THERMOSTAHL BIOPLEX MCL-BIO Installation And Service Manual

Page 1
BIOMASS-SOLID FUEL RETORT BOILER
BIOPLEX MCL-BIO
INSTALLATION AND SERVICE MANUAL
2.1
UPDATE:
10.10.2013
Page 2
Contents
1. GENERAL INFORMATION ................................................................................................. 3
1.1. Proper use of the appliance .............................................................................................. 3
1.2. Safety warnings .............................................................................................................. 3
1.3. Data label ...................................................................................................................... 3
1.4. Document information ..................................................................................................... 3
2. TECHNICAL FEATURES AND DIMENSIONS ....................................................................... 4
2.1. Technical features ........................................................................................................... 4
2.2. Function principle ............................................................................................................ 5
2.2.1. Boiler ...................................................................................................................... 5
2.2.2. Furnace ................................................................................................................... 5
2.3. Dimensions .................................................................................................................... 6
2.4. Fuel ............................................................................................................................... 8
3. BOILER MOUNTING ......................................................................................................... 9
3.1. Transportation and delivery .............................................................................................. 9
3.2. Boiler room .................................................................................................................. 10
3.2.1. General requirements ............................................................................................. 10
3.2.2. Boiler room dimensions ........................................................................................... 10
3.3. Chimney ...................................................................................................................... 11
4. INSTALLATION .............................................................................................................. 13
4.1. Hydraulic connections .................................................................................................... 13
4.2. Safety features ............................................................................................................. 13
4.3. Overheating serpentine .................................................................................................. 14
4.4. Return temperature protection ........................................................................................ 14
4.5. Filling the system .......................................................................................................... 15
4.6. Automatic ignition system .............................................................................................. 15
4.7. Connection diagrams ..................................................................................................... 16
4.7.1. Open expansion vessel connection ............................................................................ 16
4.7.2. Closed expansion vessel connection .......................................................................... 17
5. ELECTRICAL CONNECTIONS ........................................................................................... 18
5.1. General instructions ...................................................................................................... 18
5.2. Control panel functions .................................................................................................. 18
5.3. Wiring diagram ............................................................................................................. 19
6. BOILER START-UP ......................................................................................................... 20
6.1. Initial lighting checks ..................................................................................................... 20
6.2. Start-up ....................................................................................................................... 20
6.3. Checks to carry after initial start-up ................................................................................ 20
6.4. Fuel loading .................................................................................................................. 21
6.5. Combustion regulation ................................................................................................... 21
6.6. Chimney damper adjustment .......................................................................................... 22
7. SERVICE AND MAINTENANCE ........................................................................................ 23
7.1. Cleaning ...................................................................................................................... 23
7.1.1. Cleaning the boiler ................................................................................................. 23
7.1.2. Cleaning the chimney box ....................................................................................... 24
7.1.3. Cleaning the furnace ............................................................................................... 24
7.2. Maintenance intervals .................................................................................................... 24
7.2.1. Daily maintenance .................................................................................................. 24
7.2.2. Weekly maintenance ............................................................................................... 24
7.2.3. Monthly maintenance .............................................................................................. 24
7.3. Basic service procedures ................................................................................................ 25
7.3.1. Service after overheating ........................................................................................ 25
7.3.2. Service after feeder blockage ................................................................................... 25
7.3.3. Service after motor bolt breakage ............................................................................ 27
7.3.4. Service after power blackout .................................................................................... 27
7.3.5. Replacement of the ignition element ......................................................................... 27
7.4. Maintenance after long stop ........................................................................................... 28
7.4.1. Maintenance of the boiler ........................................................................................ 28
7.4.2. Maintenance of the furnace ...................................................................................... 29
8. TROUBLESHOOTING ...................................................................................................... 30
9. WARRANTY .................................................................................................................... 31
Page 3
GENERAL INFORMATION
3
1. GENERAL INFORMATION
1.1. Proper use of the appliance
Before you make use of this appliance make sure you have read and fully understood the instructions included in this manual.
The installation and use of the appliance must be performed according to the instructions indicated in this manual in combination with the current national safety regulations.
The appliance is designed for use in pumped hot water central heating systems. Any other use is considered improper and is prohibited. THERMOSTAHL declines any responsibility for
damages or injuries caused by improper use; in this case the risk is completely at the user’s
responsibility.
To ensure an efficient and flawless function of the appliance, it is strongly recommended that you have performed an annual service by a qualified technician.
1.2. Safety warnings
All installation and maintenance procedures must be carried out by professional and authorized personnel, in compliance with the indications in the present manual and national regulations. Any failure to correctly install this appliance could cause damage or injuries!
Do not make modifications to parts of the appliance, unless you have contacted the company and an authorized service contractor.
Only original accessories and spare parts must be used to ensure correct and safe function.
Make sure you respect the cleaning and maintenance procedures on the corresponding intervals. Failure to do so can cause malfunction to the appliance and possible damages.
The boiler is design to function on the fuels indicated in the corresponding paragraph. Any other fuel is prohibited. Do not use explosive or flammable substances! Do not store such substances inside the boiler room.
The working pressure varies according to the model. Make sure you use the appropriate water pressure. Working in a pressure higher than the one indicated in this manual is
strictly prohibited and dangerous!
1.3. Data label
The data label of the appliance is placed on the boiler’s side cover, on the external part. Make sure that it is properly placed and readable.
On the label it is indicated the serial number and the manufacturing year of the appliance.
1.4. Document information
This document is an integral and indispensable part of the product and must be retained in good condition by the user. Keep it in a safe place for future reference.
If the appliance is sold or transferred to another person, this manual has to always follow the appliance and handed to the new user or installer.
Page 4
TECHNICAL FEATURES AND DIMENSIONS
4
2. TECHNICAL FEATURES AND DIMENSIONS
2.1. Technical features
BIOPLEX boiler is a steel solid fuel boiler, with cylindrical heat exchanger consisted of fire tubes. The furnace system BIOFIRE made of steel plates. The furnace plate and grates that come in contact with fire are made of special refractory cast iron.
The boiler body is made of cold rolled steel St 37.2 STAS 500/2-80~S235 JR SR EN 10025/90 according to DIN 17100. The boiler is designed so that all the parts in contact with exhaust gases are water cooled. The boiler body parts are assembled by welding. Weldings are performed according to standards 288-1 and 288-3 according to DIN 50120, 50121-50145, SR EN 1011.1/2001, by means of electric arc welding (MIG-MAG).
DESCIPTION OF BOILER COMPONENTS
Steel boiler body with cylindrical heat exchanger Removable rear smoke box with inspection cleaning door Upper door for cleaning the heat exchanger Middle door for ignition and fuel loading, equipped with an inspection flange, which can also
be used for a burner mounting
Lower door for ash removal Ash box positioned on the lower part of the fire chamber Cast iron catalyst positioned above the furnace Rockwool body insulation of 50 mm thickness Electrostatically painted external covers Control panel for electromechanical operation Safety heat exchanger (optional)
DESCIPTION OF FURNACE COMPONENTS
Steel furnace body Feeding auger welded to solid axis Combustion air fan Feeding motoreducer Transmission system with chain wheels Transmission system protection cover Cast iron combustion plate Cast iron grates for manual wood feeding Ignition element (optional) Fuel silo with protection frame and shuttering lid
Page 5
TECHNICAL FEATURES AND DIMENSIONS
5
2.2. Function principle
2.2.1. Boiler
The function of the BIOPLEX boiler is based on natural gas evacuation through the chimney. The fuel is positioned on the grate. The combustion takes place in the fire chamber. During the combustion the flame comes in contact with the side walls of the fire chamber, which are surrounded by water. The fire chamber is of big volume in order to receive big dimension logs and to ensure a long autonomy.
The combustion air is supplied by the fan and distributed through an air distributor, positioned below the fuel grate. The combustion is regulated through the fan, controlled by the control panel.
Fig 1. Boiler function
The exhaust gases are guided through the heat exchanger to the smoke box, and afterwards evacuated to the chimney. The smoke box is equipped with an inspection and cleaning door, which also actions as an explosion relief.
The doors have an insulation cord to ensure air-tight closing. Each door is equipped with a screwed handle, which must always be well tightened during the combustion. The flange on the middle door has a rotating clamp, for secondary air adjustment and flame inspection. If necessary, this flange can be removed, and a burner can be placed in its position.
2.2.2. Furnace
The BIOPLEX boiler is equipped with the innovative biomass furnace BIOFIRE. The system is consisted of two axes (BI-AX): The lower axis is the main one, feeding fuel to the furnace, while the upper is the secondary, transporting the fuel from the silo to the main axis. Between the two axes there is a safety DROPBOX device. This device has a metal flap that automatically closes with a spring when the feeding stops. This way the danger of blockage and backfire is eliminated. The motoreducer is mounted on the lower axis, and the transmission is realized through chain wheels. A metal protection cover is places around the transmission system.
The combustion air is supplied by the fan mounted on the furnace. In case the optional ignition system is installed, there is a 500W ignition element mounted in the air pipe, close to the furnace plate.
Legend
1
Silo flange
2
Fuel box
3
Upper feeding axis
4
Transmission chain
5
Motor
6
Reducer
7
Support leg
8
Fan
9
Boiler flange
10
Lowe feeding axis
11
Mixing chamber
12
Fuel DROPBOX
13
Cast iron plate
14
Lower feeding axis
Page 6
TECHNICAL FEATURES AND DIMENSIONS
6
2.3. Dimensions
DIMENSIONS
Type
Feeding
door
A
A1
A2 B H
H1 E C
T3
T1-
T2
T5
T6
mm
mm
mm
inch
MCL-BIO 20
350x480
630
670
1470
560
1280
1380
960
860
195
1½
1”
¾”
MCL-BIO 28
350x480
630
670
1470
660
1280
1380
960
960
195
1½
1”
¾”
MCL-BIO 36
350x480
630
670
1470
760
1280
1380
960
1060
195
1½
1”
¾”
MCL-BIO 45
350x480
630
670
1470
860
1280
1380
960
1160
195
1½
1”
¾”
MCL-BIO 53
350x480
630
670
1470
960
1280
1380
960
1260
245
2”
1”
¾”
MCL-BIO 60
350x480
630
670
1470
1060
1280
1380
960
1360
245
2”
1”
¾”
MCL-BIO 70
600x360
910
810
1700
860
1600
1720
1240
1280
245
2”
1 ¼”
¾”
MCL-BIO 80
600x360
910
810
1700
980
1600
1720
1240
1380
245
2”
1 ¼”
¾”
MCL-BIO 90
600x360
910
810
1700
1100
1600
1720
1240
1480
245
2”
1 ¼”
¾”
MCL-BIO 100
600x360
910
810
1700
1200
1600
1720
1240
1580
295
2 ½”
1 ¼”
¾”
MCL-BIO 120
600x360
910
810
1700
1330
1600
1720
1240
1680
295
2 ½”
1 ½”
¾”
MCL-BIO 140
600x360
910
810
1700
1580
1600
1720
1240
1750
295
2 ½”
1 ½”
¾”
MCL-BIO 160
600x360
910
810
1700
1830
1600
1720
1240
2000
295
2 ½”
1 ½”
¾”
MCL-BIO 180
600x360
910
810
1700
1830
1600
1720
1240
2300
295
2 ½”
1 ½”
¾”
MCL-BIO 200
500x810
1100
1000
2050
1350
2000
2160
1500
1950
345
3”
2”
2x¾”
MCL-BIO 250
500x810
1100
1000
2050
1600
2000
2160
1500
2200
345
3”
2”
2x¾”
MCL-BIO 300
500x810
1100
1000
2050
1850
2000
2160
1500
2450
395
4”
2”
2x¾”
MCL-BIO 350
500x810
1100
1000
2050
1850
2000
2160
1500
2450
395
4”
2 ½”
2x¾”
MCL-BIO 400
500x810
1100
1000
2050
2100
2000
2160
1500
2650
395
4”
2 ½”
2x¾”
MCL-BIO 450
500x810
1100
1000
2050
2100
2000
2160
1500
2650
395
4”
2 ½”
2x¾”
MCL-BIO 500
1230x520
1540
1440
2400
1600
2400
2650
1750
2300
445
5”
2 ½”
2x¾”
MCL-BIO 550
1230x520
1540
1440
2400
1600
2400
2650
1750
2300
445
5”
2 ½”
2x¾”
MCL-BIO 600
1230x520
1540
1440
2400
1800
2400
2650
1750
25700
445
5”
2 ½”
2x¾”
MCL-BIO 650
1230x520
1540
1440
2400
1800
2400
2650
1750
25700
445
5”
2 ½”
2x¾”
MCL-BIO 700
1230x520
1540
1440
2400
2150
2400
2650
1750
2820
495
6”
2 ½”
2x¾”
MCL-BIO 800
1230x520
1540
1440
2400
2400
2400
2650
1750
3070
495
6”
3”
2x¾”
MCL-BIO 900
1230x520
1640
1540
2400
2600
2870
2650
1750
3350
495
6”
3”
2x¾”
Page 7
TECHNICAL FEATURES AND DIMENSIONS
7
*Nominal output is obtained with good quality wood pellet.
**Pellet consumption is calculated as average, based on pellet with calorific power 4.800 kcal/kg and external temperature 0oC.
FURNACE TECHNICAL DATA
Furnace type
BIOFIRE I
BIOFIRE II
BIOFIRE III
BIOFIRE IV
Boiler range
MCL-BIO 20-60
MCL-BIO 70-90
MCL-BIO 100-200
MCL-BIO 250-500
MCL-BIO 550-900
Fan
Type RV-12RK
RV-06
RV-05
RV-25 RK
RV-21 RK
Power W 80
80
85
230
250
Air debit
m3/h
240
350
400
580
900
Pressure
Pa
310
300
300
520
550
Voltage
V/Hz
230/50
230/50
230/50
230/50
Noise level
dB
<60
<60
<60
<60
Protection
IP 20
IP 20
IP 20
IP 20
Motor
Type
EWM 30-50/300
EWM 30-50/300
MAF 071 AR2-0
MAF 071 AR2-0
Power W 180
180
370
370
Voltage
V/Hz
230/50
230/50
380/50
380/50
Protection
IP 54
IP 54
IP 54
IP 54
Silo volume
lit
370
600
950
1.500
Weight
kg
200
250
320
450
BOILER TECHNICAL DATA
Boiler type
Nominal Output*
P
max
Fire
chamber
length
Pellet
consumption**
Max.
wood
length
Silo
volume
Weight
kcal/h
kW
bar
mm
kg/h
mm
lit
kg
MCL-BIO 20
20.000
23 3 450
2,0-3,0
400
370
380
MCL-BIO 28
28.000
32 3 550
3,0-4,0
500
370
420
MCL-BIO 36
36.000
41 3 650
4,0-5,0
600
370
460
MCL-BIO 45
45.000
52 3 750
5,0-6,5
700
370
500
MCL-BIO 53
53.000
61 3 850
6,0-7,0
800
370
550
MCL-BIO 60
60.000
69 3 950
7,0-8,5
900
370
600
MCL-BIO 70
70.000
81 3 700
7,5-9,5
650
600
750
MCL-BIO 80
80.000
93 3 820
7,5-9,5
750
600
880
MCL-BIO 90
90.000
104 3 920
8,5-10,0
850
600
930
MCL-BIO 100
100.000
116 3 1080
10,0-11,8
950
600
1000
MCL-BIO 120
120.000
139 3 1200
11,5-14,0
1100
600
1070
MCL-BIO 140
140.000
162 3 1450
12,5-16,0
1350
600
1220
MCL-BIO 160
160.000
186 3 1650
14,0-19,0
1550
600
1470
MCL-BIO 180
180.000
209 3 1650
14,0-19,0
1550
600
1680
MCL-BIO 200
200.000
232 3 1200
20,0-28,0
1100
950
1790
MCL-BIO 250
250.000
291 3 1450
24,0-33,0
1350
950
2010
MCL-BIO 300
300.000
348 3 1700
28,0-39,0
1600
950
2230
MCL-BIO 350
350.000
406 3 1700
33,0-45,0
1600
950
2230
MCL-BIO 400
400.000
464 3 1950
38,0-50,0
1850
950
2750
MCL-BIO 450
450.000
522 3 1950
43,0-55,0
1850
950
2980
MCL-BIO 500
500.000
580 3 1450
85,0-110,0
1350
2000
3500
MCL-BIO 550
550.000
638 3 1450
85,0-110,0
1350
2000
3800
MCL-BIO 600
600.000
696 3 1700
110,0-140,0
1600
2000
4200
MCL-BIO 650
650.000
754 3 1700
110,0-140,0
1600
2000
4700
MCL-BIO 700
700.000
812 3 1935
130,0-165,0
1800
3000
5200
MCL-BIO 800
800.000
928 3 2000
145,0-180,0
1900
3000
5650
MCL-BIO 900
900.000
1.044 3 2300
160,0-210,0
2200
3000
6150
Page 8
TECHNICAL FEATURES AND DIMENSIONS
8
2.4. Fuel
The BIOPLEX series is designed for automatic function with solid fuel of biogenic or fossil nature, with granulation up to 30 mm and humidity up to 20%. The boiler is also able to be used on wood or other solid fuels with manual feeding, without any modification.
This means different types of biomass fuels, such as pellet, agropellet, olive husks, fruit kernels, cereals, granulated carbon. When the fuel used has characteristics that significantly vary from nominal (i.e. carbon, cereals, agricultural residues), it is recommended that they are used in combination with pellet or agropellet at a 50:50 ratio. If you want to use solely carbon as fuel, please contact the manufacturer.
The fuel with the best quality, concidering calorific power, ash content, humidity and standartization, is wood pellet. The less quality of the fuel, the more fuel supply must be provided to achieve the nominal power and of course the most the consumption and the ash remains.
The nominal characteristics of the boiler are calculated for use on wood pellet!
Fuel type
Calorific
power
Max
diameter
Max
humidity
Ash
content
kWh/kg
mm
%
%
Pellet
4,8
6 – 8
<10
<1
Agropellet
4 – 4,2
6 – 10
<10
<5
Coal
5,3 – 6,5
3 – 25
<15
4 – 8
Lignite
1,6 – 3,8
3 – 25
<20
<10
Cereals (oat)
4,2
3 – 6
10 – 13
0,6
Wood chips
4,3
5 – 25
<20
4 - 6
Barks
2,6
5 – 25
<20
8 - 10
Wood
4 – 4,3
-
<20
4 - 8
Wood briquette
5,2
-
<10
<4
Table 1. Characteristics of different types of fuels
Every type of biomass fuel contains a significant amount of humidity, which highly affects its combustion behaviour and calorific value. Boiler output, efficiency and autonomy will significantly diminish as the humidity increases. The nominal data presented in this manual are calculated for humidity content 10%. Maximum allowable humidity content is 20%. If the fuel has bigger humidity, the combustion will be highly imperfect, causing problems to the furnace and the feeder.
For proper and efficient function and a long lifespan, it is strictly recommended that only dry wood is used, with a humidity content of 20%. Practically, this means at least one year dry wood.
In order for the feeding and combustion system to function properly the
maximum allowed humidity of the fuel is 20%!
It is prohibited the use of explosive, inflammable materials, plastic, domestic
residues, etc.
The boiler is provided with a flange for mounting a burner for use with oil or gas as an alternative fuel. However, this option is an emergency alternative, and it is not recommended that boiler is on stable function on oil or gas. The efficiency will be very low on such fuels.
If a burner is mounted, remove it before you use solid fuel again.
It is prohibited to manually feed solid fuel in the boiler simultaneously with the
burner function!
Page 9
BOILER MOUNTING
9
3. BOILER MOUNTING
3.1. Transportation and delivery
The boiler is delivered on wood pallet, well positioned with metal plates. Remove them carefully by unscrewinf the screws holding them in place.
The loading and unloading of the boiler must be performed with a forklift or a crane. A special hook is provided on the upper part of the boiler for lifting.
The boiler is very heavy. Do not try to lift by hands or other unsuitable
equipment. Danger of injury! Perform all moves with extreme attention and care.
Remove the boiler packaging with attention. Keep the packaging material away from chidren since it can be dangerous. After having unpacked everything, make sure that the
appliacne is intact and undamaged. In case of doubt do not use the appliance and inform the supplier.
The BIOPLEX boiler is delivered with the following equipment already fitted and mounted:
Boiler steel body Rockwool insulation mounted on the boiler body and tightened with plastic tapes Metal covers mounted on the boiler body Turbinators positioned inside the fire tubes Cast iron catalyst for the biomass combustion Cast iron grates for wood combustion Control panel and electrical connections
The furnace system BIOFIRE is already preassembled and mounted on the boiler side flange. It consists of:
BIOFIRE furnace steel body Fuel silo with lid, shutter, inspection window Feeder with screw Fan Motoreducer Transmission system with chain wheels Protection cover of the mechanism Cast iron combustion plate
The following accessories are positioned inside the boiler body. Remove them carefully by opening the middle door.
Cleaning tools Safety kit Drainage valve
In the documentation folder you will find:
Technical manual Warranty leaflet Declaration of conformity
Page 10
BOILER MOUNTING
10
3.2. Boiler room
3.2.1. General requirements
The boiler must be installed in a special and separate room. This room must be chosen so that it offers easy access for fuel transport, air supply and exhaust gas evacuation. The doors of the boiler room must be metallic, open outwards, and have at least 0,9 m width.
The boiler installation is prohibited in rooms with extensive dust, dangerous
gases, and moist spaces.
For the correct boiler function it is necessary that the boiler room has openings for natural ventilation and combustion air supply. It is recommended that two different openings are used for this purpose, positioned on opposite walls and diagonally to ensure good air circulation. The total surface of the openings must be at least 1/12 of the boiler room surface. Forced ventilation is prohibited in the boiler room.
The boiler room must be provided with a drainage channel. All safety devices must be connected to this channel.
The boiler room must have an appropriate fire extinguishing system, according to the regulations in force. In case that the building is designed with a fire alarm system, a smoke detector must be positioned on top of every boiler.
The fuel storage is prohibited in the boiler room. If so, the storage must be separated from the boiler with a non-flammable wall, and proper distanced from the boiler.
3.2.2. Boiler room dimensions
The boiler must be placed on a horizontal plane, with adequate mechanical resistance to support the boiler’s weight. The boiler must be positioned in the room in such a way so that it is easily accessible from all the sides. The following dimensions are recommended (see Fig 2)
Distance from the front wall (N):
For boilers up to 100 kW – minimum 1,5 m For boilers bigger than 100 kW – minimum 2 m
Distance from the rear wall (L):
Appropriate distance for maintenance access. Minimum 0,6 m.
Distance from side walls (M):
For boiler up to 300 KW – minimum 0,6 m For boilers bigger than 300 kW – minimum 1 m
Boiler room height (H):
For boilers up to 70 kW – minimum 2 m For boilers 70 to 230 kW – minimum 2,4 m For boiler 230 to 400 kW – minimum 3 m For boiler bigger than 400 kW – minimum 3,5 m
Distance between two boilers (P) must be at least 1m.
Fig 2. Boiler room dimensions
Page 11
BOILER MOUNTING
11
3.3. Chimney
The chimney installation must supply sufficient draught, air tightness and protection against condensation.
The appropriate chimney installation is very important for the boiler’s efficient and safe function!
The chimney must be positioned if possible in the interior of the building. It must be vertical, with no changes in the direction. The cross-section of the chimney can be round or rectangular. If the chimney is installed in the exterior, it must be insulated.
The horizontal part connecting the boiler’s chimney pipe with the vertical chimney must have
maximum length 2 m. If this distance is bigger, it is recommended to have a 15-30o inclination upwards. The connection with the boiler’s chimney pipe must be air-tight.
The chimney must be equipped with a cleaning door at its base. Also cleaning doors are recommended where there are changes in direction and ash can be accumulated. Tactical cleaning is recommended (every 3 months) for efficient boiler function.
A chimney terminal must be installed at the end of the chimney for protection against weather effects and foreign objects entrance. In areas with strong winds a special anti-downdraught terminal is recommended.
The chimney height must exceed the roofline by at least 1 m. If there are other obstacles positioned on the roof, the chimney height must exceed them by at least 1 m. If there are multiple chimneys, minimum distance between them is 0,3m.
Each boiler should be connected to an independent chimney. Connection of multiple boilers to the same chimney is not recommended.
Fig 3. Chimney distances
Page 12
BOILER MOUNTING
12
Fig 4. Chimney connection
Page 13
INSTALLATION
13
4. INSTALLATION
4.1. Hydraulic connections
The boiler is intended for connection with an open expansion vessel network. The boiler can be connected also with closed expansion vessel, if it is equipped with an overheating serpentine (optional).
The boiler is intended for maximum working temperature 90oC and maximum pressure 3 bar for boilers up to 500 kW, and 4 bar for bigger boilers.
When connected with a closed expansion vessel, its volume must be chosen double to a similar installation on liquid or gas fuel.
If a connection pipe is not used, it must be sealed before water fill!
Legend
T1
Outlet
T2
Return
T3
Chimney pipe
T4
Discharge valve connection
T5
Safety kit connection
T6
Additional safety connection
4.2. Safety features
The boiler equipment includes a safety kit, which shall be connected to the corresponding connection pipe T5. The kit consists of a safety valve, an air relief valve and a thermomanometer. Bigger boilers are equipped with two or more safety valves.
Additional safety equipment can be mounted at the connection pipe T6. This can be a dual safety valve (pressure and temperature) or a cooling valve. Alternatively this pipe can be used for connection with the expansion vessel.
Fig 5. Boiler safety kit
Page 14
INSTALLATION
14
4.3. Overheating serpentine
As an optional, the boiler can be equipped with an overheating protection serpentine. This is incorporated in the boiler body, surrounding the fire chamber.
For the function of the safety serpentine, a discharge valve must be installed. The bulb of the valve must be mounted on the boiler’s hot water delivery, at maximum distance 1m from the boiler.
Fig 6. Overheating serpentine connection
The valve can be connected on either side of the serpentine. Attention should be given to the flow direction of the valve. The valve can be fitted on the cold water inlet or hot water outlet. However, we recommend that the valve is fitted on the cold water inlet.
For the protection of the valve, a filter is recommended to be installed on the water line before the valve.
On the opposite side of the serpentine, drainage must be connected.
The correct function of the discharge valve is crucial for the boiler’s safety.
Verify its function often and replace if defect.
4.4. Return temperature protection
For the correct function of the boiler and for protection against corrosion it is very important to ensure steady temperature at the return of the boiler of at least 55oC.
This can be ensured by installing a recirculation pump between the boiler outlet and return (see connection diagrams).
An alternative variation is by installing at the return of the boiler a three-way thermostatic valve.
Page 15
INSTALLATION
15
4.5. Filling the system
After completing all the hydraulic connections, the circuit may be filled with water. After filling the system, open the radiators air valves to get rid of the air in the installation.
Verify that the installation pressure is according to the technical feature of the boiler. The pressure must be verified through the boiler’s manometer. An additional manometer should be installed on the cold water inlet to verify the cold pressure, at the lowest point of the installation, at a point close to the boiler.
The whole installation must remain under nominal pressure for at least 10 minutes. During this period, check that all the connections are tight and there are no water leakages. Make sure that during this period no pressure drop appears.
After firing the boiler, make sure the network functions properly at working temperature and pressure.
The hardness of the mains water supply affects the boiler’s life span. It is
recommended to use a water softener if water hardness exceeds 15of.
Do not fill the system at the working pressure! When the boiler will be heated, the water pressure will raise. Filling pressure must be at least 1 bar lower than working pressure!
4.6. Automatic ignition system
As an optional, the furnace can be provided with an automatic ignition system. This consists of the following:
Ignition element 500W (2 pieces in bigger boilers) Control panel Ecomax 800P (technical manual given with the control panel) Exhaust temperature sensor
The ignition element is installed in a special inox tube casing, positioned under the furnace cast iron plate. The cables are protected with a silicon layer, resistant to temperature up to 300oC. All the electrical connections are prewired.
The controller is equipped with an exhaust temperature sensor. This must be installed on the chimney, at a distance maximum 1m from the boiler.
If the boiler comes with the automatic ignition system, refer to the controller’s manual for electrical connections and settings.
Page 16
INSTALLATION
16
4.7. Connection diagrams
4.7.1. Open expansion vessel connection
Legend
1-9.
Separation valves
10,11.
Radiator valves
12.
Radiators
13-15.
Safety valves
16.
Filling valve
17.
Drainage valve
18.
Cold water valve
19-24.
One-way valves
B
Hot water boiler
VED
Open expansion vessel
PCI
Central heating pump
PRC
Recirculation pump
RP
Pressure reducer
F
Filter
A
Air relief valve
FD
Water softener
Page 17
INSTALLATION
17
4.7.2. Closed expansion vessel connection
Legenda
1-9.
Separation valves
10,11.
Radiator valves
12.
Radiators
13-15.
Safety valves
16.
Filling valve
17.
Drainage valve
18.
Cold water valve
19-24.
One-way valves
B
Hot water boiler
VE
Closed expansion vessel
PCI
Central heating pump
PRC
Recirculation pump
RP
Pressure reducer
F
Filter
A
Air relief valve
FD
Water softener
Page 18
BOILER START-UP
18
5. ELECTRICAL CONNECTIONS
5.1. General instructions
All electrical connection must be performed by an authorized professional, in conformity with the local regulations and the indications of this manual. Connections must be done according to norms EN 60529 and EN 60335-1, and protection norms IP 40 and IP 44.
All wiring must be waterproof insulated. Exposed cables should be protected within plastic channel. The main electrical supply of the boiler must be connected to an independent safety of max 16A. The boiler room lighting must be on a separate circuit.
THERMOSTAHL is not responsible for accidents or malfunctions caused by
wrong or bad electrical connections.
5.2. Control panel functions
Fig 7. Control panel
The general switch ON/OFF interrupts the electrical supply to all the devices.
The furnace thermostat interrupts the fan and motor function when the preset boiler temperature has been reached. It is recommended that this temperature is set between 70­90oC. This temperature should never be set below 60oC.
The fan speed regulator regulates the fan rotating speed by means of a dimmer rheostat.
The pump thermostat starts the circulation pump function at the preset temperature. It is recommended that this temperature is set around 45-55oC. The pump indication lamp follows the function of pump.
The safety thermostat will interrupt the fan function if the boiler temperature reaches above 95oC. If so, it needs to be reset manually by unscrewing the plastic cover.
The ventilator and motor switches are used to activate or deactivate the corresponding devices. The switch has an incorporated indication lamp that follows the function of the devices.
The motor timer controls the motor function by means of ON/OFF time intervals. The first timer T1 controls the TIME OFF interval, while the T2 the TIME ON interval.
If a burner is connected to the control panel, it can be connected in the place of the fan and regulated by the fan thermostat.
Legend:
1.
Thermometer
2.
Furnace thermostat
3.
Safety thermostat
4.
Pump thermostat
5.
General ON/OFF switch
6.
Motor timer
7.
Fan speed regulator
8.
Pump indication lamp
9.
Motor switch
10.
Fan switch
Page 19
BOILER START-UP
19
The control panel offers the possibility to connect with a room thermostat. When the room thermostat contact opens, the furnace function stops.
5.3. Wiring diagram
Fig 8. Control panel wiring diagram
Legend:
GS
General ON/OFF switch
TS
Safety thermostat
TM
Furnace thermostat
TP
Pump thermostat
VT
Fan speed regulator
LP
Pump indication lamp
SM
Motor switch
SV
Fan switch
TR
Room thermostat
PE
Grounding
Unscrew the control panel back plate to have access to the connection terminals in the interior.
Connect the main electrical supply to the terminals 1,2,3 as indicated. The fan is connected to the terminals 10,11,12 and the pump to the terminals 4,5,6.
The motor phase is connected to the terminal 9, while neutral and grounding together with the fan’s at terminals 12 and 11 respectively.
Between the terminals 7,8 there is a jumper. If you want to connect a room thermostat, remove the jumper and connect it to these two terminals.
Attention: The room thermostat must be a simple contact interruptor. It is not allowed to connect a digital thermostat with an electrical signal output!
Page 20
BOILER START-UP
20
6. BOILER START-UP
6.1. Initial lighting checks
Before you start the boiler, make the following checks:
Check that all the hydraulic connections and make sure they are tight. Make sure there is
no leakage or moisture on the pipes or other equipment.
Make sure that the connection with the chimney is air-tight and the chimney installation is
properly made.
Check that the controller bulbs are well inserted and secured in the boiler’s case. Make sure that the pressure in the network is correct. Check that the boiler pump and the central heating pumps function properly. Make sure that the connection with the expansion vessel is correct and the expansion
volume is sufficient for the boiler. No valves should be installed between the boiler and the expansion vessel.
Make sure the boiler’s separation valves are open. Make sure that there is sufficient air supply and natural ventilation in the boiler room.
Do not store inflammable materials or fuel close to the boiler! Before you light
the boiler make sure the boiler room is clear and safe.
6.2. Start-up
To correctly start up the BIOPLEX boiler follow the next steps:
Make sure the silo is full with fuel. Make sure the chimney damper is positioned in horizontal position (completely open). Open the middle door (feeding door) to have visual supervision of the feeding procedure. Turn the control panel on from the general switch and activate only the motor from the
corresponding switch. Keep the fan deactivated during this step.
Set the first timer T1 to maximum and the second T2 to zero, in order to fill the furnace
with fuel. Fill it until the fuel level reaches the cast iron plate and covers a small part of it.
Stop the motor function from the motor switch. Using sheets of thin paper or other ignition material, light the fuel placed in the furnace.
Wait several minutes until the flame stabilizes and covers the entire plate surface.
Close the middle door of the boiler. Turn on the fan by the corresponding switch. During this
step the motor must remain deactivated.
When the flame is fully developed, activate both the motor and the fan. Set the furnace
thermostat to the required temperature.
Follow the instructions given in the chapter Combustion Regulation to correctly regulate the
combustion.
It is prohibited to light the boiler with inflammable or explosive liquids.
6.3. Checks to carry after initial start-up
During the first start-up you need to carefully check the air-tightness of all the connections, especially the doors and the connection with the chimney.
Check that the thermostats function properly and devices operate accordingly. Wait for the boiler to reach the preset temperature and make sure the fan stops properly and the flame falls down.
Check the temperature and pressure rise in the network. Make sure it is according to the indications. Check if there is any water leakage in the network.
After burning of the fuel is completed, check the situation inside the boiler. If the walls are too black, it means that there is insufficient air supply. If there is condensation forming on the
Page 21
BOILER START-UP
21
boiler walls, it means that the pump operation starts at a low temperature or the fuel has too big humidity content. Make sure you set the pump according to the indications and you install a return temperature protection system as indicated.
6.4. Fuel loading
In order to correct add fuel to the boiler follow the next steps:
Stop the fan function by turning the fan thermostat to zero. Wait 30 seconds for the fume to
exit the boiler.
Open the middle door slowly to avoid leakage of smoke. Load a sufficient amount of fuel.
Each loading should be regulated according to the boiler output and the heat demand. Never load too much to fuel to fill all the fire chamber volume! Maximum fuel should be 70­80% of the fire chamber volume.
Close the door and secure with the handle. Start again the fan function by putting the thermostat to the preset temperature.
When loading fuel in the boiler do not throw them but position them carefully.
6.5. Combustion regulation
After completing the start-up procedure and closing the door, set the required temperature to the furnace thermostat (noted Motor Regul”). After the fan and motor are activated, have a look at the quantity of fuel fed to the furnace and the shape of it on the cast iron plate.
The timer must be set in such a way, so that the quantity of fuel fed is stable to a level where it makes a small hill over the plate, covering almost half of its surface (middle picture). If the fuel accumulates covering all the plate surface (left picture), it means the feeding is too big and must be reduced. If the level of the fuel is below the plate (right picture), it means the feeding is too small and must be increased.
Fig 9. Fuel feeding regulation
The feeding depends on two parameters: the feeding time (timer T1) and the stop time (time T2). When you want to increase the feeding, increase the feeding time and reduce the stop time. When you want to reduce the feeding, reduce the feeding time and increase the stop time. These two timers must be set together, and with not too big difference (the ratio between TIME ON/TIME OFF must be between 0,5-0,9). This way you achieve a stable feeding and fire in the furnace.
After regulating the feeding, observe the flame shape and color through the flange provided on the middle door. The flame will have to occupy about two thirds of the fire chamber and quietly lick the cylindrical heat exchanger. Its shape must be fully developed and with not too many detachments at the flame end. Its color must be vivid orange-yellow, not too transparent.
The combustion quality is regulated through the air delivery. By positioning the fan damper you regulate the air pressure and by the control panel speed regulator you regulate the fan
Page 22
BOILER START-UP
22
speed. The combination of these two will result to the optimum air delivery in order to accomplish perfect combustion.
GENERAL SUGGESTIONS
The flame needs to have reasonable dimensions and fill up the fire chamber as told. The flame must not be too red (too low air supply). The flame must not have big detachments and sparkles (too high air supply). The flame must not be too small. If it is slow, easily influenced by air currents and the
chimney draught, it means that the air supply is too low.
The smoke at the chimney must be clear-grey. Black smoke means lack of air supply. If too much ash and big coal pieces fall down to the ash box reduce the air supply.
The flame is too fast, dry, and might make a noise.
6.6. Chimney damper adjustment
The boiler chimney pipe is equipped with a damper. This can be set in various positions to throttle the exhaust gases.
At nominal function of the boiler this damper should be normally open. Also it should always be at open position at boiler start-up.
If the chimney draught is too big and the gases are evacuated too fast, set this damper at a side position by inserting the positioner at a different hole.
If a burner is installed, it is recommended that the damper is in completely closed position.
Fig 10. Chimney damper
Page 23
SERVICE AND MAINTENANCE
23
7. SERVICE AND MAINTENANCE
7.1. Cleaning
7.1.1. Cleaning the boiler
Solid fuel boiler require regular cleaning in order to function properly and efficient. Cleaning must be effected at least once a week. The boiler is equipped with three cleaning tools
appropriate for the cleaning procedure of the boiler, as shown in Fig 11.
Fig 11. Boiler cleaning tools
The boiler function must be stopped before cleaning! Make sure all the devices are stopped, and the boiler has cooled down. It is strictly prohibited to clean the boiler while in function!
Open the upper door to have access to the heat exchanger. Remove the turbinators from the tubes, and clean the tubes with the appropriate tool. Afterwards clean the exterior surface of the cylindrical heat exchanger with the exchanger cleaning tool, as shown in Fig 12. With the same tool, scrape the ash and any other remains from the side walls of the boiler.
Fig 12. Cleaning of the heat exchanger
Open the lower door of the boiler and remove the ash box. Empty all the containing ash. With the ash cleaning tool you can scrape the lower surface of the boiler for any residues of ash.
The ash must be disposed in an appropriate container! Do not throw the ash together with the domestic garbage. Be careful since ash might contain hot particles, even long time after stop.
Fig 13. Removing the ash
Legend:
1.
Tubes cleaning tool
2.
Heat exchanger cleaning tool
3.
Ash cleaning tool
Page 24
SERVICE AND MAINTENANCE
24
7.1.2. Cleaning the chimney box
To ensure efficient and safe function of the boiler, you must clean the chimney box from ash residues at least every 3
months.
The ash box is equipped with a cleaning door for this purpose, as shown in Fig 14. In order to open the door, unscrew the wing nuts, remove the washers and springs that keep it in place.
Clean the interior of the chimney box and remove all the ash and residues.
Put back the door the same way as removed.
The springs must not be omitted! They act as safety in order of explosion of exhaust gases in the chimney box.
Fig 14. Cleaning the chimney box
7.1.3. Cleaning the furnace
The furnace should be regularly cleaned according to the ash deposits, but not less than once a week. To clean the furnace follow the next steps:
Stop the furnace function by the control panel and leave it to cool down completely. Clean the surface of the cast iron plate from ashes and other deposits. Make sure the air
holes are clean and free from obstacles.
Clean the ashes and deposits at the perimeter around the plate. After you turn on again the furnace, ensure the fuel feeding is performed freely and the fuel
is evenly distributed at the plate surface.
Check the function of the motoreducer and the fan. Clean from dust if needed.
7.2. Maintenance intervals
7.2.1. Daily maintenance
The pressure of the network must be daily verified to be within the allowed limits. Make sure that all the safety devices and pumps function properly.
7.2.2. Weekly maintenance
The boiler must be cleaned every 3-4 days or at least once a week, depending on the ash quantity accumulated on the boiler walls and in the heat exchanger. Cleaning procedure must be performed according to the instruction given in the corresponding paragraph.
Check the quantity of ash accumulated in the ash box. The ash disposal can be performed every 1-2 weeks, depending on the ash quantity formed.
7.2.3. Monthly maintenance
Check the doors and the sealing cord. Make sure the contact with the boiler is air-tight. If ash has accumulated on the sealing cord, clean it.
Check the fan and make sure it functions properly. Clean from dust and check that the air passage is clear of obstacles and dust.
Remove the turbinators from the heat exchanger and check their condition.
It is recommended that you clean the chimney box of the boiler and the chimney pipes at least every 3-4 months, in order to assure efficient and safe function of the boiler.
Page 25
SERVICE AND MAINTENANCE
25
7.3. Basic service procedures
7.3.1. Service after overheating
If overheating occurs, the safety valves of the boiler must open. If the boiler is equipped with an overheating protection coil, cold water will enter the coil to protect the boiler.
Make sure the boiler pump is working. In case of blackout open all the valves of the system to let hot water out of the boiler. In any case a blackout protection UPS is recommended to be installed on the boiler pump.
If the chimney damper is not fully opened, put it in fully open position.
All safety devices must lead to drainage! After overheating, make sure that all the water from the safety devices has drained, and the system has filled with cold water. Check the pressure and the temperature of the boiler.
At overheating, the safety thermostat will activate, and cut electrical supply to the fan. In that case, you need to manually reset the safety thermostat and put the system back in function. Unscrew the plastic cover of the safety thermostat and press the switch. Put the plastic cover back.
Verify the causes of the overheating! If it happens again, check the installation
and function of the pumps and safety devices!
7.3.2. Service after feeder blockage
If a blockage occurs to one of the feeders, you will have to remove the axes in order to clean the feeding tubes. The same procedure is applicable at the annual maintenance procedure.
Before proceeding to any of the following steps, make sure the boiler function is stopped, the boiler is cool, and it is disconnected from the electricity. Do not try to do any works while the motor is working and the control panel is activated! Risk of injury!
REMOVING THE UPPER AXIS
Remove the protection cover of the transmission system. Remove the two gears from the axes by unscrewing the headless inserted screws keeping
them in place. You do not need to unmake the chain! Remove them all together with the chain.
Unscrew the four nuts from the back side of the flange (see Fig 15)
Fig 15. Removing the upper axis flange
Page 26
SERVICE AND MAINTENANCE
26
Remove the whole feeder together with the bearings and supporting disk (see Fig 16).
Fig 16. Removing the upper axis
When putting back together, it is absolutely necessary to put the rubber gasket at
its position!
REMOVING THE LOWER AXIS
Remove the protection cover of the transmission system. Remove the two gears from the axes by unscrewing the headless inserted screws keeping
them in place. You do not need to unmake the chain! Remove them all together with the chain.
Unscrew the four nuts keeping the motor in place and remove it (see Fig 17).
Fig 17. Removing the lower axis
Remove the support disk and the feeder. When putting back together, it is absolutely necessary to put the rubber gasket at
its position!
Page 27
SERVICE AND MAINTENANCE
27
7.3.3. Service after motor bolt breakage
The connection between the motoreducer and the lower axis is realized through a protection bolt. This is designed in such a way so that it breaks in case of feeder blockage, to protect the motor from burning.
If this bolt breaks, follow these steps to replace it:
Remove the two gears from the axes by
unscrewing the headless inserted screws keeping them in place. You do not need to unmake the chain! Remove them all together with the chain.
Unscrew the nut and remove the broken bolt. Introduce a new bolt M6x50 and tighten with the
nut from the other side.
Verify the causes of the breakage. If there is an
obstacle in the feeding pipe remove it.
Fig 18. Motor protection bolt replacement
7.3.4. Service after power blackout
In case there is a power blackout, it is absolutely necessary to perform some checks and take some safety measures to avoid overheating. The solid fuel has all the time a certain amount of fuel in the fire chamber, which will not stop burning immediately.
For safety reasons it is recommended you have installed a UPS with a battery, which assures function of the boiler pump at least for 30 minutes.
Remove the amount of fuel that is still burning in the furnace. Due to power blackout, there
is risk of backfire to the silo.
Turn the control panel to OFF. When the power is restored, turn on the control panel and make sure all the devices
function properly.
7.3.5. Replacement of the ignition element
In case you need to replace the ignition element follow the instructions:
Turn OFF the control panel and disconnect from electricity. Disconnect the connection wires of the ignition element and loosen the plastic tap holding
them in place.
Remove the fan by unscrewing the four screws keeping it in place. Remove the furnace plate. The ignition element is positioned inside the INOX tube casing. Remove the ignition element from the tube and insert in position the new one. When you position back the furnace plate, be careful to fix it correctly with the fixing tooth,
as shown on Fig 19.
Page 28
SERVICE AND MAINTENANCE
28
Fig 19. Removing the ignition element
7.4. Maintenance after long stop
7.4.1. Maintenance of the boiler
It is necessary to perform a general maintenance and cleaning of the boiler after the heating season. Clean thoroughly all the surfaces of the boiler as described in the corresponding paragraph. Also clean the chimney box, and all the chimney parts where ash might be deposited. After cleaning all the ash, empty the ash box and leave the boiler clean for the next winter season.
After long stop of the boiler, before you put in function you need to perform the following checks:
Check the condition of the electric cables and the sensors. Make sure they are not
damaged. Check that the thermometer indicates the correct temperature and all the thermostats function properly. Make sure the bulbs are properly positioned in the case.
Make a general check of the chimney and make sure it is clean and free of obstacles. Verify the pressure in the heating network and the boiler.
Do not empty the water of the boiler and the heating installation after the
heating season! It will corrupt all the installation and especially the boiler.
Check that all the valves are working properly. Replace them if necessary. Pay special
attention so that all the safety equipment of the boiler functions properly!
Make sure all the ball valves of the boiler and other relative equipment are open. Check the function of the pumps. They might be blocked after long stop. Check that there have been no modifications to the installation and the boiler room
(ventilation openings, chimney, doors).
Check the fan and clean from dust. Turn it manually to ensure it is not blocked.
Page 29
SERVICE AND MAINTENANCE
29
7.4.2. Maintenance of the furnace
It is necessary to perform a general maintenance and cleaning of the furnace after the heating season. The maintenance of the furnace should only be done when the boiler is stopped, cool and the power deactivated. For easier maintenance it is recommended to leave all the fuel in the silo be consumed before you proceed to works. The maintenance procedure includes the following steps:
Do not attempt to do any maintenance or service to the furnace while working! There is serious danger of burning! Wait until the boiler is cool and deactivate from the electricity.
Make sure the silo is empty. If not, empty manually the silo before proceeding to any
works. Open the silo cleaning door if necessary to remove any remaining fuel.
Remove the silo from the furnace body by unscrewing the bolts. Remove the motoreducer which is mounted on the lower axis. See instruction in chapter
7.3.2.
Check the motoreducer. Check the oil level in the reducer and add oil if necessary. Remove the two feeders. Check them and make sure they are in good shape and not
deformed.
Clean the tubes where the feeders are inserted. Remove any fuel or ash remains. Remove the cast iron plate of the furnace. Clean thoroughly the elbow underneath the plate, form where the fuel is provided. It is very
important to be clean of any obstacles that could block the feeding.
Clean very well all the holes on the plate surface. If they are blocked use a sharp tool to
clean them.
Put together all the pieces in the reverse order. Check all the sealing material between the
connections. Make sure they are in good shape and provide an air-tight sealing. Tighten well the screws to ensure an air-tight connection.
After putting together the axes and the chain wheels, make the chain has a good grip on
the wheels and the rotation is performed freely. Grease carefully the chain and the wheels.
Attention: All the connections (boiler-furnace, furnace-silo, inspection doors,
etc.) must be air tight! If not there is high danger of backfire to the silo!
Page 30
WARRANTY
30
8. TROUBLESHOOTING
Problem
Cause
Solution
The lamps of the control panel do not light
- no electrical supply to the lamp
- the control panel is not connected to electricity
- lamp defect
- electric cable defect
- check/replace the lamp
- connect to electricity
- check/replace the cables
The boiler does not reach set temperature
- fan blocked
- air passages are blocked
- boiler is not cleaned
- incorrect boiler start-up
- insufficient water in the system
- too big pump debit
- boiler under dimensioned
- bad quality fuel used
- insufficient chimney draught
- check/replace the fan, check the function of the fan regulator and thermostat
- clean the air passages
- clean the boiler
- start the boiler correctly
- fill the system
- regulate the pump speed
- change the fuel used
- check/clean the chimney
High temperature in the boiler, but low temperature at the radiators
- too high hydraulic resistance in the heating network
- thermostatic mixing valve is connected wrong
- increase the pump speed
- check/replace the mixing valve
Condensation formation in the fire chamber
- too big boiler power
- too low return temperature in the boiler
- fuel with excessive humidity
- load less fuel in the chamber
- install a return protection system/thermostatic valve
- change the fuel used
Smoke coming out of the doors
- boiler doors not regulated
- defect sealing cord of the door
- insufficient chimney draught
- too high air supply by the fan
- regulate the doors so that the sealing cord stays tight
- check/replace the sealing cord
- check/clean the chimney
- reduce the air speed
Smoke coming back to the silo
- chimney not cleaned/blocked
- fire tubes blocked, boiler not cleaned
- furnace air holes blocked
- insufficient air supply and ventilation of the boiler room
- too low flame and fuel level
- bad air regulation
- wrong fuel ignition
- bad chimney connection/ insufficient chimney draught
- damaged sealing
- check the chimney, clean it
- clean the boiler and the tubes
- clean the furnace and the air holes
- check the air supply and ventilation
- regulate correctly the fuel feeding
- check the ignition procedure
- check the chimney connection and draught
- check all the connections sealing, do not leave the silo lid open while in function
The fan does not function or it makes a lot of noise
- set temperature reached
- disconnected by safety thermostat
- capacitor/motor defect
- bad electrical connection of the fan
- correct boiler function
- reset manually
- check/replace the fan
- check the electrical connection of the fan
The feeder does not function/fuel not fed to the furnace
- feeder blocked from obstacle
- feeder is burnt or damaged
- no electricity to motor
- damaged motor/reducer
- connection pin broken
- remove the axes and the obstacle
- bad combustion regulation/bad chimney draught
- replace feeder
- check the electrical connections
-replace the motoreducer
- replace the connection pin
Page 31
WARRANTY
31
9. WARRANTY
1. Warranty duration is 3 years for all boiler parts under pressure, 1 year for other
electro-mechanical equipment. The warranty period starts from the date of installation,
but no longer than 120 days from the day of purchase.
2. The warranty covers costs of replacing parts that have been proved to be defect, and any
work that is connected with replacing these parts. Costs related to removing defect parts or products, transportation, etc. are not covered by the producer’s warranty.
3. The producer will not accept to cover warranty terms in case of the following:
Maltreating the product and bad conditions of transportation and loading-unloading. Wrong installation, failing to apply the directions given in the manual. Improper use of the product. Damages that have been cause by using improper fuels, with dimensions or
characteristics different from those described in the manual.
Damages from freezing if not necessary measures are taken against anti-freezing. Incident of explosion due to use of impropriate chemical substances. Electrical shocks that may harm electrical parts of the appliance.
4. Warranty is only valid if the installation is performed by a professional installer, authorized
by the producer, according to the local legislation and the instructions of this manual.
5. Warranty does not cover function problems or damages that are caused by bad chimney
installation, failing to respect the instruction of this manual and local legislation.
6. Warranty is not valid if the boiler cleaning, maintenance and service intervals are not
respected and the directions given are not followed.
7. Warranty is not valid if the maintenance is not performed by an authorized professional
according the instructions given and at the time intervals given.
8. Warranty does not cover costs related to emergency incidents like: earthquake, fire,
electrical blackout, robbery.
9. Warranty is not valid if the hardness of the water is over the allowed limits and no water
softening protection is installed.
10. The warranty is not transferable in case of reselling or replacing the product. A new
warranty should be accorded to the new user.
Page 32
THERMOSTAHL ROMANIA
SISTEME TERMICE S.R.L.
DRUMUL OSIEI 57-59, sector 6
Bucharest 062395, Romania
www.thermostahl.ro
Loading...