FLUE INSTALL ATION
The boiler is supplied as standard for use with conventional flue. The chimney must comply with building regulations and BS 5410. Factory made insulated chimneys are covered by BS 4543 Parts 2 & 3.
Notes on Conventional Flue
1. Liner A stainless steel flue liner of diameter to suit the boiler is recommended.
2. Flue pipe can be of vitreous enamel or stainless steel.
3. Bends Bends in the flue pipe should not be greater than 135 degrees.
4. Insulation Insulation between the flue pipe and brick chimney, is recommended to
minimize the occurrence of condensation.
5. Cowls Cowls and pots that may restrict the flue should not be used.
6. Draught Stabiliser Chimneys over 6 metres high may produce excessive draught (over
4mm w.g.). In this case a draught stabilizer may be required.
7. Length Before bends are applied, length of flue must be at least 600mm.
COMBUSTION AIR SUPPLY -CONVENTIONAL FLUE
INFORMATION SUPPLIED BY OFTEC
Conventional Flue - Typical Arrangement
550mm2/kw
1100mm2/kw
1650mm2/kw
550mm2/kw
1100mm2/kw
OPEN FLUE BOILER IN ROOM
OPEN FLUE BOILER COMPARTMENT
VENTILATED FROM OUTSIDE
OPEN FLUE BOILER COMPARTMENT
VENTILATED FROM ROOM
550mm
2
/kw
Terracotta Pot
Liner
Soot Door
Soot Door
Flue Pipe
Insulation
Bends
135˚
180 TO 450
B
C
SIDE OUTLET LEFT
180 TO 450
B
REAR OUTLET
10
BALANCED FLUE INSTALLATION
VENTILATION AIR SUPPLY
Air ventilation for balanced flue boilers is only required if the boiler is installed in a confined space e.g. a cupboard. This is to prevent over heating of components.
COMBUSTION AIR SUPPLY
25MM M IN
WALL
TERMINAL LENGTH
COMBUSTION AIR SUPPLY
BALANCED FLUE BOILERS
550mm /kW
2
550mm /kW
2
BOILER IN COMPARTMENT VENTED FROM OUTSIDE
1100mm /kW
2
1100mm /kW
2
Top view on next page
LOW LEVEL BALANCED FLUE
BALANCED FLUE BOILERS
BOILER IN COMPARTMENT
VENTED FROM ROOM
11
LOW LEVEL BALANCED FLUE
A
D
REMOVE FOIL REMOVE FLUE RING FIT SQUARE GASKET
RETAIN BOLTS FOR
FITTING FLUE
FIT SEALS AND
LUBRICATE
LOW LEVEL BALANCED FLUE SIDE AND REAR ASSEMBLY INSTALL ATION
1. Cut hole in wall. Remember measure, mark, CHECK then cut.
2. Remove Conventional Flue ring from top of boiler.
3. Fit Red inner seal and Black out Seal to flue connector and extension if required.
4. Apply lubricant included in kit. To the inner and outer seal taken care to only lubricant the lip of the seal.
MODEL Flue A B C D 50/70 3” 125 176 765 130 70/90 3” 125 176 765 130 90/115 3” 125 176 803 130 115/140 4” 150 185 917 138 140/170 4” 150 185 917 138
REMOVE CASING LID
TEST POINT
TERMINAL GUARD
A Terminal Guard must be fitted to low level Flue Terminal below 2 metres and where persons or animals could come into contact with the terminal or if it could be subject to damage.
12
5. With boiler in position pass the flue assembly through the wall and bolt the bottom section of the flue to the boiler, insuring that square gasket is in between the boiler and the flue.
6. Attached the snorkel tube with clips to the flue.
7. Make sure that flue terminal protrudes through the wall a minimum of 176mm for 80mm flue and 185mm for 100mm flue.
FLUE EXTENSION
The maximum horzontal flue level is 1450mm this can be achieved using the following extension kits:
3 x kit 3 300mm extension
OR
1 x kit 6 950mm extension
8. Remove CF adaptor from burner and discard.
9. Fit the gasket and B F adaptor and connect snorkel Tube.
N.B. Kit 8 45 degree bends must not be used on low
level balanced flue kits.
HORIZONTAL FLUE
FIT BOLTS
FIT SNORKEL TUBE
FIT CLIP
INTERNAL VIEW
13
HIGH LEVEL ROOM SEALED BALANCED FLUE DIMENSIONS
INSTALLATION OF HIGH LEVEL BALANCED FLUE
1. Position boiler and Cut Hole in wall. Remember measure, mark, CHECK then cut.
2. Remove Conventional flue ring from top of boiler.
REMOVE CASING LID REMOVE FOIL
REMOVE FLUE RING
FIT SEALS AND
LUBRICATE
BOLT BOTTOM SECTION
TO BOILER
TEST POINT
MODEL Flue A B C 50/70 3” 125 176 200 70/90 3” 125 176 200 90/115 3” 125 176 200 115/140 4” 150 185 230 140/170 4” 150 185 230
50/115 700­1100 mm
145/170 700­1100mm
14
3. Fit Red inner seal and Black outer seal to flue connectors and extensions if required.
4. Apply lubricant to the inner and outer seals. Taken care to only lubricant the lip of the seals.
5. Bolt bottom section of the flue to the boiler insuring the square gasket is fitted in between the boiler and the flue.
6. Attached snorkel to the flue with the clip.
7. Refit boiler top panel insure the knock out in the panel has been removed.
8. Assemble second vertical flue section and any vertical extension.
9. Assemble horizontal section and pass through the wall. Making sure that the terminal protudes through the wall a minimum of 176mm for 80mm flue and 185mm for 100mm flue.
10. Connect vertical and horizontal section together.
11. Secure vertical section with the screws provided.
12. Seal around the flue terminal in wall using mastic.
13. Remove CF adaptor from burner and discard.
14. Fit BF adaptor connect snorkeltube with clip.
NOTE: Expanding foam can be used to fill/insulate the gap between flue parts and wall.
FLUE EXTENSIONS
Please note a maximum of one kit 6
950mm or 3 x kit 3 300mm extension can be used on the high level.
Kit 8 45 degree bends must not be used on high level balanced flue kits.
FIT SNORKEL TUBE
FIT HORIZONTAL SECTION
FIT CLIP
FIT LID
INTERNAL VIEW
15
VERTICAL BALANCED FLUE
2.4
METRE
MINIMUM 600MM
VERTICAL BALANCED FLUE DIMENSIONS
50/70 70/90 90/115
125MM
FLASHING NOT SUPPLIED
115/140
150MM
140/170
The vertical flue is telescopic as supplied. The flue has a range of 1020-2400mm
from the top of the boiler to the flashing. Extension kits of 300 and 950mm
are available. The maximum vertical length is 4800mm. Also available are 45 degree bends. For further information contact our sales office. N.B. Every 45 degree elbow is equivalent to
500mm of flue.
16
INSTALLATION OF VERTICAL FLUE
1. Position boiler and cut hole/s in ceiling and roof. Remember measure mark ,CHECK then cut.
2. Remove conventional flue ring from top of boiler.
3. Fit Red inner seal and Black outer seal to flue connectors and extensions if required.
4. Apply lubricant to the inner and the outer seals. Taking care to only lubricant the lip of the seals.
5. Bolt bottom section of the flue to the boiler insuring the square gasket is fitted in between the boiler and the flue.
6. Attached snorkel to the flue with the clip.
7. Refit boiler top panel insure the knock out in the panel has been removed.
8. Assemble second vertical flue section and any vertical extension.
9. Fit the roof flashing and flue terminal.
10. Secure the terminal to a roof joist with clamps provided.
11. Fit flue elbows if required and secure vertical section with the screws provided
12. Seal around the flue terminal in wall using mastic
13. Remove CF adaptor from burner and discard
14. Fit BF adaptor connect snorkel tube with clip. NOTE: Expanding foam can be used to
fill/insulate the gap between flue parts and wall.
Remove lid
Remove flue ring
Bolt bottom section
Fit Clip
Fit Snorkel Tube
Vertical Terminal
Internal View
Fit seals and
lubricant
Remove lid
FITTING OF BF ADAPTOR
Disconnect Burner Plug
Fit B F Adaptor
Fit B F Adaptor Gasket
Peel backing sticky
from B F adaptor
Gasket
Remove C F Adaptor
Tighten bolt on burner Fit snorkel tube
Internal view
Loosen Bolt
Remove Burner
17
FLUE KIT DESCRIPTION AND PART NUMBERS
DESCRIPTION PART NUMBER
50-115,000BTU 115.000-170,000BTU
1. LOW LEVEL BALANCED FLUE STANDARD KIT1-80mm KIT1-100mm WALL THICKNESS FROM 150-450mm
2. LOW LEVEL BALANCED FLUE EXTENDED KIT2-80mm KIT2-100mm WALL THICKNESS FROM 260-600mm
3. 300mm FLUE EXTENSION KIT3-80mm KIT3-100mm
4. HIGH LEVEL HORIZONTAL FLUE KIT4-80mm KIT4-100mm
5. VERTICAL FLUE KIT5-80mm KIT5-100mm
6. 950 MM FLUE EXTENSION KIT6-80mm KIT6-100mm
7. 45 DEGREE BENDS KIT8-80mm KIT8-100mm
N.B. Kit 8 (45 degree bends) must only be used on kit 5 vertical flue kits.
OIL FULL LEVEL
OIL LOWEST LEVEL
VENT
FILL
SIGHT GAUGE
OIL TANK
Plastic tank shown Steel tank also suitable
FIRE VALVE
ALTERNATIVE FILTER POSITION
VALVE
PAPER ELEMENT FILTER
BURNER
BOILER
BEST POSITION FOR FIRE VALVE SENSOR
REMOTE FIRE VALVE MUST BE OUTSIDE THE BUILDING
TYPICAL SYSTEM SHOWN
Single Pipe Oil System
OIL SUPPLY
18
OIL SUPPLY
Diagrams of twin pipe oil supply systems
BOILER
FIRE VALVE SENSOR
ALTERNATIVE FILTER POSITION
FIRE VALV E
FILL
VENT
SAW CUT INSIDE TANK TO PREVENT SYPHON
OIL TANK Plastic tank shown steel tank also suitable
BURNER
PAPER ELEMENT FILTER
VALV E
PAPER ELEMENT FILTER
BOILER
FIRE VALVE SENSOR
TIGER LOOP MUST BE
1.UPRIGHT
2.OUTSIDE RESIDENCE Can be above or below burner
VALV E
FILL
VENT
OIL FULL LEVEL
OIL LOWEST LEVEL
OIL LEVEL FULL
OIL LOWEST LEVEL
FIRE VALVE
OIL TANK Plastic tank shown steel tank also suitable
A flexible oil pipe is supplied to connect the burner to the incoming oil supply pipe.
IMPORTANT NOTES
- If siting oil tank above burner height, use single supply pipe only.
- If siting oil tank below burner height, use twin pipe supply or Tiger loop.
19
ELECTRICAL ENTRY
The electrical supply to the boiler must be wired using a double pole-isolating switch 240v/50hz, fused 5 amp. A multi 3 pin plug is included with the boiler , which connects with the boiler control panel. The burner is supplied with a 4 wire cable plug which allows disconnection for maintenance.
1 2 3 4 5 6 7 8
MAINS SOCKET
CHASSIS EARTH
MAINS
LIMIT
LOCKOUT
BURNER PLUG
BLK
L
N/O
N
E
YG
BLK
BR
R
YG
YG
BLK
BLK
CONTROL STAT
LIMIT STAT
NEON INDICATORS
Wiring Diagram
IMPORTANT ELECTRICAL SUPPLY SHOULD BE FUSED 5 AMP
N
E
L
RED
ORG
GRN
20
General Data
Electrical Supply: 240v ~50Hz Oil Supply Connection 1⁄4” BSP Fuel: 28 second or 35 Second High Limit Stat: Manual Reset Maximum Control Thermostat Setting 85˚C Maximum Operating Pressure: 3 bar- 45psi - 28m static head room 92ft Draught Limit: Min 12.5 Nm
2
- 0.05” WG
Max 33.0 Nm
2
- 0.12” WG
BOILER SPECIFICATIONS
BOILER OUTPUT IN BTU 50/70 70/90 90/115 115/140 140/170 170/220 Amm 857 857 896 1025 1025 1025
Bmm 590 590 630 671 671 721 Cmm 420 420 450 490 490 539 Dmm 140 140 140 140 140 140 Emm 93 93 93939393 Fmm 575 575 615 715 715 775 Gmm 45 45 45454545 Hbsp 4x1 4x1 4x1 4x1
1
4 4x11⁄4 4 x 11⁄4 Jmm 100-125 100-125 100-125 125 152 152 Boiler Weight in (Kg) 100.5 106.25 140 147 160 180 Water Content 20Ltr 21.5Ltr 30Ltr 31.5Ltr 31.5Ltr 42Ltr
CONVENTIONAL FLUE SOCKET
G
D
B
J
H
A
C
F
E
H
21
COMMISSIONING INSTRUCTIONS
A competent service engineer OFTEC registered should be appointed on an annual basis.
- Insure heating system has been flushed and treated with inhibitor.
-Remove inspection door and check baffle arrangement.
-Remove Burner and check electrode settings and also check settings between face
of nozzle to diffuser plate. Please refer to Burner technical manual for correct settings.
-Fit manifold pressure gauge to the gauge port of the burner.
-Turn electrical supply, to the boiler, to ON.
- Set the central heating controls so they are calling for heat. .
- Set the boiler control thermostat to 80˚C.
-Purge air from the oil supply system .
- Set burner pump pressure.
- Allow time for the boiler to reach normal operating temperature.
-Check the smoke reading.
- Measure the Co
2
.
- Measure net flue gas temperature
Please Note:
Reducing the air supply into the burner air inlet shutter, decreases the flue gas temperature and increases the Co
2
.
SERVICING INSTRUCTIONS
A competent service engineer OFTEC registered should be appointed on an annual basis.
- Remove inspection door, burner and baffle assembly.
- Brush down the inside of the heat exchanger and vacuum out debris .
- Clean baffle assembly.
- Inspect and clean burner assembly, and replace with new nozzle (see burner manual)
- Renew any insulation e.g. inspection door or inside base of heat exchanger
- Reassemble baffles and replace inspection door.
-Replace paper oil filters
-Test oil pressure and test combustion.
22
BOILER WILL NOT START
Check if mains electricity supply is reaching boiler control panel, making sure control thermostat is turned on and time clock is calling for heat.
23
PARTS LIST
ITEM DESCRIPTION
1 Control Thermostat
2 Green Neon
Orange Neon
Red Neon 3High Limit Thermostat 4 Door Insulation Kit
50/70 Baffle
70/90 Baffle
90/115 Baffles
115/140 Baffles
140/170 Baffles
170/220 Baffles 5 Burners
Sterling 40
Sterling 50
Ecoflam Minor 4
Ecoflam Minor 8
Ecoflam Minor 12
ITEM DESCRIPTION
1Reset Button 2 Control Box 3 Ignition Transformer 4Ignition Cables 5 Nozzle Assembly 6 Nozzle 7 Brake Plate 8 Blast Tube ST40
Blast Tube ST50
9 Ignition Electrodes 10 Connecting Pipe 11 Air Damper 12 Solenoid Valve 13 Pump 14 Drive Coupling 15 Indication Air Damper 16 Fan Wheel ST40
Fan Wheel ST50 17 Adjustment, Air Damper 18 Photo Resistor 19 Motor
4
3
2
1
5
FOR PART NUMBERS ON ECOFLAM GO TO BURNER MANUAL
24
BURNER SETTINGS
KEROSENE CLA SS ‘C ’ FUEL 28 SEC
BOILER MODEL 50/70 70/90 90/115 115/140 140/170 170/220
BURNER STERLING 40 STERLING 50 MINOR 4 MINOR 8 MINOR12
OUTPUT Btu/h x 100 50 60 70 70 80 90 90 105 115 115 130 140 140 160 170 170 190 220
OUTPUT Kw 14.65 17.6 20.5 20.5 23.5 26.4 26.4 30.8 33.7 33.7 38.1 41.0 41.8 4.60 49.4 49.4 55.7 65.5
NOZZLE SIZE US/GPH 0.50 0.55 0.55 0.60 0.65 0.65 0.85 0.85 0.85 1.1 1.1 1.1 1.25 1.35 1.35 1.35 1.50 1.75
& TYPE 80. S 80 S 80 S 80 S 80 S 80 S 80 S 80 S 80 S 80 H 80 H 80 H 80 H 80 H 80 H 80 H 80 H 80 H
OIL PRESSURE BAR 7.5 8.0 9.5 9.0 9.5 10 8.0 8.5 9.0 7.5 9.5 11.0 9.0 9.0 10.0 10.0 9.5 8.0
FIRING RATE Kg/hr 1.35 1.63 1.95 1.98 216 2.44 2.6 2.84 3.2 3.21 3.52 3.8 3.7 4.3 4.6 4.6 5.1 5.9
AIR SETTING
SCALE No. 4.5 7.5 10.5 7.0 10.5 14 7.0 10.0 13 3 4 6.5 3 5 7 3 4 7
(approx)
SMOKE Bacharach
000000000000000000
Scale
Co
2
%121112.5 12 12 12.5 12 12 12.5 12 12.5 12.5 11.5 11.5 11.5 11.5 11.5 11.5
FLUE GAS TEMP. Minimum Temperature 160˚C Maximum Temperature 260˚C
These figures are a guide only. Site conditions determine oil pressure and air settings required for best combustion test results.
Please Note - More air may be required for balanced flue room sealed models.
25
THERMSAVER
1, Croftsbank Crescent, Uddington, Glasgow G71 7JD
Telephone: 01698 327997
Fax: 01698 327776
P
rin
te
d
b
y
N
S
P
rin
t 0
19
3
9
2
3
2
7
9
6
Copyright of the contents of this manual is secured by Turkington Engineering Limited and neither the manual nor any part may be reproduced without permission.
Turkington Engineering Limited have a continuing research and development programme which occasionally necessitates changes to specifications herein. It is, therefore essential that instructions issued with each individual appliance are carefully read prior to installation and strictly adhered to during installation.
The statutory rights of the customer are not affected.
L
Part
Compliant
Loading...