Thermo Technologies USDT 2005 User Manual

Revision
3
Note:
The information supplied in this manual is for guidance only
-
no part of this may be
THERMO TECHNOLOGIES
USDT 2005 Analog Differential Controller
used for any agreement, whether express or implied, or to form any contract. Thermo Technologies reserves the right to change specifications without prior notice.
The control unit has the following functions:
2 inputs for temperature sensors
Suitable for sensors of type Thermistor and PT1000
Adjustable (70 o F to 210 o F) overheating protection
Adjustable (4
Manual override of pump for system testing
Symbolic display of all parameters
Indications of current state of pump
System status and diagnostic displays
Collector sensor surge protection
o
F to 24 o F) temperatu re difference delta T
Thermo Technologies
5560 Sterrett Place • Suite 115
Columbia, Maryland 21044
Phone 410.997.0778 • Fax 410.997.0779
e-Mail info@thermotechs.com
May, 2005
Installation and User’s Guide
1
S2 A1
A1 S1
Introduction
he USDT 2005 unit is an analog temperature differential controller. It can be used in a wide range of applications. At the factory, it is set to control a simple solar water heating
system.
Solar System Control (S) Mode
In this program mode, it ensures that the collected energy from the sun is transferred efficiently, and harnessed under optimum conditions. It monitors the collector temperature (TKS) and the return temperature (TBS, bottom of the storage tank). The solar loop circulation pump runs while the collector temperature exceeds the return temperature by an adjustable temperature difference ?T. To avoid overheating, the circulation pump stops if the return temperature (TBS) reaches the adjustable high limit (T temperature. The temperature hysteresis (a lagging in the set-point) may over -ride ?T to avoid pump cycling.
The pump A1 runs only when the temperature at the collector sensor location S1 is higher than the return temperature at location S2 by at least ?T. The pump stops if ?T is less than the preset value or, the if the temperature at location S2 (storage tank) has reached the T
MAX
Boiler Control (L) Mode
The User can switch USDT 2005 to operate a boiler circulator. In boiler mode (L), the pump runs only when boiler temperature at S1 location is higher than the minimum set point dialer and the ?T condition is satisfied.
A1 (ON) only when S1 > max &
S1 > (S2 + diff)
Note: The maximum temperature dialer (max) serves as the minimum starting temperature, T must change the switch position on the back of the circuit board to use the USDT 2005 as a boiler controller. Details will follow.
MAX set point protects the solar system from overheating. It turns off the circulator if the boiler contribution to the storage tank is not satisfied.
in the boiler mode. User
MIN
)
MAX
A1 (ON) only when S1 > (S2 + diff) & S2 < max
S1
S2