Chimney cleaning especially in the exit points of the boiler and at curves where the
gases change their way.
Chimney insulation is compulsory.
An untight chimney can produce many problems to the boiler, for example:
blocking, a lot of soot, noise, bad functioning of the burner, etc. In addition, a great problem is
creating of a drift and turbions that may prevent the easy exit of the burnt gases.
The chimney must be higher above the building.
The burning residue should not influence the material, from which the chimney is
made.
For all the above reasons a regular checking of the chimney is compulsory especially at the
beginning of the winter season.
ATENTION:
A very small diameter of chimney gets charged and obturated very quickly. A very big
diameter chimney gets cold and produces condensation of the burnt gases. So the chimney
must not be too small or too big.
At the roofs with a steep of up to 20%, the height of the chimney towards the roof, measured
must be of minimum 1000 mm.
In case of some elements that are higher than the roof surface (attics, fireproof walls) the
chimney must overcome that height with at least 1000 mm, except the chimneys placed at a
distance smaller than 3000 mm of these elements, in this case the difference may be reduced
to 500 mm.
At the roofs with a steep >20%, the height of the chimney depends of the material and the
position of the chimney towards the ridge, so:
-chimneys placed until a distance of 1500 mm from the ridge must surpass the ridge with 500
mm for incombustible covering and with 1000 mm for flammable coverings.
-the chimney placed at greater distance must have the evacuation opening at a height of at
least 1000 mm from the covering and to overpass the plan that goes through the ridge and
has an inclination of 100 towards the horizontal.
Causes of defective function of the boilers with solid fuels:
1) Small Active height of the chimney
2) Untight masonry of the chimney
3) Too narrow masonry of the chimney
4) Obturation or narrowing of the chimney section
5) Untight diaphragm
6) Wrongly set draught limitator
7) Smoke opening in the chimney
8) Untight joints at the smoke opening
9) Untight chimney Cleaning door
10) A big part of the smoke opening without insulation, too little inclination
11) Untight joints (flanges), defective insulation
12) Reduced draught because of soot layers on the smoke tubes
13) Soot layers
14) Untight doors and covers