Thermoscreens VRF PHV1000 DXE HO, VRF PHV1500 DXE HO, VRF PHV2000 DXE LO, VRF PHV1500 DXE LO, VRF PHV2000 DXE HO Installation, Operation & Maintenance Instructions Manual

Page 1
9901035-1 Page 1 of 30
PHV SURFACE MOUNTED HEAT PUMP AIR CURTAINS
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
For use with CITY MULTI VRF units
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTI NG INSTALLATION
Thermoscreens Ltd
St. Mary’s Road Nuneaton
Warwickshire England
CV11 5AU
Email: sales@thermoscreens.com
Tel: +44 (0) 24 7638 4646 Fax: +44 (0) 24 7638 8578
www.thermoscreens.com
English
Page 2
9901035-1 Page 2 of 30
Thermoscreens / Mitsubishi Electric
Thermoscreens City Multi Heat Pump Air Curtains can be used with Mitsubishi Electric City Multi Y/WY-Series (Heat Pump) or City Multi R2/WR2-Series (Heat Recovery) systems.
City Multi Y/WY-Series Heat Pump Air Curtain System
City Multi Y/WY-Series Heat Pump Air Curtain Schematic :-
City Multi Y-Series System:­ Indoor Units and Air Curtains(s) all operate on heating at the same time, or all operate on
cooling at the same time.
The City Multi Y Series Heat Pump Air Curtain system consists of :-
One or more Thermoscreens VRF PHV Heat Pump (heating and cooling) Air Curtains *
A Mitsubishi Electric PAC-AH…M-G AHU Controller or PAC-AH…M-H AHU Controller
(one for each air curtain) *
A Mitsubishi Electric PAR-21MAA Remote Controller (one for each AHU Controller) +
One or more Mitsubishi Electric City Multi Y/WY-Series Compressor Unit +
Mitsubishi Electric Indoor Unit(s)
+
[NB. Can be used on a full air curtain basis if required
up to 100% diversity]
Mitsubishi Electric BMS System or Centralised Controller, if required
+
* - supplied by Thermoscreens Ltd.;
+
- supplied by others
Heat Pump
Air Curtain
Mitsubishi Electric
Com
p
resso
r
Unit
LEV(s)
PAC-AH AHU
Controller
BMS Control
Fan
Sensors
Mitsubishi Electric
Indoor Units
Permanent electrical supply
(from local switched spur)
PAR-21MAA
remote
controlle
r
Defrost signal
Refrigeration pipework Electrical/Controls cables
1 per air
curtain
Powe
r
Permanent mains electrical supply
(from local switched spur) for:
x Fans x Defrost electric heaters (if used) x PAC-AH…AHU Controller
Remote
3-Speed
Fan Switch
Cond. alarm
Page 3
9901035-1 Page 3 of 30
City Multi R2/WR2-Series Heat Pump Air Curtain System
City Multi R2/WR2-Series Heat Recovery Heat Pump Air Curtain Schematic :-
City Multi R2/WR2-Series System:­ Indoor Units and Air Curtains(s) can operate on heating or cooling simultaneously, e.g.
some indoor units are cooling whilst other indoor units and air curtain are heating at the same time.
The City Multi R2/WR2-Series heat recovery system with Heat Pump Air Curtain(s) consists of :-
One or more Thermoscreens VRF PHV Heat Pump (heating and cooling) Air Curtains *
A Mitsubishi Electric PAC-AH…M-G AHU Controller or PAC-AH…M-H AHU Controller
(one for each air curtain) *
A Mitsubishi Electric PAR-21MAA Remote Controller (one for each AHU Controller)
+
One or more Mitsubishi Electric City Multi R2/WR2-Series Compressor Unit
+
Mitsubishi Electric BC Controller
+
Mitsubishi Electric Indoor Unit(s)
+
[NB. Can be used on a full air curtain basis if required
up to 100% diversity]
Mitsubishi Electric BMS System or Centralised Controller, if required +
* - supplied by Thermoscreens Ltd.; + - supplied by others
Heat Pump
Air Curtain
Mitsubishi Electric
Compressor Unit
Permanent mains electrical supply
(from local switched spur) for:
x Fans x Defrost electric heaters (if used) x PAC-AH…AHU Controller
PAC-AH AHU
Controller
BMS Control
Fan
Sensors
Mitsubishi Electric
Indoor Units
Permanent electrical supply
(from local switched spur)
PAR-21MAA
remote
controller
Defrost signal
BC Controller
Refrigeration pipework
Electrical/Controls cables
1 per air
curtain
LEV(s)
Remote
3-Speed
Fan Switch
Power
Cond. alarm
Page 4
9901035-1 Page 4 of 30
DESIGN INFORMATION
Each Thermoscreens Heat Pump Air Curtain needs to operate with a Mitsubishi Electric
PAC-AH…AHU Controller. There are two versions that can be used; PAC-AH…M-G and PAC-AH…M-H the supply of which is dependent on the EU state where the installation is
being carried out.
The rated size of the PAC-AH…AHU Controller needs to be matched to the size of the heat pump air curtain. Each size of AHU Controller comes with different size LEV(s) and number of LEVs so they need to be matched to the air curtain. The table shows the AHU Controller to be selected and maximum outputs and air volume flow rates of the heat pump air curtain.
Maximum Heat
Pump Output (kW)
Air Curtain
PAC-AH…AHU
Controller
LEV(s) No.Off
Index Size
Heating Cooling
Air
Volume
Flow
(m3/h)
VRF PHV1000
DXE HO
PAC-AH125M-G
or
PAC-AH125M-H
Type P632411X01
1 off
P100
9.0 8.1 1400
VRF PHV1500
DXE LO
PAC-AH125M-G
or
PAC-AH125M-H
Type P632411X01
1 off
P125
10.6 9.0 2500
VRF PHV1500
DXE HO
PAC-AH140M-G
or
PAC-AH140M-H
Type P632414X01
1 off
P140
15.1 13.6 2600
VRF PHV2000
DXE LO
PAC-AH140M-G
or
PAC-AH140M-H
Type P632414X01
1 off
P140
16.4 14.8 3300
VRF PHV2000
DXE HO
PAC-AH250M-G
or
PAC-AH250M-H
Type P632411X01
2 off
P200
21.4 19.3 3130
Maximum heat pump output refers to the heating or cooling output from the air curtain air stream. Figures are derived from laboratory testing with reference to test standard EN14511. They are with the air curtain operating at high fan speed, outdoor air temperature 7/6°C db/wb indoor air temperature 20°C db for heating; outdoor air temperature 35/27°C db/wb indoor air temperature 27°C db for cooling. Contact Mitsubishi Electric for performance at other outdoor and indoor conditions. The air curtain normally operates under automatic temperature control set on the PAR-21MAA remote controller and can also run at part load.
The following City Multi compressor units can be connected:
For Y/WY-Series systems:
PUHY-(E)P200 …. 1250Y(S)HM-A PQHY-P200 …. 600Y(S)HM-A PUMY-P100 …. 140V(Y)HMB PUHY-HP200 …. 500Y(S)HM-A
For R2/WR2-Series systems:
PURY-(E)P200 …. 800Y(S)HM-A PQRY-P200 …. 600Y(S)HM-A
Page 5
9901035-1 Page 5 of 30
The Thermoscreens Air Curtain requires a permanent mains electrical supply from a local switched isolator. Electrical power to the PAC-AH…AHU controller is then fed from the air curtain. Electrical power to the Mitsubishi Electric compressor unit(s) and BC Controller is fed separately in the normal way (see separate Mitsubishi Electric instructions). If the defrost cycle electric heaters inside the air curtain are to be used during the heating mode defrost cycle the electrical supply to the air curtain needs to be 3-phase (3L+N+E). If the defrost cycle electric heaters are not required they can be permanently disconnected at installation and a single phase electrical supply (1L+N+E) fed to the air curtain instead, see 'Installation - Electrical Supply'.
Warning: Air curtain fans continue to operate during heating mode system defrost to
maintain an air stream across the doorway. With the defrost cycle electric heaters operating the discharge air temperature from the air curtain is kept to a few degrees below that of the indoor ambient air temperature during the duration of system defrost. If the electric heaters are disconnected, discharge air temperatures could be very cold, approximately 6ºC during the defrost and defrost times will also be extended, particularly with the R2-Series System. Defrost does not occur with WY and WR2 systems so the defrost cycle electric heaters should be disconnected on these systems.
There are various control cables that are wired on site to the PAC-AH…AHU Controller and the Thermoscreens Air Curtain that provide control for the operation of the unit. These are:-
Start/Stop of air curtain fans
Operation of LEV(s) for control of heating or cooling output
Thermistor sensors
PAR-21MAA Remote Controller for end user manual control, if used
On/Off of electric heaters inside the air curtain during system defrost (if used)
Condensate alarm derived from condensate pump alarm sensor (if used)
M-Net communications link to the Mitsubishi Electric Compressor Unit.
(see also wiring diagrams)
The Thermoscreens Air Curtain is supplied with an integral condensate drain tray to enable the air curtain to be used in cooling mode during warm weather, if so desired. If it is intended to use the air curtain in cooling mode a suitable condensate pump (not supplied by Thermoscreens) must be supplied by the installer. The condensate pump must be of sufficient capacity, self priming and capable of providing the appropriate suction head so the pump will lift condensate out from the top of the air curtain but can be hidden in a remote location if necessary. Suitable condensate pumps are Peristaltic or Rotary Diaphragm type. We recommend the Blue Diamond rotary diaphragm type with cooling signal sensor (drainStik) manufactured by Charles Austen Pumps Ltd. (www.miniblue.co.uk).
It is recommended that the condensate pump has the facility so it only operates when the air curtain is in cooling mode by detection of water in the drain tray or by detecting a cooling differential in the airflow. It should also have a pump overrun to empty the drain tray as much as possible when the air curtain is switched off. It should have an alarm system with appropriate sensor that will give a volt-free signal (open circuit = alarm). This will stop the air curtain cooling if the condensate drain tray is in danger of flooding, air curtain fans will continue to operate. Other City Multi indoor units are unaffected if the air curtain condensate alarm occurs. There is a plastic fixing bracket with 8mm diameter hole
Page 6
9901035-1 Page 6 of 30
attached to the drain tray inside the air curtain so a condensate sensor can be fixed in the tray by the installer. The hole can be enlarged, if necessary, to suit the type of sensor used so it is located in the tray at the appropriate position, see the manufacturer’s instructions that come with the condensate pump for further information. The 230v AC, single phase electrical supply to operate the condensate pump will come from the air curtain.
Warning: The air curtain condensate collection system is designed to remove condensate
with the air curtain operating in cooling mode during normal summer weather conditions in countries with a temperate climate. In case of extreme weather conditions or condensate pump failure, which can occur, it is vital that the design of the floor beneath the air curtain and its surface is such that it will not become slippery or damaged if it became wet. This is similar to the conditions that might be experienced with heavy rainfall or wet pedestrian foot traffic at an open doorway, so careful consideration must be paid to the design of the floor and its finish.
If it is intended that the air curtain should not be operated in cooling mode and a condensate pump is not fitted, the BMS System, Centralised Controller or PAR-21MAA manual Remote Controller must be configured at commissioning so that COOL or AUTO mode can never be selected (see Section – Commissioning). It is still recommended, however, that the floor design and surface be as described above in case cooling mode is used in the future and to cope with heavy rainfall or wet pedestrian foot traffic.
Note: It could still be possible for an end user to unlock a PAR-21MAA Remote Controller
if they found out how to and switch it into cooling, not realising that condensate would then flood out of the drain tray. It may therefore be considered prudent to install a condensate pump and drain system even if it is intended that the unit should only be used in HEAT or FAN mode.
If a Building Management System (BMS) or Centralised Controller is to be used for control of the air curtain please contact Mitsubishi Electric for more details.
The air curtain is designed only for use with a Mitsubishi Electric City Multi VRF system for use on R410A. The complete Thermoscreens/Mitsubishi Electric heat pump system, including fridge pipework, wiring, controls, etc. must be installed only by an approved Mitsubishi Electric refrigeration contractor.
The air curtain is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety.
High Output (HO) and Low Output (LO) in this document refers to the heat pump heating or cooling capacity of the Air Curtain, not to any electrical rating. HO air curtains have a 3­row coil, LO air curtains have a 2-row coil.
These instructions must be read in conjunction with the Mitsubishi Electric instructions that come with other components of the heat pump system, e.g. Compressor Unit, BC Controller, PAR-21MAA Remote Controller, BMS System, Centralised Controller, etc. They should be kept by the building facilities manager for future reference.
Page 7
9901035-1 Page 7 of 30
UNPACKING THE HEAT PUMP AIR CURTAIN
The following items are supplied and packaged within the Thermoscreens air curtain box.
The Mitsubishi Electric PAC-AH…M-G AHU Controller or PAC-AH…M-H AHU Controller comes in its original Mitsubishi Electric box. It is delivered with the larger Thermoscreens air curtain box. It is factory pre-wired as much as possible to reduce installation time on site.
Check with the cross-reference labels on the Thermoscreens air curtain box and the Mitsubishi Electric AHU Controller box that the correct AHU Controller is matched with the correct air curtain.
Other components for the heat pump system are as described above on the System Schematics on pages 2 and 3.
Wall Brackets and Fixing Bolts
City Multi Heat Pump Air Curtain
Please note, end caps are supplied loose to be fitted during installation
Remote 3-Speed Fan Switch
PAC-AH..M-G or M-H..AHU Controller
Page 8
9901035-1 Page 8 of 30
The Installer will also need to supply and install the following:-
The following optional equipment is also available for the air curtain:-
For your records:
Date of Purchase……………………………..
Place of Purchase…………………………….
Serial Number…………………………………
For warranty purposes proof of purchase is necessary so please keep a copy of your invoice.
Sheet metal covers to hide services Fan Speed Controller for low speeds
Condensate Pump – self priming with cooling mode detection, alarm system and pump overrun
PAR-21 MAA Remote Controller
If Air Curtain is to be manually controlled,
also needed for commissioning
If Air Curtain is to be operated in COOL or
AUTO mode – see text for more information
Page 9
9901035-1 Page 9 of 30
INSTALLATION OF THE HEAT PUMP AIR CURTAIN
The air curtain is designed to be surface mounted inside of the building and located over a doorway. It must not be installed outside of the building, or built into a cabinet or recessed in any way.
Location
The air curtain must be mounted so the discharge grille is between 1.8m minimum and 3.75m maximum above floor level and situated as close to the doorway as possible. Beware of doorway top edges, structural beams, door opening devices, etc. which may interfere with the air stream and affect the location of the unit. The air curtain must be installed level or condensate may leak out, particularly if it tilts down at the left hand side (looking out of the doorway from inside). It is better to tilt down slightly at the right hand side as the drain tray spout is this side.
Wall Fixing
Bolt all of the wall brackets supplied to the rear face of the unit as shown in the adjacent picture using the M6 bolts supplied. Suitable wall fixing bolts (not supplied) need to be used to fix the brackets to the wall, taking into account the type of wall and the weight of the unit*, see table:
Air Curtain Weight (kg)
VRF PHV1000 DXE HO 39
VRF PHV1500 DXE LO 59
VRF PHV1500 DXE HO 60
VRF PHV2000 DXE LO 78
VRF PHV2000 DXE HO 80
Step 1. Refer to Figure 1 for mounting details and drill the
fixing points in the wall.
Step 2. Screw in the top wall bolts leaving a small gap between the head and the wall.
Lower the unit onto the bolts via key-hole slots in the top of the wall brackets and then screw in the bottom wall bolts.
Step 3. Ensure all fixing bolts are tightened and the air curtain is safely secured to the
wall.
Ceiling Suspension
M10 threaded inserts are provided in the top face of the unit (see Figure 1 for positions) so it can be suspended on M10 threaded hanging rods (not provided). All suspension points must be used. Ensure each of the hanging rods is secured onto a suitable structure that can support the
weight of the unit (see table above)*. Screw the hanging
rods into the inserts by a minimum of 20mm and fit locking nuts (not supplied) to prevent the rod rotating and coming away from the casing. Do not screw the hanging rod too far in or it will interfere with internal components.
* It is the sole responsibility of the installer to ensure that the building fixing locations and
suspension system used are suitable for the air curtain being installed.
250mm min
Page 10
9901035-1 Page 10 of 30
295
E E
D
C C
B
A
168
36
255
377
PHV2000DXPHV1500DX
22961746
18961400
1300
700
1824
948
650 912
A (mm)
B (mm)
C (mm)
D (mm)
E (mm)
Hot Gas
Refrigerant Connection
Liquid line
Refrigerant Connection
100
Electrical Supply and
Control Wiring Inlets
for pipes
250 min.
PHV1000DX
1196
800
800
N/A
N/A
Alternative holes for condensate hose
Optional sheet metal covers
to hide pipework, cables, etc.
250, 500 or 1000 high
Holes for M10 drop rods
4 for 1m unit, 6 for 1.5m/2m units
Use all drop rod holes !
FIGURE 1 – DIMENSIONS OF PHV HEAT PUMP AIR CURTAIN
Page 11
9901035-1 Page 11 of 30
Refrigerant Pipework
This must be carried out before connection of any electrical and controls cables and in accordance with the Instructions that come with the Mitsubishi Electric City Multi equipment. This work must only be undertaken by a Mitsubishi Electric approved Contractor.
Refrigerant installation pipework sizes need to be as follows :-
Air Curtain
Discharge Line
(Gas)
Liquid Line Index Size
VRF PHV1000 DXE HO
8
5
in.
8
3
in.
P100
VRF PHV1500 DXE LO
8
5
in.
8
3
in.
P125
VRF PHV1500 DXE HO
8
5
in.
8
3
in.
P140
VRF PHV2000 DXE LO
8
5
in.
8
3
in.
P140
VRF PHV2000 DXE HO
4
3
in.
8
3
in.
P200
NOTE: Contact Mitsubishi Electric for recommended pipework lengths, numbers of fittings etc.
The installation must be done in accordance with Mitsubishi Electric Service Manual.
It is intended that refrigerant pipe connections to the air curtain are made using brazed joints and these must be carried out in a professional and safe manner. If installation pipe sizes for the discharge (gas) line and liquid line are different from the pipe connection sizes on the air curtain, suitable pipe reducers must be used for the connection. R410A refrigerant systems can operate at pressures up to 610 psi (c. 42 Bar). These brazed joints may well be located in a public area and a weakness leading to an explosion could be extremely dangerous. The air curtain with its coil is manufactured in accordance with the Pressure Equipment Directive and the installation must be carried out to a good standard of workmanship. Remove the protective plastic film on top of the air curtain before starting work. Use a heat sink on the copper pipes when brazing to reduce the transfer of heat to the inside of the air curtain where sensitive components are located. Make sure the thermistor (gas) sensor has not been inserted into its pocket on the gas pipe at the top of the air curtain before brazing. Remove it if it has or it will burn when the pipe connection is brazed.
For the City Multi system the LEV needs to be brazed into the liquid line as close as possible to the air curtain (2m maximum). The picture shows an example of this. On the VRF PHV2000 DXE HO there are two LEVs to be fitted in parallel (see Mitsubishi Electric AHU Controller instructions). If required the LEV(s) can be hidden away in an adjacent void or above ceiling tiles, or the LEV(s) and pipework can be hidden inside the optional sheet metal services covers, see Page 8.
For the City Multi VRF R2 and WR2 Series system, pipework from each air curtain must connect to one pair of ports on the Mitsubishi Electric BC Controller. The exception to this is the VRF PHV2000 DXE HO air curtain that requires 2 pairs of ports on the BC Controller to achieve the correct output. Do not combine pipework from two or more air curtains together into one set of pipework and then connect this to one pair of ports.
NB: A maximum P140 Index is possible from 1 pair of ports, contact Mitsubishi Electric.
Page 12
9901035-1 Page 12 of 30
To gain access inside the Air Curtain
To gain access for connection of the electrical supply, controls wiring and to work on the unit during commissioning, remove the air inlet grilles and the bottom access panel.
First remove the plastic end caps if already fitted by pulling off to the side (see picture).
Then remove each inlet grille in turn with its filter by unfastening the M4 Pozi Head screw at the bottom corner of the grille. Use a Pozi No.1 screwdriver to access the screw via the elongated hole at each bottom corner of the grille (see adjacent picture).
To remove the bottom access panel unfasten the access panel securing screws, one at each end and two in the centre (PHV1500 and PHV2000 units) and slide the panel out forwards.
Please note: All the panels of the air curtain are covered in a protective plastic film which should now be removed.
Electrical Supply to the Air Curtain
This must be carried out AFTER the connection of the refrigerant pipework. All electrical wiring and connections MUST be carried out by a competent qualified electrician in accordance with the latest edition of the IEE wiring regulations and/or local statutory regulations. (see also Wiring Diagrams on Pages 14 and 15)
A local isolator having a contact separation of at least 3mm on all poles must be
fitted in the electrical supply to the air curtain and located in an accessible position adjacent to the unit. 3 phase if defrost electric heaters are required. 1 phase if defrost electric heaters are not required.
The appliance must be connected using cables having an appropriate temperature
rating (heat resistant).
Ensure that the supply cables, circuit breakers and other electrical installation
equipment are correctly sized for the air curtain being installed. See Table below.
A 20mm size cable gland or conduit connector should be used for the Electrical
Supply into the air curtain.
This appliance must be Earthed.
access panel
Page 13
9901035-1 Page 13 of 30
400V/3ph/50Hz
if defrost electric heaters are required
230V/1ph/50Hz
if defrost electric heaters are not used
Air Curtain
Rated Electrical
Power Input (kW)
Rated Current per
phase (A)
Rated Electrical
Power Input (kW)
Rated Current (A)
VRF PHV1000 DXE HO
4.8 7.8 0.3 1.3
VRF PHV1500 DXE LO
7.8 12.7 0.35 1.8
VRF PHV1500 DXE HO
7.8 12.7 0.35 1.8
VRF PHV2000 DXE LO
9.5 15.7 0.5 2.7
VRF PHV2000 DXE HO
9.5 15.7 0.5 2.7
If the defrost electric heaters are not to be used they can be disabled by disconnecting the neutral to the contactor coil inside the air curtain (see below and wiring diagrams on Pages 14 & 15).
Note: If the defrost electric heaters are disconnected, discharge air temperatures could
be very cold, approximately 6ºC. Defrost times could also be extended, particularly with the R2-Series System. *
Do not use cable size of more than 2.5mm2 or connection will be difficult.
See also wiring diagram on page 14 or page 15.
If the defrost electric heaters are to be disabled this can be done by disconnecting the
purple (neutral) wire from terminal A2 on the contactor inside the air curtain. The disconnected purple wire should be terminated safely into unused auxiliary terminal
14NO as
shown in the adjacent picture, or into a suitable terminal block.
*NB. Defrost does not occur with WY and WR2 systems so the
defrost cycle electric heaters should always be disconnected on these systems.
The photo above shows the completed wiring to terminals L1,L2, L3, N and (Earth) for a 3 phase electrical supply (400v/3ph/50Hz) if defrost electric heaters are used
The photo above shows the completed wiring to terminals L1, N and (Earth) for a single phase electrical supply (230v/1ph/50Hz) if defrost electric heaters are not
used
Page 14
9901035-1 Page 14 of 30
Local Electrical Supply for Defrost
Electric Heaters and Fans
VRF PHV1000 = 7.8A per phase
VRF PHV1500 = 12.7A per phase
VRF PHV2000 = 15.7A per phase
K1
K1
SITE WIRING
E
400V/3ph/50Hz
L1
L2 L3
N
Electrical Supply for
Outdoor Unit
400V/3ph/50Hz
or 230V/1ph/50Hz
OPTIONAL LOW SPEED CONTROLLER
1m unit 3 x 1.5kW = 4.5kW
1.5m unit 3 x 2.5kW = 7.5kW
2m unit 3 x 3.0kW = 9kW
If Defrost Electric Heating Elements
are not required disconnect purple wire
from A2 and terminate wire safely in
auxiliary terminal 14NO.
L2 and L3 are not then needed
L1 is then 230V/1ph/50Hz
1.3A for VRF PHV1000DX
1.8A for VRF PHV1500DX
2.7A for VRF PHV2000DX
Terminal 1 (Switched LIVE - Live only when air curtain is operating)
Terminal 8 (NEUTRAL)
Terminal 9 (EARTH)
Electrical supply for Condensate Pump, use:-
or, Terminal 7 (Permanent LIVE - Live at all times)
LINK-OUT if not
using 3-Speed Fan
Switch
(Medium Fan
Speed shown)
WIRING DIAGRAM – VRF PHV Heat Pump Air Curtain with PAC-AH…M-G AHU Controller
Page 15
9901035-1 Page 15 of 30
K1
SITE WIRING
E
400V/3ph/50Hz
L1
L2 L3
N
Electrical Supply for
Outdoor Unit
400V/3ph/50Hz
or 230V/1ph/50Hz
OPTIONAL LOW SPEED CONTROLLER
1m unit 3 x 1.5kW = 4.5kW
1.5m unit 3 x 2.5kW = 7.5kW
2m unit 3 x 3.0kW = 9kW
Local Elect r ical Supply for Defrost
Electric Heaters and Fans
VRF PHV1000 = 7.8A per phase
VRF PHV1500 = 12.7A per phase
VRF PHV2000 = 15.7A per phase
Terminal 1 (Switched LIVE - Live only when air curtain is op erating)
Terminal 8 (NEUTRAL)
Terminal 9 (EARTH)
Electrical supply for Condensate Pump, use:-
or, Terminal 7 (Permanent LIVE - Live at all times)
LINK-OUT if not
using 3-Speed Fan
Switch
(Medium Fan
Speed shown)
K1
If Defrost Electric Heating Elements
are not required disconnect purple wire
from A2 and terminate wire safely in
auxiliary terminal 14NO.
L2 and L3 are not then needed
L1 is then 230V/1ph/50Hz
1.3A for VRF PHV1000DX
1.8A for VRF PHV1500DX
2.7A for VRF PHV2000DX
WIRING DIAGRAM – VRF PHV Heat Pump Air Curtain with PAC-AH…M-H AHU Controller
Page 16
9901035-1 Page 16 of 30
Wiring to PAC-AH…AHU Controller and Controls Wiring
The Mitsubishi Electric PAC-AH…AHU Controller needs to be located within 7m from the air curtain (cables are 8m long). It has four mounting feet to fix it to a wall or alternatively it can be placed on a horizontal flat surface if located in a compartment or ceiling void. It comes pre-wired with various 8m long cables for power supplies, thermistor sensors, LEV(s), alarms, etc. which have to be connected to the air curtain. It can be hidden behind a nearby bulkhead or in an adjacent room so it is out of view, although it must be accessible for future service work if necessary. Each of the pre-wired cables has a label attached to it at the end of the cable showing where it has to be connected at the air curtain. The following table lists the connections to be made between the PAC-AH…AHU Controller and the Air Curtain. Please note, there are two types of
AHU Controller, PAC-AH…M-G and PAC-AH…M-H, and wiring of some cables and
components is different for each type. This is indicated in the table below. See also wiring
diagram on Page 14 for PAC-AH…M-G, and Page 15 for PAC-AH…M-H.
Controller
Type
Termination at
PAC-AH…
Cable / Component Termination at Air
Curtain
M-G and M-H 8m 3-core cable pre-
wired to terminals E N L POWER SUPPLY
Electrical power supply from air curtain to PAC-AH… – 230v ac
wire to terminals 7 8 9
M-G and M-H 8m 2-core cable pre-
wired to terminals D1 D2 OPERATION SIGNAL
Operation signal from PAC-AH… to start Air Curtain – 230v ac
wire to terminals 1 & 2
M-G and M-H 8m 2-core cable pre-
plugged into CN52 on PAC-AH… pcb
Defrost signal from PAC-AH… to operate contactor in air curtain for defrost electric heaters if used
wire to terminals 5 & 6
M-G and M-H 8m 2-core cable pre-
wired to terminals T21 T22 THERMISTOR (GAS)
Thermistor (Gas) temperature sensor – identified Black
Fit sensor bulb into Hot Gas pocket on refrigerant gas pipe at top of air curtain after brazing pipe connections
M-G and M-H wire to terminals
T11 T12 THERMISTOR (LIQUID)
Thermistor (Liquid) temperature sensor – identified White
8m 2-core cable with sensor bulb factory fitted within air curtain
M-G only wire to terminals
T1 & T2 THERMISTOR (INLET AIR)
Thermistor (Return Air) temperature sensor – identified Red
8m 2-core cable with sensor bulb factory fitted within air curtain
M-H only wire to terminals
T1 & T2 THERMISTOR (OUTLET AIR)
Thermistor (Return Air) temperature sensor – identified Red
8m 2-core cable with sensor bulb factory fitted within air
curtain M-H only Terminals T31 T32 5.6k resistor factory fitted Not Applicable M-G and M-H 8m 6-core cable pre-
wired to 6-way colour coded LEV terminals
Linear Expansion Valve(s) - LEV(s) Install in liquid line near to air
curtain
M-G and M-H 8m 2-core cable pre-
plugged into CN31 on PAC-AH… pcb
Condensate alarm from condensate pump alarm system, open circuit = alarm and stops unit
Connect to condensate pump
alarm terminals which must
be volt free, open cct = alarm
Page 17
9901035-1 Page 17 of 30
Remote 3-Speed Fan Switch
A remote 3-speed fan switch is supplied with the air curtain so the end user can remotely
select High, Medium or Low fan speeds to suit the local conditions. The 3-Speed Fan Switch should be mounted on a wall with the Mitsubishi Electric PAR-21MAA Remote Controller, if used, so the end user will then have On/Off, temperature control and fan speed control all from one location. The 3-speed fan switch is wired to terminals FAN, HIGH, MED and LOW in the Air Curtain using 230v mains rated, 4 core double insulated cable of size 0.75mm2.
If the remote 3-Speed fan switch is not to be used, a permanent wire link must be fitted across the fan terminals in the air curtain or the fans will not operate when the system is started. This will result in an error message from the compressor unit after a time. The picture opposite shows a wire link fitted across terminals FAN and MED and the air curtain would operate at Medium Fan Speed whenever the heat pump system is switched on.
Note: Fan speed selection using the PAR-21MAA Remote Controller is not available. The
fan speed control logic within the PAC-AH…AHU Controller is not suitable for the operation of an air curtain and so is not used.
The finished wiring to the air curtain will be as shown in the pictures opposite (wiring is shown with a 3-phase electrical supply for enabled defrost heaters).
Note the use of 20mm conduit with thermistor sensors and low voltage cables in a separate conduit to the mains rated cables.
PAR-21MAA Remote Controller
If the air curtain is to be manually controlled by the end user a Mitsubishi Electric PAR-21MAA remote controller (not supplied by Thermoscreens) must be supplied and fitted by the installer. This is wired to the PAC-AH…AHU Controller using 2-core cable. Refer to the Mitsubishi Electric instructions that come with the PAR-21MAA remote controller for installation and wiring of the controller. A PAR-21MAA Remote Controller is also required for commissioning purposes and if using AUTO mode with a BMS System or Centralised Controller.
M-NET Communications Cable
The M-NET communications cable is wired to the PAC-AH…AHU Controller in accordance with Mitsubishi Electric instructions. Avoid isolators in the communications cables as this can lead to transmission problems.
Sensors and
low voltage
cables
230v rated
cables
Page 18
9901035-1 Page 18 of 30
Condensate Pump
If it is intended to use the air curtain in cooling mode a suitable condensate pump (not supplied by Thermoscreens) must be supplied and fitted by the installer. The condensate pump must be of sufficient capacity, self priming and capable of providing the appropriate suction head so the pump will lift condensate out from the top of the air curtain. The condensate pump can sit on the top of the air curtain or be hidden in a remote location if necessary. Suitable condensate pumps are Peristaltic or Rotary Diaphragm type. We recommend the Blue Diamond rotary diaphragm type with cooling signal sensor (drainStik) manufactured by Charles Austen Pumps Ltd. (www.miniblue.co.uk).
It is recommended that the condensate pump has the facility so it only operates when the air curtain is in cooling mode by detection of water in the drain tray or by detecting a cooling differential in the airflow. It should also have a pump overrun to empty the drain tray
as much as possible when the air curtain is switched off. It should have an alarm system with appropriate sensor that will give a volt-free signal (open circuit = alarm). This will stop the air curtain cooling if the condensate drain is in danger of flooding, bringing up error code 2502 or 2503, and the air curtain fans will continue to operate. Other City Multi indoor units are unaffected if the air curtain condensate alarm occurs. There is a plastic fixing bracket with 8mm diameter hole attached to the drain tray inside the air curtain so a condensate sensor can be fixed in the tray by the installer. Enlarge the hole if necessary to suit the sensor so it is located in the tray at the appropriate position, see the manufacturers instructions that come with the condensate pump for further information.
The 230v AC, single phase electrical supply to operate the condensate pump should come from the air curtain (see wiring diagram). For a condensate pump with cooling mode start and pump overrun, as recommended above, use Terminals:- 7 (Permanent Live), 8 (Neutral), 9 (Earth) which provides a permanent 5A fused supply. Terminal 1 (Switched Live) can be used if a Switched Live is required. This will energise when the air curtain is operating (Heat, Fan or Cool) and de-energise when it is switched off. This is also a 5A fused supply.
The air curtain is supplied with a 1m length of 12mm bore plastic hose ready fitted to the outlet spout of the drain tray. The plastic hose can be found curled up inside the air curtain at the right hand side of the unit. There are two holes in the casing, one at the top of the unit and one at the rear, both fitted with rubber plugs (see Figure 1, Page
9). The plastic hose should be pushed through one of the these holes after removing the plug and connected to the condensate pump using the adapter supplied with the pump. It may be necessary to extend the hose if the pump is remotely located. Whichever condensate exit hole is used for the hose the condensate must be pumped away, it will not gravity drain via the lower hole at the rear of the casing, the condensate must still be pumped away!
Air Curtain
Maximum likely
Condensate flow rate
(litres/hour)
VRF PHV1000 DXE HO
6.0
VRF PHV1500 DXE LO
7.0
VRF PHV1500 DXE HO
10.0
VRF PHV2000 DXE LO
11.0
VRF PHV2000 DXE HO
14.0
Page 19
9901035-1 Page 19 of 30
Optional Sheet Metal Covers
Optional sheet metal covers are available to hide the various services that enter the air curtain from above. They are available in sizes of 250mm, 500mm and 1000mm high and are supplied flat packed for assembly on site. The sheet metal covers are secured to the top of the air curtain via M6 screws into threaded inserts. They hide hanging rods and all other services such as pipework, cables, condensate pump, hoses, optional fan speed controller, etc. Two covers can be fitted to PHV1000 units and three to PHV1500 and PHV2000 units (see Figure 1, Page 9)
Optional Fan Speed Controller
An optional fan speed controller is available to provide a greater range to the three fan speeds in the air curtain. Three fan speeds are still used but the speeds can be reduced to lower levels than the standard fan motor offers. The controller is useful if noise levels are an issue on site as the fan speeds can be reduced accordingly. The controller can be fitted to the air curtain retrospectively. It does not fit inside the air curtain but comes with 2m cables so it can be hidden remotely from the unit or even inside one of the optional sheet metal covers. Separate instructions come with the fan speed controller showing how it is connected to the air curtain and commissioned.
Page 20
9901035-1 Page 20 of 30
COMMISSIONING THE HEAT PUMP AIR CURTAIN
Ensure that the electrical supply to the Air Curtain is switched off before starting any commissioning work.
Air Curtain Checks
Check that the components inside the air curtain are as shown in the picture below. Check that the thermal overheat cut-out switch has not ‘tripped’. Push down on the red button on the top of the thermal overheat switch - if it has tripped it will click back on.
Set the adjustable aluminium vanes of the discharge air grille so they point straight downwards over the doorway.
A PAR-21MAA Remote Controller should be connected and used to carry out commissioning even if the air curtain is to operate under the control of a BMS System or Centralised Controller. Disconnect the remote control plug from inside the PAC-AH…AHU Controller to use the remote controller. Plug it back in again if a BMS/Centralised Controller is to be used and the PAR-21MAA is disconnected after commissioning.
NB. If the air curtain is used in AUTO mode under the control of
a BMS System or Centralised Controller it is necessary to also have a PAR-21MAA Remote Controller connected.
Mitsubishi Electric Compressor Unit
For Y-Series systems ensure that the appropriate dip switch has been set in the compressor unit so that the PAR-21MAA Remote Controller will operate in AUTO mode and to enable Auto Re-Start after power failure if required.
PUMY-P model:- SW2-5 ON for AUTO mode PUHY-P YHM and PQHY-P YHM model:- SW4-5 ON for AUTO mode
SW1-9 and SW1-10 on for Auto Re-Start after power failure.
Thermal overheat cut-out switch
Air Inlet Sensor RED
Liquid Line Sensor WHITE
12v DC & 230v AC
relays
Connections on electric elements
Page 21
9901035-1 Page 21 of 30
Mitsubishi Electric PAC AH…AHU Controller
Remove the access covers of the PAC-AH…AHU Controller and check that the dip switch settings are correct for the controller. These need to be set as follows:
123
45
6
ON
OFF
SW2 (P100)
123
4
ON
OFF
SW7
123
45
ON
OFF
SW4
123
45
6
ON
OFF
SW3
7
8910
123
45
6
ON
OFF
SW1
7
8910
123
ON
OFF
SW8
VRF PHV1000DXE HO
123
45
6
ON
OFF
SW2 (P125)
VRF PHV1500DXE LO
123
45
6
ON
OFF
SW2 (P140)
VRF PHV2000DXE LO
123
45
6
ON
OFF
SW2 (P200)
VRF PHV2000DXE HO
VRF PHV1500DXE HO
Black rectangle indicates moveable head of dip switch
These settings are the same for PAC-AH…M-G and PAC-AH…M-H AHU Controllers.
Starting the System
Carry out a final inspection to ensure that all wiring is in accordance with the wiring
diagram on Page 14 for a PAC-AH…M-G or Page 15 for a for PAC-AH…M-H and that
all connections have been properly made. Ensure that the refrigerant system is complete, there are no leaks and there is sufficient charge of refrigerant R410A. Switch on the electrical supply to the compressor unit and other City Multi system components. Wait 30 seconds and switch on the electrical supply to the air curtain at the local isolator. The system will boot-up and when the screen on the PAR-21MAA Remote Controller becomes active it will repeat the message “PLEASE WAIT”. After several minutes when the PLEASE WAIT message has stopped the system is ready to start.
DANGER: Beware of Fans Starting! Turn the air curtain on using the ON/OFF Button on
the PAR-21MAA Remote Controller and the air curtain fans will start straight away. Switch the Mode Button on the PAR-21MAA to heating mode and adjust the target temperature to 28°C maximum setting using the TEMP Button. If the 3-Speed fan switch is installed check that the fans run at Low speed, Medium speed and High speed by operating the slider switch. Check there is no mechanical noise coming from the fans at each of the three fan speeds and that all fans are working. If the 3-Speed fan switch is not to be installed a wire link will have been fitted to the fan speed terminals on the air curtain. Set the wire link to one of the three fan speeds (LOW, MED or HIGH) appropriate to the site conditions (see also Page 17).
Check Heating and Cooling Performance
In heating mode check that the air stream from the discharge grille warms up across the whole length of the air curtain after approximately 20 minutes of operation and that the air stream reaches right down across the doorway with the door open or closed. If necessary the aluminium vanes of the discharge grille can be angled either inwards or outwards if this gives better penetration/warming of any incoming draughts. The fan speed can also be adjusted (High, Medium or Low) to suit the conditions. If an optional
Page 22
9901035-1 Page 22 of 30
fan speed controller has been installed it may be necessary to re-set the voltage tappings on the transformers inside the fan speed controller to achieve a compromise between airstream performance and noise levels. This is explained in the instructions that come with the optional fan speed controller.
If it is intended that the air curtain is to ever operate in cooling mode switch the Mode Button on the PAR-21MAA remote controller to ‘COOL’ and adjust the target temperature to 14°C minimum setting using the TEMP Button. Wait for the air curtain air stream to go cold. Check the inside of the drain tray is clean, there is no debris in the outlet spout, there are no kinks in condensate hoses and the condensate pump will operate. It is unlikely that condensate will fill the drain tray straight away so it will be necessary to fill the tray manually with water to see if the condensate removal system is working satisfactorily. If an alarm sensor is fitted in the drain tray, check it operates to stop the air curtain cooling if the drain tray becomes too full. Test the air curtain for a time in cooling mode with all the panels and grilles fitted and if environmental conditions permit check that condensate is being collected and pumped away by the condensate pump. No condensate should leak out of the air curtain. At the end of the cooling test remove the inlet grilles and the bottom access panel and check that the inside of the air curtain has remained dry and that all condensate was collected by the removal system.
To conserve energy and carbon resources it is recommended to set up the BMS System, Centralised Controller or PAR-21MAA Remote Controller so it can operate in AUTO Mode at a target temperature of 24°C. This is the normal mode of operation for the heat pump air curtain and it should run in this set-up with no further adjustments, automatically heating or cooling as required. If the end user is to operate the air curtain with a PAR-21MAA Remote Controller set up the No.1 locking function on the controller so they can only switch the air curtain ON or OFF, with no control of mode or target temperatures. See user instructions for the Mitsubishi Electric PAR-21MAA Remote Controller.
BEWARE: It is possible for the air curtain to go into cooling mode on a warm day if the
BMS System, Centralised Controller or PAR-21MAA Remote Controller is set in AUTO mode as described above. A condensate pump and drain system must therefore be fitted if the air curtain is set in AUTO mode.
If it is intended that the air curtain should only operate in heating mode, never in cooling mode, the PAR-21MAA Remote Controller must be set to HEAT mode with an appropriate heating target temperature (say 24°C) and locked so only the ON/OFF function on the Remote Controller works. If it is to be operated from a BMS System or Centralised Controller this should be configured such that the air curtain can only operate in HEAT or FAN mode, never in AUTO or COOL mode. It is important this is done at commissioning if the air curtain is not to operate in cooling mode and is not fitted with a condensate pump and drain system.
Page 23
9901035-1 Page 23 of 30
Filter Dirty Indicator
The air curtain is fitted with a Filter Dirty Indicator. It is located at the left-hand end of the outlet grille and signals when the air curtain inlet grille/filters should be vacuum cleaned or the air curtain requires servicing.
NB. The filter dirty indicator on the PAR-21MAA Remote Controller
does not function wired to a PAC-AH…AHU Controller.
The indicator states are outlined below:
Indicator State Indicator Light Action Required Reset Button
GREEN FLASH On 0.5s; Off 3s None N/A
RED ON On permanently Vacuum inlet Quick reset
RED FLASH On 0.5s; Off 0.5s Service filters Press for 5s
The filter indicator schedule is based on fan operating hours. For the default schedule, shown schematically below, the inlet grilles should be vacuum cleaned every 120hrs of fan operation (every 1 to 2 weeks) and a full filter service should take place every 480hrs of fan operation.
The factory set default schedule is suitable for most applications. However, the actual frequency of cleaning required will depend on the environment. Two alternative indicator schedules are available, and can be selected by changing the ‘jumper’ position (marked 1, 2 or 3) on the Filter Indicator pcb.
Filter Indicator Schedule
Double-
frequency
Default
Half-
frequency
Jumper position
Inlet grille vacuum interval 60 hrs 120 hrs 240 hrs
Filter service interval 240 hrs 480 hrs 960 hrs
1
23
• • • •
123
• • • •
1 2
3
• • • •
START
120 hrs
120 hrs
120 hrs
120 hrs
480 hrs
RED ON: Quick reset
RED ON: Quick reset
RED ON: Quick reset
RED FLASH: Hold 5s to reset
Fan operating hours
Page 24
9901035-1 Page 24 of 30
To access the Filter Indicator pcb to change jumper:-
Switch off the electrical power to the Heat Pump Air Curtain. If the left-hand plastic end cap is already fitted, remove it from the air curtain. Unfasten the two screws as indicated.
Gently lower the left-hand end of the outlet grille, supporting it from below. The Filter Indicator pcb is now accessible to change the jumper.
Once the filter indicator pcb ‘jumper’ has been re-positioned, push the outlet grille back into place and fasten screws.
Hand-over to End-User
Before leaving site it is important that there is a 'Hand-Over Meeting' to hand-over the heat pump system and air curtain installation to the end user or their representative. This should include a full and clear explanation of how the system operates. Be sure to explain the Filter Indicator Schedule, that the air inlet grilles must be regularly vacuum cleaned and the unit serviced at regular intervals.
If the air curtain is to be operated under manual control, it is important that the end user understands how the Mitsubishi Electric PAR-21MAA Remote Controller and 3-Speed Fan Switch operate. That the PAR-21MAA Remote Controller has been locked so only the ON/Off button functions and the air curtain operates in AUTO mode with a fixed target temperature of 24°C. If a condensate pump and drain system has not been fitted it is vital they understand that the air curtain must not be run in COOL or AUTO mode and that the PAR-21MAA Remote Controller has been locked so only the ON/Off button functions and the air curtain operates only in HEAT mode with a fixed target temperature of 24°C.
If the air curtain is to be operated under the control of a BMS System or Centralised Controller, explain all the settings and demonstrate the operation of the system. If a condensate pump and drain system has not
been fitted it is vital they understand that the air curtain must not be run in COOL or AUTO mode, that it must only be operated in HEAT or FAN mode.
If a condensate pump and drain system has been fitted and they are going to run the air curtain in COOL mode (not just AUTO mode) explain that the target temperature should be adjusted to a comfortable level of cooling, not necessarily to the lowest target temperature possible as this uses a lot more energy and carbon resources.
Ensure that all instructions and manuals are handed to the end user or their representative.
Fixing
screws
Jumper
Page 25
9901035-1 Page 25 of 30
USER INSTRUCTIONS FOR THE AIR CURTAIN
For manual control using a PAR-21MAA Remote Controller
To Switch On and Off:
Turn the air curtain on by pressing the ON/OFF Button on the PAR-21MAA Remote Controller and the air curtain fans will start within a few seconds. If a 3-Speed Fan Switch is fitted adjust the fan speed to suit using the slider switch. As set up by the Commissioning Engineer the air curtain will operate in AUTO mode, automatically heating or cooling as required, with a target temperature of 24°C - all other buttons on the Remote Controller are locked out.
NB. The air curtain may produce condensate during hot weather so a condensate
pump and drain system must be fitted!
Turn the air curtain off by pressing the ON/OFF Button on the PAR-21MAA Remote Controller and the air curtain fans will stop.
If the PAR-21MAA Remote Controller is not locked the following functions operate:-
HEAT Mode:
Press the Mode Button on the Remote Controller until HEAT appears on the display. Adjust the target temperature using the or TEMP Button between 22°C and 28°C maximum. Allow time for the air stream to heat up.
AUTO Mode (only if condensate pump and drain system fitted!!):
Press the Mode Button on the Remote Controller until AUTO appears on the display. Adjust the target temperature using the or TEMP Button to 24°C. This is the normal mode of operation for the heat pump air curtain and it should run in this set-up with no further adjustments, automatically heating or cooling as required.
FAN Mode (Fan only - no heating or cooling):
Press the Mode Button on the Remote Controller until FAN appears on the display.
COOL Mode (only if condensate pump and drain system fitted!!):
Press the Mode Button on the Remote Controller until COOL appears on the display. Adjust the target temperature using the or TEMP Button between 20°C and 14°C minimum. Allow time for the air stream to chill. Do not necessarily use the lowest target temperature possible as this uses a lot more energy and carbon resources.
The temperature of the air returning to the air curtain is constantly displayed on screen.
PAR-21MAA
Remote Controller
3-Speed
Fan Switch
Page 26
9901035-1 Page 26 of 30
SERVICING THE HEAT PUMP AIR CURTAIN
Vacuum Clean the Air Inlet Grilles / Filters
(Weekly, or when the Filter Dirty Indicator shows PERMANENT RED)
With the air curtain switched OFF, a vacuum cleaner with an extension tube and brush attachment at its end should be used to clean the face of the air inlet grilles/filters. This is important to minimise the build-up of dust and lint on the air filters which will affect the performance of the air curtain. This is a simple service task that can be carried out by the Cleaner or Janitor on a weekly basis from floor level without having to access the air curtain at high level. This should be done weekly as a regular service task and/or when the Filter Dirty Indicator shows permanent red. Reset the Filter Dirty Indicator after cleaning by a quick press of the Reset Button (even if the indicator has not gone red).
Servicing the Air Curtain
(suggest every 3 Months, or if the Filter Dirty Indicator shows FLASHING RED)
Always disconnect and isolate the mains electricity supply both at the local electrical supply to the Air Curtain and to other Mitsubishi Electric equipment in the City Multi system before servicing, maintaining or repairing the Air Curtain.
Note: All servicing, maintenance and repairs to the air curtain must be carried out by a
Thermoscreens approved Service Agent. It may be necessary to involve a Mitsubishi Electric Service Agent if any work is to be carried out on the Mitsubishi Electric City Multi heat pump refrigeration system and its controls.
Remove the plastic end caps by pulling off to the side as shown.
Remove each Air Inlet Grille with its air filter by unfastening the M4 Pozi Head screw at the bottom corner of the grille. Use a Pozi No.1 screwdriver to access the screw via the elongated hole at the bottom corners of the grille (see picture).
Remove the air filters from the air inlet grilles by gently prizing them free as shown. Vacuum clean and refit the filters into the curved air inlet grilles. The filters are very durable but may need to be replaced after a number of service intervals.
Remove the bottom access panel by unfastening the panel fixing screws (2 on PHV1000, 4 on PHV1500 & 2000 units ­see picture) and sliding panel out forwards. Clean the inside of the panel.
Bottom Access Panel
Page 27
9901035-1 Page 27 of 30
Vacuum clean and remove any build-up of dust, dirt and debris within the air-curtain, especially on the face of the coil and the electric heating elements.
Note: Fan motors are permanently lubricated and require no additional lubrication.
The drain tray now angles down along its front edge and the inside surface of the tray can be easily cleaned. Remove all debris from the drain tray, outlet spout and condensate hose.
Check there are no kinks in condensate hoses. If the condensate pump is a peristaltic type change the rubber pump head tube.
Once the air curtain has been cleaned, visually inspect the air curtain components. Ensure pipe sensors are located in their pockets and any foam insulation covering these pockets is un-damaged. Check the location of the thermal overheat cut-out and air sensor and that the thermal overheat cut-out switch has not tripped (see Section ­Commissioning). Check all electrical connections and terminals within the unit are tight and that crimp connections have not become loose.
Refit the drain tray, bottom access panel and air inlet grilles/filters. Switch on the electrical supplies and fully function test the air curtain to ensure correct operation (see Section - Commissioning). Check the condensate pump operates, if fitted.
Reset the Filter Dirty Indicator after the service by pressing the Reset Button for at least 5 seconds (even if the indicator has not gone flashing red).and hand back the unit to the end user.
Loosen by 3 turns, the rear row of drain tray fixing screws along the whole length of the tray. Do not remove these screws completely.
Remove the front row of drain tray fixing screws along the whole length of the drain tray. Keep the screws.
Page 28
9901035-1 Page 28 of 30
Fault Conditions
If the Thermoscreens Heat Pump Air Curtain System does not operate as expected refer to the fault finding table below:
Symptom Possible Cause Action Required
Electrical power is not switched on to the Mitsubishi Electric City Multi system and at the local electrical isolator next to the Thermoscreens Air Curtain
Switch on power to all components in the heat pump system and wait 30 seconds
Air curtain is not switched On
Switch on air curtain using the PAR-21MAA Remote Controller, BMS System or
Centralised Controller Air Curtain fans are not wired to operate with either a 3-Speed Fan Switch or a wire link on fan terminals in air curtain
Wire in 3-Speed Fan Switch or
wire link – see wiring diagram
Air curtain
fans do not
operate
Problem with air curtain fan motor(s), or internal wiring, or controls
Use wiring diagram to
investigate possible cause of
fault Air curtain has been running for less than 20 minutes and is still warming up or cooling down
Give system sufficient time to
reach operating condition
Air curtain is set to Fan-Only on PAR­21MAA Remote Controller, BMS System or Centralised Controller
Check schedule on Controller
and amend if necessary
Target temperature is set incorrectly, i.e. too low for heating or too high for cooling
Adjust the target temperature
on the BMS System,
Centralised Controller or PAR-
21MAA Remote Controller
The operating mode is set incorrectly, i.e. set on COOL when heating is required
Select the correct mode for the
conditions on the BMS
System, Centralised Controller
or the PAR-21MAA Remote
Controller
Condensate Alarm circuit is open circuit and air curtain will not COOL
Rectify alarm circuit which
must be closed circuit for air
curtain to operate in cooling
Air curtain discharge air stream is not
heating or cooling when
required
Air Curtain filters and/or coil is dirty.
Service air curtain as described in Section -
Servicing Error Code 2502 or 2503 indicating condensate alarm from condensate pump alarm system
Inspect air curtain condensate
tray and condensate pump,
service or repair if necessary
Mitsubishi
Electric
system is
indicating an
error code
A variety of error codes can occur because of a fault within the air curtain
Refer to Mitsubishi Electric
Service Manual to understand
fault, then inspect and repair
air curtain if there is a fault
If the Heat Pump Air Curtain system is still not operating correctly call for a Mitsubishi Electric Service Agent.
Page 29
9901035-1 Page 29 of 30
Warranty
If any problems are encountered with the heat pump air curtain please contact your Mitsubishi Electric Service Agent.
Care has been taken in compiling these instructions to ensure they are correct, although Thermoscreens Ltd. disclaims all liability for damage resulting from any inaccuracies and/or deficiencies in this documentation. Thermoscreens Ltd. retain the right to change the specifications stated in these instructions.
Thermoscreens Ltd St. Mary’s Road Nuneaton Warwickshire England CV11 5AU
Email: sales@thermoscreens.com Tel: + 44 (0) 24 7638 4646 Fax: + 44 (0) 24 7638 8578
www.thermoscreens.com
Page 30
9901035-1 Page 30 of 30
EC DECLARATION OF CONFORMITY
as defined by the EC Council Directive on Machinery 2006/42/EC, the Low Voltage Directive 73/23/EEC,
the Electromagnetic Compatibility Directive 89/336/EEC and the Pressure Equipment Directive 97/23/EC
Herewith we declare that the air movement equipment designated below, on the basis of its design and construction in the form brought onto the market by us in accordance with the relevant safety, health and performance requirements of the Machinery.
If alterations are made to the machinery without prior consultations with us, this declaration becomes invalid.
Designation of Equipment : THERMOSCREENS AIR CURTAINS with CITY MULTI SYSTEM Series Type : VRF PHV1000DXE HO, VRF PHV1000RDXE HO, VRF PHV1500DXE LO,
VRF PHV1500RDXE LO, VRF PHV1500DXE HO, VRF PHV1500RDXE HO,
VRF PHV2000DXE LO, VRF PHV2000RDXE LO, VRF PHV2000DXE HO VRF PHV2000DXE HO
Relevant EC Council the Machinery Directive (2006/42/EC) the Low Voltage Directive (73/23/EEC as amended by 93/68/EEC) the Electromagnetic Compatibility Directive (89/336/EEC as amended by
91/31/EEC and 93/68/EEC)
the Pressure Equipment Directive (97/23/EC)
Applied Harmonised Machinery - EN 292-1, EN 292-2, EN 294, EN 394, EN 414 Standards : LVD - EN 60335-1, EN 60335-2-30, EN 60335-2-40
EMC - EN55011, EN 61000-3-2, EN 61000-3-3, EN 61000-4-2,
EN 61000-4-4, EN61000-4-5, EN61000-4-11, EN61000-6-4
PED - EN 13134, EN 13133 Basis of Self Attestation : Quality Assurance to BS EN ISO 9001 : 2000
B.S.I. Registered Firm Certificate Number FM 85224
Responsible Person : Mr. M. Francis, Managing Director, Thermoscreens Limited Date : 17th June 2009
Signed :
Thermoscreens Ltd St. Mary’s Road Nuneaton Warwickshire CV11 5AU United Kingdom Telephone: +44 (0)24 7638 4646 Fax: +44 (0)24 7638 8578