9901035-1 Page 16 of 30
Wiring to PAC-AH…AHU Controller and Controls Wiring
The Mitsubishi Electric PAC-AH…AHU Controller needs to be located
within 7m from the air curtain (cables are 8m long). It has four
mounting feet to fix it to a wall or alternatively it can be placed on a
horizontal flat surface if located in a compartment or ceiling void. It
comes pre-wired with various 8m long cables for power supplies,
thermistor sensors, LEV(s), alarms, etc. which have to be connected
to the air curtain. It can be hidden behind a nearby bulkhead or in an
adjacent room so it is out of view, although it must be accessible for
future service work if necessary. Each of the pre-wired cables has a
label attached to it at the end of the cable showing where it has to be
connected at the air curtain. The following table lists the connections to be made between
the PAC-AH…AHU Controller and the Air Curtain. Please note, there are two types of
AHU Controller, PAC-AH…M-G and PAC-AH…M-H, and wiring of some cables and
components is different for each type. This is indicated in the table below. See also wiring
diagram on Page 14 for PAC-AH…M-G, and Page 15 for PAC-AH…M-H.
Controller
Type
Termination at
PAC-AH…
Cable / Component Termination at Air
Curtain
M-G and M-H 8m 3-core cable pre-
wired to terminals E N L
POWER SUPPLY
Electrical power supply from air
curtain to PAC-AH… – 230v ac
wire to terminals 7 8 9
M-G and M-H 8m 2-core cable pre-
wired to terminals D1 D2
OPERATION SIGNAL
Operation signal from PAC-AH… to
start Air Curtain – 230v ac
wire to terminals 1 & 2
M-G and M-H 8m 2-core cable pre-
plugged into CN52 on
PAC-AH… pcb
Defrost signal from PAC-AH… to
operate contactor in air curtain for
defrost electric heaters if used
wire to terminals 5 & 6
M-G and M-H 8m 2-core cable pre-
wired to terminals
T21 T22 THERMISTOR
(GAS)
Thermistor (Gas) temperature
sensor – identified Black
Fit sensor bulb into Hot Gas
pocket on refrigerant gas
pipe at top of air curtain after
brazing pipe connections
M-G and M-H wire to terminals
T11 T12 THERMISTOR
(LIQUID)
Thermistor (Liquid) temperature
sensor – identified White
8m 2-core cable with sensor
bulb factory fitted within air
curtain
M-G only wire to terminals
T1 & T2 THERMISTOR
(INLET AIR)
Thermistor (Return Air)
temperature sensor – identified
Red
8m 2-core cable with sensor
bulb factory fitted within air
curtain
M-H only wire to terminals
T1 & T2 THERMISTOR
(OUTLET AIR)
Thermistor (Return Air)
temperature sensor – identified
Red
8m 2-core cable with sensor
bulb factory fitted within air
curtain
M-H only Terminals T31 T32 5.6kΩ resistor factory fitted Not Applicable
M-G and M-H 8m 6-core cable pre-
wired to 6-way colour
coded LEV terminals
Linear Expansion Valve(s) - LEV(s) Install in liquid line near to air
curtain
M-G and M-H 8m 2-core cable pre-
plugged into CN31 on
PAC-AH… pcb
Condensate alarm from condensate
pump alarm system,
open circuit = alarm and stops unit
Connect to condensate pump
alarm terminals which must
be volt free, open cct = alarm