Thermoscreens T1000R, T2000R, T1500R Installation Instructions

Page 1
T-RECESSED RANGE AIR CURTAINS
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING INSTALLATION
Thermoscreens Ltd
St. Mary’s Road Nuneaton
Warwickshire England
CV11 5AU
Email: sales@thermoscreens.com
Tel: +44 (0) 24 7638 4646 Fax: +44 (0) 24 7638 8578
www.thermoscreens.com
4003155-9 UK Page 1 of 19
Page 2
UN-PACKING YOUR T-RECESSED AIR CURTAIN
The following items are supplied and packaged within the boxes.
T-Recessed Air Curtain
Motorised Valve
(Ecopower LPHW units only)
Note Optional filters are available for Water and Ambient models.
If anything is missing or damaged please contact your place of purchase immediately.
For your records
Date of Purchase…………………………….. Place of Purchase……………………………. Serial Number…………………………………
For warranty purposes proof of purchase is necessary so please keep a copy of your invoice.
(All documentation supplied with each unit should be stored and kept for future reference).
Remote Control
Ecopower Electric & LPHW
Manual Ambient
Recessed Grille
(Packed separately)
4003155-9 UK Page 2 of 19
Page 3
INSTALLATION OF YOUR T-RECESSED AIR CURTAIN
The T-Recessed air curtain has been designed for recessing within ceiling voids or bulkheads.
Location
Ensure that the unit is mounted within its height specification of 1.8m to 3.0m maximum (from floor level to the underside of the unit/grille) and that it is situated as close to the door as possible. Note: The air discharge should be nearest to the door as shown in adjacent figure. Ensure the air curtain is as close to the door opening as possible for best performance, obstructions such as door opening devices, structural beams etc will reduce the performance.
Note the T-Recessed air curtain has a series of square punched air ventilation holes along one side panel of the unit which will be within the ceiling void once the unit is installed. There must be an air gap of 50mm minimum between these ventilation h oles and any obstruction/bulkhead within the ceiling void to allow ventilation air to easily enter the air curtain via these holes. Furthermore, the ceiling void must be sufficiently large and freely ventilated so there will be adequate supply of ventilation air (m the ceiling void is enclosed around the air curtain it will need an air ventilation grille of effective free area (cm enter the square punched air ventilation holes.
Table 1
Air curtain
2
) as given in Table 1 and an adequate air path within the void for air to
Required air flow within
ceiling void (m3/hr)
Effective free area of ventilation grille
for an enclosed ceiling void (cm2)
3
/hr) to the unit, see Table 1. If
T1000R 353 500 T1500R 421 700 T2000R 707 1200
Ceiling Suspension
For a standard width recess grille (436mm), make the cut-out in the ceiling to the dimensions given in Figure 1. The air curtain needs to be tipped on its side and angled upwards to fit through the ceiling cut-out, ensure there is sufficient height clearance in the ceiling void to do this. For an air curtain with a wider recess grille (476mm), make the cut-out in ceiling to the dimensions given in Figure 2. The air curtain will fit through the ceiling cut-out. Alternatively, the ceiling can be fitted after the air curtain has been installed.
Clearance holes for M10 threaded rod to enter from above are provided on the top face of the casing (4 x 1m and 6 x 1.5/2m models, for dimensions see Figure 1 or Figure 2) allowing the unit to be suspended. All
six suspension points must be used for 1.5m and 2m
models. Insert rod through each hole in top and attach onto each fixing bracket at lower edge of air curtain (see insert). Lock rod in place using M10 nut above and below fixing bracket (threaded rod and locking nuts are not provided). Ensure rod does not come below bottom face of unit.
Ensure each of the threaded rods is secured on to a suitable structure that can support the weight of the unit (for unit weights see Table 2)*.
4003155-9 UK Page 3 of 19
fixing bracket
Page 4
Electrical supply inlets suitable
for 25mm gland (1m & 1.5m)
LPHW connections
A
Rp 3/4 (3/4in.BSP female)
B B
Figure 1 - Standard Recess Grille
296
CEILING LEVEL
436
Electrical supply inlets suitable for 25mm
gland - 2m electric heating unit only.
140
55 314
Holes for M10
drop rods
2145
390
2190
1095
2240
T2000R
20-90mm
800
1650
T1500R
436 C
1150
1604
N/A
1104
1555
1055
390
390
T1000R
A(mm)
C(mm)
B(mm)
Width(mm)
Length(mm)
Cut-Out
in Ceiling
4003155-9 UK Page 4 of 19
Page 5
Electrical supply inlets suitable
for 25mm gland (1m & 1.5m)
LPHW connections
A
B B
Rp 3/4 (3/4in.BSP female)
Figure 2 - Wider Recess Grille
436
Electrical supply inlets suitable for 25mm
gland - 2m electric heating unit only.
Holes for M10
drop rods
2290
1095
296
CEILING LEVEL
35-100mm
476 C
T2000R
T1500R
T1000R
2240
1650
1150
A(mm)
800
1690
N/A
1190
C(mm)
B(mm)
2240
1650
1150
Length(mm)
140
55 314
436
436
436
Width(mm)
Cut-Out
in Ceiling
4003155-9 UK Page 5 of 19
Page 6
Note: When installing the air curtain ensure that the underside of the unit is 50mm above the bottom face of the ceiling tile/plasterboard. The recessed grille has an adjustment range from the underside of the air curtain to the exposed bottom face of the ceiling tile/plasterboard (see Figure 1 or Figure 2).
*It is the sole responsibility of the installer to ensure that the building fixing points and suspension system used are suitable for the air curtain being installed
Safety and Electrical Connections
All electrical wiring and connections MUST be carried out by a competent qualified electrician in accordance with the latest edition of the IEE wiring regulations and/or local statutory regulations.
A single phase or 3 phase local isolator with a contact separation of at least 3mm in all
poles must be fitted to the supply wiring (the isolator must be fitted in an accessible position).
The air curtain must be earthed.
The appliance must be connected by means of wires having an appropriate
temperature rating (heat resistant).
Ensure that the supply cables, circuit breakers and other electrical installation equipment
are correctly sized for the air curtain being installed; see Table 2.
On a 3 phase electrical supply the unit requires a neutral connection (3N~).
Cable glands used for the Electrical Input must be rated IP21 or higher.
Table 2
Air Curtain Electrical
Supply
Rated Power
Input (kW)
Current per
phase (A)
Heat Output
(kW)
Weight
(kg)
(V/ph/Hz)
T1000AR 230/1/50 0.25 1.1 N/A 27
T1500AR 230/1/50 0.35 1.7 N/A 40
T2000AR 230/1/50 0.45 2.0 N/A 50 T1000WR 230/1/50 0.25 1.1 12.0 29 T1500WR 230/1/50 0.35 1.7 18.0 42 T2000WR 230/1/50 0.45 2.0 24.0 53
T1000E9R 400/3/50 9.25 14.1 6.0/9.0 28
T1000E12R 400/3/50 12.25 18.7 6.0/12.0 28 T1500E12R 400/3/50 12.35 18.9 9.0/18.0 41 T1500E18R 400/3/50 18.35 27.9 6.0/12.0 41 T2000E18R 400/3/50 18.45 28.1 12.0/18.0 52 T2000E24R 400/3/50 24.45 36.8 12.0/24.0 52
4003155-9 UK Page 6 of 19
Page 7
Fitting of the Recessed Grille
The grille consists of a frame, grille core (fitted within
the frame) and four brackets (note: the brackets are fixed to the frame).
Removal of Grille Core
Prior to fitting the grille to the air curtain and the ceiling the grille core will need to be removed from its frame. Release the grille core by unfastening the two conical headed bolts fitted at each end of the grille core. Push against the spring loaded pins and the grille core can now be pulled clear of its frame.
Note: the grille core will still be attached to the frame via cord safety ties.
The rectangular hole in the ceiling must be sized to suit the grille frame, see Figure 1 or Figure 2 for dimensions.
Attaching the Grille to the Air Curtain
Before lifting the grille frame into position locate the four M6 bolts (two inside each end of the air curtain). Remove the M6 bolts and lift the frame into position (ensure that when fitted the air discharge vanes align with the air discharge of the air curtain, see Figure 1 or Figure 2), screw each M6 bolt through the slot in the grille bracket until all four are located into place. Adjust the height of the grille frame (via slots in brackets) so the frame fits nicely against the under side of the ceiling. Once the desired height is achieved tighten each M6 bolt in place locking the grille frame into the correct position.
Adjusting the Separator Plate
Within the air curtain there is a sliding separator plate, this needs adjusting up or down to stop the air discharge re-circulating within the air curtain. To adjust the separator plate release the M6 bolts at either end, extend the slide plate so that it will just touch the topside of the grille along its whole length and tighten the bolts. It will be necessary to fit the grille core to gauge where the separator plate should be fitted.
Fitting the Grille Core
Once the above is complete the grille core can be refitted, to do so locate each spring loaded pin in its locating hole, push against the spring loaded pins to allow the fixed pins to locate within their fixing holes. Tighten and secure the conical bolts fitted at each end of the grille core.
Once the ceiling is finished remove the protective plastic film from the recessed grille frame.
4003155-9 UK Page 7 of 19
Page 8
LPHW Models
For LPHW models ensure suitable water mains isolation valves are fitted in the flow and return pipework. When fitting the 3-port valve ensure that the pipe connections are fitted as detailed below and are in accordance with the manufacturers leaflet supplied with the valve.
Air Curtain Water Flow Rate (l/s)
Coil Water Pressure Drop (kPa)
82/72 °C
T1000WR 0.29 2.66 T1500WR 0.29 2.02 T2000WR 0.57 3.54
Ambient Models
Ambient units are supplied with a remote switch unit. The switch unit allows the air curtain to be powered ON/OFF and select one of three fan speeds.
4003155-9 UK Page 8 of 19
Page 9
Fitting/Connecting the Remote Control
The Ecopower Plus controller uses extra low voltage to communicate via the RJ control cable supplied. The controller should be located in a suitable place for easy access, it
can be fixed to the wall via various fixing slots provided in the back case or onto an electrical switch box (not provided). To mount controller onto an existing switch box, feed one end of the control cable through the switch box (see insert).
Using a screwdriver undo screw mounted on the top of the controller case. Pull the front case slightly forwards and lift the back case away.
Feed and secure the RJ control cable through one of the openings in the back case and secure back case to switch box using 2 x M3.5 mounting screws (not provided).
With the cable RJ plug locking clip lying nearest to controller PCB, connect the RJ plug to the RJ socket on the board.
Note: For controller DIP switch options refer to
Ecopower Plus Remote Control Operation and DIP Switch Settings.
Refit the controller front case to the back case. The air curtain end of the control cable should be connected to one RJ socket fitted either on the top panel for NT or the Ecopower motherboard inside a recessed air curtain. Ensure the control cable is safely secured.
Multiple Installation (Ecopower only)
To Master/Slave two or more air curtains together the remote control is plugged into the Master unit and a RJ lead should be connected from the Master to the Slave unit(s). Thermoscreens 3m RJ extension leads are available and must be ordered separately. Additional air curtains, up to a maximum of eight units, may be connected as indicated below. For Master/Slave configuration an independent mains supply as per Table 2 must be supplied to each air curtain.
4003155-9 UK Page 9 of 19
Page 10
Ecopower Controller Motherboard
Function
Fan Heat Interlock –
The heat output is governed by the fan speed. If low or medium fan speed is selected the heat output will operate on only first heat stage. Second stage heating will only
operate on high fan speed.
Disable Fan Run-on –
Disable fan run-on.
Thermostat Master –
Only the air sensor thermistor in the master air curtain will be used for measuring the reference air temperature for the whole master/slave installation.
Overheat Fan Disable –
If DIP4 is on and thermal cut-out(s) operate both heat and fan circuits are isolated and LED’s on wall switch flash. If DIP4 is off and thermal cut-out(s) operate, only the heating circuit is isolated and the LED’s on the wall switch flash.
Fan run-on time set two minutes.
- white rectangle indicates the moveable head of each 4 way DIP switch
Control
DIP1 Option
ON
OFF
1 2 3 4
DIP2 Option (LPHW & Ambient only)
ON
OFF
1 2 3 4
DIP3 Option
ON
OFF
1 2 3 4
DIP4 Option (Electric only)
ON
OFF
1 2 3 4
Built-in
Comments
Suitable on vertical electrically heated Designer air curtain. Maximum heat output achieved if maximum fan speed selected. Independently set-up DIP switch on each mother board. This feature operates in manual or auto mode.
Must only be used for LPHW and Ambient air curtains. Independently set-up DIP switch on each mother board.
The air sensor thermistors in all the slave air curtains will be ignored. This will then avoid situations on larger doorways with master/slave air curtains where some units can blow cold air whilst others can blow warm air, because they currently all refer to their own air sensor for control of the heat output of each air curtain. The master air curtain need not be the one that the wall control is plugged into. This dip switch setting must also be used for Global Switching (Master/Slave) via the INHIBIT terminal – see next page.
Independently set-up DIP switch on each mother board.
To remove fault, isolate electrical supply to air curtain, reset TOC and reconnect supply.
If “FAN ONLY” has been selected, at switch off, no fan run­on.
Standard
As supplied, for LPHW and Ambient the default setting would be for heat and fan settings to be independent (DIP1 OFF).
As supplied, the default setting would enable fan run-on (DIP2 OFF).
As supplied, the default setting would be for the air sensor thermistor on all units to be measuring (DIP3 OFF).
As supplied, the default setting would enable fan if TOC trips (DIP4 OFF).
4003155-9 UK Page 10 of 19
Page 11
DIP switches fitted on the Ecopower board provide a selection of optional features as described above. Isolate and switch electrical power off before configuring and/or changing any DIP switch settings.
Easy plug-in arrangement for remote air sensor thermistor on a 1m lead. Plugging-in the remote
air sensor to J3 disables the standard air sensor thermistor already fitted on the Ecopower board.
As supplied, the board will not have the remote air sensor fitted.
An INHIBIT two screw terminal fitted on the Ecopower board for BMS remote On/Off feature.
If the terminal is linked, i.e. by 2 wires to a remote volt free contact, the unit will run. If it is open circuit across the terminal the unit will switch off. This remote On/Off feature has global switching logic, i.e. if you master/slave several units together you need connect the remote contact to only one of them to turn all units on and off in the master/slave system. As supplied, a wire link will be fitted to the terminal block on every unit. For summer settings place a 3.3k resistance across the
INHIBIT terminal, with these settings fans only will run even if controller is requesting for heat.
Customer Building Management System
ECOPOWER BOARD
A HEALTHY two screw terminal is included on the board for a fault signal indication if the electric
elements overheat cut-out has operated. A healthy system provides a 24V DC signal at the terminals compared to an overheat fault which provides OV DC.
4003155-9 UK Page 11 of 19
Page 12
ON
1234
T1000E9R, T1000E12R, T1500E12R AND T1500E18R
4003155-9 UK Page 12 of 19
Page 13
ON
123
4
T2000E18R
ON
1234
T2000E24R
4003155-9 UK Page 13 of 19
Page 14
ON
4
123
T1000WR, T1500WR AND T2000WR
4003155-9 UK Page 14 of 19
Page 15
230V/1ph/50Hz
E
L
N
F1
(5A)
Red
Blue
Red
1
Red
Fan motor 1
Fan motor 2
(2m Only)
Orange
2
Violet
3
Brown
4
I
0
T1000AR, T1500AR AND T2000AR
4003155-9 UK Page 15 of 19
Page 16
Ecopower Plus Remote Control Operation and DIP Switch Settings
7
Heating Level Scale
6 4
3
5
1
2
On/Off (I/O)
Press On/Off switch (1) to turn the air curtain On and operate as follows:-
Press Auto switch (2) to cycle between Manual and Automatic modes. The Auto on indicator LED is lit for "Auto Mode" and un-lit for "Manual Mode".
Manual:
Heat output can be selected as Zero, Half Heat or Full Heat. Heating levels are selected by stepping up or down with switches (3) and (4). Heating level indicator LED's go 0%, 50% or 100% to show the level selected.
Automatic:
If DIP switches 1, 2 and 4 on the Ecopower motherboard are set to OFF, the air curtain measures the incoming air temperature and automatically selects the necessary amount of heat to keep it at the level selected.
Fan Speed
Switches (5), (6) and (7) select fan speed low, medium or high respectively. The appropriate LED above each fan speed indicator is illuminated to show which fan speed is selected.
Pressing the On/Off switch (1) again switches the air curtain off with all the LED’s switched off. If a heated air curtain is heating when switched off the fan will run-on at low fan speed for an extended time (approx. 2 minutes) to dissipate excess heat.
Do not switch the air curtain On/Off from the isolator. If the mains supply is
isolated or cuts-out during operation the safety thermal cut-out(s) for electric
heated air curtains within the air curtain may operate. If this happens the
thermal cut-out(s) will need to be reset by a competent technician.
DIP Switch Settings
At the back of the Ecopower Plus remote control PCB there are four DIP switches (see above) that provide the following optional features.
DIP1 Restart on Power-Up – If electrical
supply to the air curtain is interrupted, upon restoring electrical supply, the customer’s settings on the remote control will be retained. The default is with this feature ON.
DIP2 Stop Fan on Cold – Fans switch off
when heating level is achieved (Automatic mode only). The default setting is with this feature OFF.
DIP3 Never Blow Cold – Unit always
heats in Automatic mode (i.e. will not go to ambient mode). The default setting is with this feature OFF.
DIP4 Air Sensor in Controller – The air
sensor in the remote controller is enabled (DIP4 ON) and the air sensor on the Ecopower motherboard in the air curtain is disabled. Temperature control for Automatic Mode is then done at the remote control, which may be an advantage to limit overheating of the door entrance area. The default
setting is with this feature OFF.
4003155-9 UK Page 16 of 19
Page 17
Commissioning
Once the air curtain is functioning check that the fans operate at Low, Medium and High speeds, that there is no excessive mechanical noise coming from the fans and that all fans are working. If the unit is electric heated or water heated check that the air stream from the discharge grille warms up across the whole length of the air curtain when heating is selected. Check that heating increases as higher heat is selected and feel to see that the warm air stream is reaching across the doorway with door open or closed. If an Ecopower controller is being used check its operation in Manual Mode. Then select Auto Mode and increase the heating set point until the air stream warms up. Reduce the heating set point until the air stream goes cold.
Persons using the air curtain must be given adequate instruction and supervision concerning the use of the appliance by a person responsible for their safety. The air curtain is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities.
Explain to the end user that the doorway should be closed whenever possible but that during times of high pedestrian use it will become effectively ‘open doorway’. The air curtain serves an essential purpose by saving energy and providing comfort to the occupants when compared to an open doorway with no air curtain fitted.
Before leaving site it is important that the air curtain installation is “Handed-Over” to the end user or his representative and the operation of it is fully explained and that they understand how it operates. Explain also the service intervals and that the unit must be regularly cleaned and if it has filters fitted that these require regular cleaning/replacement.
Fault Conditions
In the event of a fault the thermal cut out(s) on electric heated units (Note: If the mains supply is isolated during operation then the thermal cut outs may operate) or internal fuses may
operate. The thermal cut out(s) are located upon the fan deck assembly inside the air curtain (one on the 1 & 1.5m and two on the 2m model). For Ecopower units two internal electrical fuses are located on the Ecopower board; 6.3A (T) supplies the fan motors within the air curtain and 125mA (F) controls the operation of the Ecopower board. For Ambient and Standard LPHW units the fuse is located within the control panel at the left hand end of the air curtain.
If for an electric heated air curtain an overheat fault occurs, or if J2 link is missing for LPHW models, the LED’s on the remote control will flash and the Ecopower board status LED on the board will be permanently red to indicate a fault.
In the case of a fault condition (refer to flowchart) do not attempt to reset the thermal cut outs or replace the fuses, arrange for a Thermoscreens appointed technician or certified electrician to attend the unit to investigate the reason why the thermal cut outs/fuse(s) have operated. Once the cause has been determined and rectified, they will reset/replace the thermal cut out/fuse and function test the unit.
PCB Status
Fitted on the PCB board inside of the air curtain is an LED shown as LED1 on wiring diagrams that will indicate the Ecopower control status.
1. LED flashing green – operation normal.
2. LED flashing red – low supply voltage or controller not plugged into Ecopower motherboard.
3. LED permanently red – thermal cut outs open circuit (electrically heated models) or J2 link missing (LPHW models). Remote Control LED’s will also flash to indicate the thermal cut-out(s) has operated or J2 link is missing.
Note to reset the thermal cut outs please refer to fault condition section detailed above.
4003155-9 UK Page 17 of 19
Page 18
User Fault Finding Flowchart (for Ecopower Control)
Service Agent to
reset thermal cut-
out(s)
Service Agent to
thermal cut-out(s)
investigate why
have operated
Is Electrical
Power
switched on
Yes
Are the fans
operating
correctly
Yes
Select heat output
No
No
Do the LED’s
light up on the remote
control
Yes
Switch on Electrical
Power
Connect remote control and push On/Off switch
to turn unit on
No
No
Is the remote
control plugged in and turned
on
Yes
Yes
Check if thermal
cut-out(s) have
tripped (Electric
Heated only)
No
Contact Installer
No
Contact Installer
Is the unit
discharging
warm air
Yes
Unit is working
satisfactorily
4003155-9 UK Page 18 of 19
Page 19
Service & Maintenance
Always disconnect and isolate the mains electricity supply before installing, maintaining or repairing this equipment. Note: All maintenance/repairs should only be carried out by a competent electrician or Thermoscreens appointed technician.
To ensure the air curtain operates at full efficiency the inlet/outlet grilles, fan impellers, housings and motors must be kept free of dust and debris. Build up of dust on the fan impellers can cause vibration, noise and excessive wear on the motor bearings.
Frequency of cleaning will depend on the environment, but we would recommend that the unit be cleaned a minimum of every 3 months (failure to adequately maintain the unit and provide a suitable cleaning schedule will result in performance degradation and reduce the life expectancy of the air-curtain).
Remove the grille core from the air curtain. Vacuum and clean the build-up of dirt and
debris within the air-curtain (please note that the motor(s) are permanently lubricated
and require no additional lubrication). If filters are fitted, ensure these are regularly inspected and cleaned or replaced. All dirty or blocked filters should be immediately replaced.
Once the air curtain has been cleaned check all electrical connections within the unit ensuring terminals are tight and that crimped connections have not become loose. Refit the grille core in the recessed grille. Reconnect the electrical supply and fully function test the air-curtain to ensure correct operation (See Commissioning).
Warranty
If any problems are encountered, please contact your installer/supplier. Failing this please contact the Thermoscreens warranty department. All units are covered by a two year warranty period.
Care has been taken in compiling these instructions to ensure they are correct, although Thermoscreens disclaims all liability for damage resulting from any inaccuracies and/or deficiencies in this documentation. Thermoscreens retain the right to change the specifications stated in these instructions.
Thermoscreens Ltd St. Mary’s Road Nuneaton Warwickshire England CV11 5AU
Email: sales@thermoscreens.com Tel: + 44 (0) 24 7638 4646 Fax: + 44 (0) 24 7638 8578
www.thermoscreens.com
4003155-9 UK Page 19 of 19
Loading...