Thermoscreens T Series, T2000AR, T1000AR, T1500AR, T1000WR Operation And Maintenance

...
Page 1
T Series.
Recessed Range
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
English
T9901012-1-1 UK (v9) Page | 1
Page 2
1. CONTENTS
Page
1. CONTENTS ...................................................................................................................................... 2
2. ELECTRICAL SAFETY ..................................................................................................................... 3
3. SPECIFICATIONS ............................................................................................................................ 3
4. INTRODUCTION .............................................................................................................................. 4
5. DELIVERY CONTENTS ................................................................................................................... 5
6. TOOLS REQUIRED .......................................................................................................................... 5
7. INSTALLATION ................................................................................................................................ 6
8. LPHW MODELS ............................................................................................................................... 9
9. REMOTE CONTROL INSTALLATION ........................................................................................... 10
10. REMOTE CONTROL SETTINGS ................................................................................................... 10
11. EXTERNAL CONTROLS ................................................................................................................ 11
12. MULTIPLE AIR CURTAIN SYSTEMS ............................................................................................ 12
13. SYSTEM CONFIGURATION .......................................................................................................... 13
14. FAN SPEED SELECTION .............................................................................................................. 14
15. REMOTE CONTROL OPERATION ................................................................................................ 15
16. COMMISSIONING THE SYSTEM .................................................................................................. 17
17. SIGN OFF ....................................................................................................................................... 17
18. FAULT CONDITIONS ..................................................................................................................... 18
19. SERVICE & MAINTENANCE ......................................................................................................... 19
20. WARRANTY ................................................................................................................................... 20
APPENDIX 1A — DIMENSIONS OF T RECESSED AIR CURTAIN WITH STANDARD RECESS
GRILLE ...................................................................................................................................................... 21
APPENDIX 1B — DIMENSIONS OF T RECESSED AIR CURTAIN WITH WIDER RECESS GRILLE ... 22
APPENDIX 2A — WIRING DIAGRAM T1000E9R, T1000E12R, T1500E12R AND T1500E18R ............ 23
APPENDIX 2B — WIRING DIAGRAM T2000E18R ................................................................................. 24
APPENDIX 2C — WIRING DIAGRAM T2000E24R ................................................................................. 25
APPENDIX 2D — WIRING DIAGRAM T1000WR, T1500WR and T2000WR ......................................... 26
APPENDIX 2E — WIRING DIAGRAM T1000AR, T1500AR and T2000AR ............................................. 27
20. DECLARATION OF CONFORMITY ............................................................................................... 28
T9901
012-1-1 UK (v9) Page | 2
Page 3
2. ELECTRICAL SAFETY
Electrical Supply and Wiring to the Air Curtain
All electri accordance with the latest edition of the IEE wiring regulations and/or local statutory regulations.
cal wiring and connections MUST be carried out by a competent qualified electrician in
A 1 phase or 3 phase local isolator having a contact separation of at least 3mm
s must be fitted in the electrical supply to the air curtain and located in an accessible
pole position adjac
Models operating on 3 phase electrical supply - see section 3: Specifications -
A 25mm size cable gland or conduit connector of IP21 rating or above should be used
See Wiring Diagram for connecting electrical supply and control ca
The appliance must be connected by cables having an appropriate heat resistan temperature rating.
All supply cables, circuit breakers and other electrical installation equipment mu
ctly sized for the air curtain model being installed; see section 3: Specifications.
corre
neutral con
the Electri
The air
ent to the unit.
nection (3N~).
cal Supply into the air curtain.
curtain must be ea
rthed.
bles to the air curtain.
on all
t
st be
require a
for
3. SPECIFICATIONS
Air Curtain
Model No
T1000AR 230/1/50 0.25 1.1 N/A 27 T1500AR 230/1/50 0.35 1.7 N/A 40
T2000AR 230/1/50 0.45 2.0 N/A 50 T1000WR 230/1/50 0.25 1.1 6.0 / 12.0 29 T1500WR 230/1/50 0.35 1.7 9.0 / 18.0 42 T2000WR 230/1/50 0.45 2.0 12.0 / 24.0 53
T1000E9R 400/3/50 9.25 14.1 6.0 / 9.0 28 T1000E12R 400/3/50 12.25 18.7 6.0 / 12.0 28 T1500E12R 400/3/50 12.35 18.9 6.0 / 12.0 41 T1500E18R 400/3/50 18.35 27.9 9.0 / 18.0 41 T2000E18R 400/3/50 18.45 28.1 12.0 / 18.0 52 T2000E24R 400/3/50 24.45 36.8 12.0 / 24.0 52
Electrical
Supply
(V/ph/Hz)
Rated
Electrical
Power Input
(kW)
Rated
Current
per phase
(A)
Heat Output
[Low/High]
(kW)
Weight
Table 1
(kg)
T9901
012-1-1 UK (v9) Page | 3
Page 4
4. INTRODUCTION
Established in the 1960s, Thermoscreens is a leading air curtain manufacturer that exports to over 60 countries worldwide.
As with all our products, the T recessed range of air curtains are designed with energy efficiency in mind.
T models suffixed ER, WR or AR are designed to be recess mounted inside a building and located horizontally over a doorway.
They must not be installed on the outside of a building.
Please complete the following details for your reference:
Date of Purchase Place of Purchase
Serial Number
Proof of purchase is required to make a claim under warranty.
Thermoscreens Ltd
St. Mary’s Road
Nuneaton
Warwickshire
England
CV11 5AU
Email: sales@thermoscreens.com — http://www.thermoscreens.com
Tel: +44 (0) 24 7638 4646 — Fax: +44 (0) 24 7638 8578
T9901012-1-1 UK (v9) Page | 4
Page 5
y
5. DELIVERY CONTENTS
The following items are supplied in the box at delivery.
NOTE: If any parts are missing or damaged contact your place of purchase.
T Recessed Air Curtain Ecopower Remote Control
Recessed Grille
The recessed grille is
supplied separately
(for Electric and Water Heated units)
Supplied with 6m RJ Control Cable
3-port control valve
(for water heated units)
Fitted in pipework to
air curtain b
installer
(Optional – supplied by Installer)
(disables heating on a warmer day)
Remote Control Switch
(for Ambient units)
Outdoor Air Thermostat
Used for simple weather
compensation control
6. TOOLS REQUIRED
The following tools are required for installation:
Flat blade screwd rivers  Pozi hea d screwdrivers  10mm spanner  Adjustable spanner
T9901012-1-1 UK (v9) Page | 5
 Electric drill  Ladders  Appro priate lifting equipment  Appropriate tools for cutting ceiling
aperture
Page 6
7. INSTALLATION
The air curtain is designed to be recessed within ceiling voids or bulkheads with in a building and located horizontally over a doorway. It must not be installed outside of the building.
7.1 Location
Mount the air curtain above and as close to the doorway as possible, with:
the recesse d grille not more than 3m above floor
level
the air discharge (see 1, Fig 1) section of the
recessed grille nearest the doorway and the air inlet section (see 2, Fig 1) furthest from the doorway
Beware of doorway top edges, structural beams, door opening/closure devices, etc., which may interfere with the air stream and affect the location of the unit.
NOTE: For the air curtain to work well the doorway should be less than the width of the airstream.
7.2 Ceiling Suspension
Step 1 Depending on whether a standard or wider width
recessed grille is used, cut an aperture in the ceiling to the dimensions in Appendices 1. Cut notches, if necessary, to clear screws in the air curtain casing.
NOTE: For LPHW models, pipework will need to be installed
Step 2 Fix M10 threaded rods (not supplied) through the 2
NOTE: Do not let the hanging rods come below the bottom
above the curtain. Allow sufficient access and height clearance within the ceiling void to do this.
holes at each end in the top casing (see Fig 2). Feed the rods through the casing and attach to fixing brackets near the bottom of the unit (see Fig 3, looking up into the air curtain). Use M10 lock-nuts either side of fixing brackets to secure hanging rods. An additional threaded rod is fitted on a 1.5m unit with two extra threaded rods fitted on a 2m unit, see Appendices 1.
of the unit casing or they may prevent the recessed grille fitting properly.
Fig 1
Fig 2
Fig 3
2
1
T9901012-1-1 UK (v9) Page | 6
Page 7
M10 hanging rods
RECESSED AIR CURTAIN
CEILING LEVEL CEILING LEVEL
25 - 50
Bottom surface of recessed air curtain casing
25 - 50
Fig 4
th
Step 3 If you are installing model T1500R, fit a 5
of the unit. For model T2000R, fit 5
th
M10 threaded rod into the hanging point in the middle
and 6th threaded rods, see Appendices 1 and Fig 4.
Step 4 Secure each rod to a suitable structure that can support the weight of the unit (see section 3:
Specifications for weights).
Step 5 Adjust the height of the unit on its hangi ng rods so the bottom surface of the casing goes
between 25-50mm up into the ceiling as shown in Fig 4. Ensure the unit is level.
WARNING: It is the sole responsibility of the installer to ensure that the fixing locations and
suspension system used are suitable for the air curtain being installed.
7.3 Attaching the recessed grille to the air curtain
The recessed grille consists of:
Metal frame Hinged standard or wider width inlet/discharge grille  Slotted fixing brackets
There are 4 fixing slotted brackets on the T1000R with 6 brackets fitted on T1500R and T2000R (see Fig 5a and Fig 5b).
Centre brackets for 1.5m and 2m
Fig 5a; standard width grille
Less angled bracket
Fig 5b; wider width grille
More angled bracket
Centre brackets for 1.5m and 2m
T9901012-1-1 UK (v9) Page | 7
Page 8
Fix the grille as follows:
Step 1 Open the hinged inlet grille using a flat bladed
screwdriver to release the quarter turn fasteners (see Fig 6). There are two fasteners on the T1000R unit and three fasteners on T1500R and T2000R units. Before lifting the grille frame into position, remove four (six on T1500R/T2000R) M6 bolts fitted on the inside edge of air curtain.
Step 2 Make sure the grille will go the correct way
around (discharge nearest to doorway). Offer the recessed grille up through the cut-out in the ceiling.
Step 3 Using the M6 bolts removed in Step 1, secure
grille by fixing each bolt through the slotted brackets as shown in Fig 8. For illustration purposes Fig 8 details a wider recess grille. With the hinged grille open, adjust the height of the grille frame via slots in each bracket, so frame is snug fit against the ceiling with no gaps all the way around.
Step 4 To stop discharge air re-circulating within the
air curtain a sliding separator will need adjusting up or down (see Fig 9). To adjust plate release M6 bolts either end, extend the slide plate so that it will touch the topside of the grille along its whole length and tighten the bolts. It will be necessary to close the hinged grille core to gauge where the separator plate should be fitted.
Step 5 Once the above steps are complete the
hinged grille core can be closed and all the quarter turn fasteners tightened up.
Fig 6
Fig 7
Fig 8
Fig 9
NOTE: Open the hinged grille core to gain access to
electrical connections, and for servicing and maintenance.
Fig 10
T9901012-1-1 UK (v9) Page | 8
Page 9
8. LPHW MODELS
For LPHW models ensure that water isolation valves are fitted in the flow and return pipework adjacent to the air curtain and connected correctly as shown in the diagram in Appendix 1.
For the design of the water pipework system and pump, water flow rates and pressure drops for maximum heat output of the air curtain are given in Table 2 below.
Air Curtain
Water Flow Rate
(l/min at 82/71°C)
Water Pressure Drop
(kPa)
T1000WR, 2-row (12kW) 15.6 16.1 T1500WR, 2-row (18kW) 23.4 10.4 T2000WR, 2-row (24kW) 31.2 16.3
Table 2
Air Curtain
Water Flow Rate
(l/min at 60/40°C)
Water Pressure Drop
(kPa)
T1000WR, 3-row (12kW) 8.6 8.3 T1500WR, 3-row (18kW) 12.9 18.2 T2000WR, 3-row (24kW) 17.1 15.0
NOTE: Water Pressure Drop is across the flow and return pipework to the air curtain and includes for the
coil fitted inside the unit and the valve fitted in the heating pipework to the unit. Water flow rates and pressure drops at different water temperatures can be calculated using the Thermoscreens coil calculation programme. Visit the Thermoscreens website for details.
The installer must connect the 3-port valve in the heating pipework as shown in Figure 11 below:
22mm pipe
22mm pipe
wire valve to pcb inside air curtain
22mm pipe
A
B
A/B
22mm pipe
R E T U R N
F L O
W
Fig 11
T9901012-1-1 UK (v9) Page | 9
Page 10
9. REMOTE CONTROL INSTALLATION
Mount the remote control unit in a convenient position directly to the wall or onto a switch box.
9.1 Wall mounting
Step 1 Using a screwdriver undo the screw on the top of the remote control
case and pull the back case away (see Fig 12).
Step 2 Feed one end of the RJ control cable through the back case, secure it,
then screw the back case to the wall using suitable fixings (not supplied).
Step 3 Connect the RJ plug to the RJ socket on the PCB in the remote control.
Step 4 Refit the front case.
9.2 Switch box mounting
Step 1 Using a screwdriver undo the screw on the top of the remote control case and pull the back
case away (see Fig 12).
Step 2 Feed one end of the RJ control cable through the switch box, feed and
secure the RJ control cable through the back case and secure ba ck case to switch box using 2 x M3.5 screws (not supplied) (see Fig 13).
Step 3 Connect the RJ plug to the RJ socket on the PCB in the remote control.
Step 4 Refit the front case.
Fig 12
Fig 13
NOTE: For optional remote control settings, see section 10.
10. REMOTE CONTROL SETTINGS
On the back of the PCB inside the Ecopower Remote Control you will find four DIP switches that provide the following optional features, see Table 3.
DIP Feature Explanation Default Notes
1 Reset on power-up On restoring power after an
electrical interruption all Remote Control settings are retained
2 Stop fan on cold Fans are switched off when
heating level is achieved (AUTO mode only)
3 Never blow cold Air curtain always h eats in
AUTO mode
4 Room air
temperature control
Enables the room air sensor in the Remote Control
ON WARNING! – Fans start
on their own after power is restored
OFF
OFF Will not go to ambient
mode
OFF Disables all other
temperature sensors
Table 3
T9901012-1-1 UK (v9) Page | 10
Page 11
11. EXTERNAL CONTROLS
11.1 Remote switch contacts IN0, IN1
Terminals IN0 and IN1 on the Ecopower PCB inside the air curtain can be used to provide different control strategies using remote volt-free contacts (see Fig 14). This could be to provide remote On/Off from a timer or BMS Digital/Output contact, to work with a door switch or for simple weather compensation control to disable heating when outdoor air temperatures become warmer. Table 4 describes the different functions:
Fig 14
Table 4
Function
Remote
On/Off
(INHIBIT)
Function
Door
Switch
Control
Summer
Winter
NOTE: Wire volt-free, remote switch contacts to 2-way screw terminals IN0 and IN1 using 2-core
WARNING: Do not apply any voltage to terminals IN0 and IN1 as this will damage the Ecopower
* NOTE: The Ecopower Remote Control must stay plugged-in for the air curtain to keep working.
Unit operates normally in MANUAL Mode or AUTO Mode from the Remote Control
After 30s the heating is disabled and the fan goes to low speed
Unit operates normally in MANUAL Mode or AUTO Mode from the Remote Control
COLD DAY
cable.
PCB inside the air curtain.
An optional plug-in EEPROM is available from Thermoscreens so the Remote Control can be un­plugged and the air curtain stay working. Visit the Thermoscreens website for details.
IN0
Unit switches off after 15s, with fan run-on at Medium fan speed if DIP 2 = OFF
IN1
Unit operates normally in MANUAL Mode or AUTO Mode from the Remote Control Heating is disabled straight away, Fan speeds operate normally from the Remote Control
WARM DAY
Notes
Use the Remote Control to set up unit and then hide it away if required. *
On/Off is then done via IN0 using a remote volt-free contact.
DIP 4 IN0 Notes
ON
OFF
Door Open:­ Normal Control
Door Closed:­ Heating Off Low Fan Speed Simple weather compensation control using an outdoor air thermostat with volt free contacts (see Section 11.3)
T9901012-1-1 UK (v9) Page | 11
Page 12
11.2 Overheat safety cut-out indication
g
A
For electric heated air curtains the Ecopower PCB includes a fault indication signal for if the overheat safety cut-out on the electric heater operates.
Volt free changeover contacts (6A 250VAC 30VDC) can be wired via the 3-way screw terminal “HEALTHY” (see Fig 15).
Refer to section 18.1: Overheat safety cut-out, for how to reset a overheat safety cut-out situation.
Fig 15
NO
HEALTHY
NC
LARM!
C
11.3 Weather compensation control (Summer/Winter)
To save heating energy on warmer days a simple weather compensation (Summer/Winter) heat control strategy can be used. Fit an outdoor air thermostat with volt-free contacts (supplied by the installer) to a north facing wall.
Use a 2-core cable to connect the outdoor air thermostat to 2-way terminal IN1 on the Ecopower PCB (see Fig 16)
On the Ecopower PCB, set DIP 4 to OFF as per Table 4, (see section 11.1: Remote switch contacts IN0, IN1).
Switch Contact Closed = Heating Enabled (cold day)
Switch Contact Open = Heating Disabled (warm day)
WARNING: Do not apply any voltage to terminal IN1 as this will damage the Ecopower PCB.
NOTE: To promote increased energy saving a more advanced weather compensation control strategy is available from
Thermoscreens. Using a heating curve, the discharge air temperature of the airstream coming from the air curtain is controlled a
ainst the outside air temperature. Visit the Thermoscreens website for details.
Fig 16
Outdoor Air Thermosta
12. MULTIPLE AIR CURTAIN SYSTEMS
For master/slave control, plug and connect units together with Thermoscreen RJ extension cables (not supplied) as per Figure 17 below. Each air curtain must have its own electrical supply.
T9901012-1-1 UK (v9) Page | 12
maximum 8 units
Fig 17
Page 13
13. SYSTEM CONFIGURATION
13.1 Optional features
WARNING: Isolate and di sconnect air curtain from the power source before making any changes.
DIP switches on the air curtain Ecopower PCB (see Fig 18) provide the following optional features, as explained below:
Fan heat inte rlock  Disable fan run-on  Thermostat master (for master/slave installations)  Weather compensation heat control (Summer/Winter)  Door switch control
Feature
DIP setting Default Notes
Fan heat interlock
Allows fan speed to govern heat output on electric heated units.
If low or medium fan speed is selected, a lower heat output
DIP 1
ON
1234
ON
Heat output is governed by fan speed.
results. High heat operates only on high fan speed.
Disable fan run-on
The 2 minute fan run-on after switch off is enabled or disabled on electric heated air curtains.
Thermostat master For master/slave installations. Only the air sensor in the thermostat master air curtain is used to measure air temperature.
DIP 2
ON
OFF
Fan run-on at
1234
DIP 3
ON
medium speed enabled.
OFF
Air curtains in master/slave
1234
systems all act
independently. Set DIP 3 to ON in the air curtain that will be the master unit.
Weather compensation control or Door switch control
Simple weather compensation control to save heating energy.
or
Door switch control.
NOTE: Black rectangle is moveable head of DIP switch.
NOTE: A range of advanced factory fitted and plug-in control options are available from Thermoscreens to
enhance the performance of the Ecopower PCB controller inside the air curtain. These include advanced weather compensation control using a heating curv e, outlet air temperature control, ECObus strategies. Visit the Thermoscreens website for details.
®
Modbus BMS control, modulating heater outputs and EEPROMs for non-standard control
DIP 4
ON
1234
OFF
IN1 Weather
compensation.
ON
IN1 Door switch.
Fig 18
This feature is only used with electric heated air curtains to limit very high air temperatures.
Set DIP1 to OFF if unit is water heated or ambient.
Must only be used for water heated or ambient air curtains. Each air curtain must have DIP2 set to ON for no fan run-on. Air sensor thermistors in all slave air curtains will be ignored.
Stops some units blowing cold air and others blowing warm air in master/slave systems on larger doorways. See section 11.1 Remote Switch Contacts IN0 and IN1 for details
Weather compensation control is the same as Summer/Winter control
T9901012-1-1 UK (v9) Page | 13
Page 14
14. FAN SPEED SELECTION
If required, select fan speed at commissioning to suit outdoor environmental conditions and indoor noise levels.
Factory settings for the 3 fan speeds are as follows:
HIGH fan speed (black wire) is wired into motor tapping
1 (highest motor speed tapping)
MEDIUM fan speed (blue wire) is wired into motor
tapping 3
LOW fan speed (red wire) is wired into motor tapping 4
Set fan speeds according to Table 5 below:
(refer also to wiring diagrams in Appendix 2)
motor tapping: 5 4 3 2 1
Fan Speed
(air curtain as
delivered)
HIGH
(black wire)
Motor Speed
Tapping
1 (highest speed)
Maximum air curtain
mounting height
(m)
3.0
Sound Pressure
Level of air
curtain
[dB(A) at 3m]
T1000R - 57 T1500R - 58 T2000R - 59
2 2.8
T1000R - 56 T1500R - 56 T2000R - 57
MEDIUM
(blue wire) 3 2.5
T1000R - 54 T1500R - 54 T2000R - 55
LOW
(red wire) 4 2.2
T1000R - 52 T1500R - 52 T2000R - 53
5 – (lowest speed) 2.0
T1000R - 50 T1500R - 51 T2000R - 52
Sound pressure levels dB(A) at 3m distance are for a single air curtain mounted at its maximum mounting height, operating in a room with average acoustic characteristics as defined in CIBSE Guide B5 (reverberation time 0.7s at 1kHz) and a room size equivalent to 8 air changes per hour (ac/h). Care needs to be taken when selecting air curtains for an installation as noise levels can be several dB higher if the mounting height is reduced, if the room is more ‘live’ (i.e. hard surfaces, no furnishings or absorbent materials), if the room is smaller than 8 ac/h equivalent or a combination of these factors. Noise levels will also increase if more than one air curtain is installed at the same doorway (e.g. +3dB(A) for 2 equal point sources: direct field).
Air Volume
Flow Rate
3
(m
/h)
[for E & A]
2000 3000 4000 1890 2685 3815 1730 2500 3570 1445 1990 3075 1255 1600 2765
T9901012-1-1 UK (v9) Page | 14
Page 15
15. REMOTE CONTROL OPERATION
15.1 Remote Control Switch (for Ambient units)
1 On/Off
Turns the air curtain fans On or Off.
2, 3 & 4 Fan speed
Switch fan speed between Low, Medium and High respectively.
3
4
2
1
T9901012-1-1 UK (v9) Page | 15
Page 16
15.2 Ecopower Remote Control (for Electric and Water Heated units)
7
1
Heating level scale
6 4
2
3
5
Use the remote control to operate the air curtain as follows:
1 On/Off
Turns the air curtain On or Off.
NOTE: If an electric heated air curtain is heating when switched off the fan will run-on for approximately 2 minutes to dissipate excess heat.
2 Manual/Automatic
Switches between Manual and Automatic modes. The Auto On indicator LED is lit for "Auto Mode" and unlit for "Manual Mode".
3 & 4 Heating level controls
Manual mode
Select heating level from zero, to half heat, to full heat by stepping up or down with the heating level controls. The heating level scale shows the level selected.
Automatic mode
Heat output is controlled automatically according to:
Inlet air temp erature, or  Room air temperature
This is dependent on the settings made in section 10: Remote Control Settings (DIP switch 4).
5, 6 & 7 Fan speed
Switch fan speed between Low, Medium and High respectively. The appropriate LED illuminates.
T9901012-1-1 UK (v9) Page | 16
Page 17
16. COMMISSIONING THE SYSTEM
16.1 Verify system operation
To commission the system, verify the following conditions are met:
All fans are working.  Fans operate at Low, Medium and High speeds.  There is no excessive mechanical noise coming from the fans.  When heating is selected, the air stream from the discharge grille warms up across the whole
length of the air curtain.
When set to manual with fans set to high speed, heating increases as higher heat is selected.  Warm air reaches across the doorway with door open or closed.  Ecopower Remote Control operates correctly in both manual and auto modes.
16.2 Instruct operator and hand over
Before leaving site, hand over the installation to the end user or their representative.
Explain that any person operating the air curtain must be given supervision and instruction by the person responsible for their safety, concerning the safe use of the unit and to understa nd any hazards involved. Children and those with reduced physical, sensory or mental capabilities should not operate the air curtain.
Recommend that the doorway should be closed whenever possible but that during times of high pedestrian use it will become an ‘open doorway’. The air curtain then serves an essential purpose by saving energy and providing comfort to occupants.
Explain that the inlet grilles and air filters (if fitted) must be cleaned regularly and the unit serviced at schedule intervals – see section 19: Service & Maintenance.
NOTE: Leave these instructions with the customer/end user or their representative!!
17. SIGN OFF
Complete the following once commissioning is completed.
Installer signature Customer signature Installer name
Customer name Installer company Customer company Date
Date
T9901012-1-1 UK (v9) Page | 17
Page 18
18. FAULT CONDITIONS
18.1 Overheat safety cut-out
An overheat fault in electric heated units may cause the overheat safety cut-out(s) to operate.
This is indicated by flashing LEDs on the remote control and a red status LED on the Ecopower PCB inside the air curtain.
Before resetting ensure there is adequate air flow from the air curtain and the unit has been commissioned as per Section 16.
To reset a overheat safety cut-out trip:
Step 1 Switch off the electrical supply to the air curtai n.
Step 2 Allow time for the air curtain to cool down; typically 10 minutes.
Step 3 Switch on the electri cal sup ply to the air curtain.
Step 4 Press the Auto button on the Ecopower remote control 4 times.
Air curtain heaters will then operate and after 30 seconds the LEDs on the remote control will stop flashing and the status LED on the Ecopower PCB in the air curtain will flash green.
18.2 Fuses
In the event of an electrical fault internal electrical fuses may operate.
There are two internal fuses located on the Ecopower PCB inside the air curtain:
Fuse 6.3A (T) supplies the fan motors within the air curtain  Fuse 100mA (F) controls the operation of the motherboard
18.3 Ecopower PCB status indication
There is a status LED on the Ecopower PCB inside the air curtain (See LED shown on Wiring Diagrams in the Appendix).
This indicates the status of the Ecopower Control system as follows:
1. LED flashing green – operation normal
2. LED flashing red – low supply voltage, remote control not plugged in or RJ cable fault
3. LED permanently red – overheat safety cut-out(s) open circuit from an overheat situation (see Section 18, Fault Conditions for how to reset)
T9901012-1-1 UK (v9) Page | 18
Page 19
19. SERVICE & MAINTENANCE
WARNING: Failure to adequately maintain the unit and provide a suitable cleaning schedule will
19.1 Every week
NOTE: Weekly maintenance can be carried out by the Cleaner or Janitor from floor level.
Turn off the air curtain to prevent dust entry, then clean the face of the recessed grille using a vacuum cleaner with an extension tube and brush.
19.2 Every 3 months
WARNING: Before servicing, isolate and disconnect the air curtain from the electrical power.
result in a loss of performance and reduced life expectancy of the air-curtain and possible overheating and fire risk with electric heated units.
WARNING: The following servicing and maintenance must be carried out by a competent
Clean and inspect the inside of the air curtain as follows:
Step 1 Open the hinged inlet grill e using a flat bladed screwdriver to release the quarter turn
Step 2 Clean and re move any build-up of dust and dirt within the air-curtain (inlet/outlet grilles,
NOTE: Build-up of dirt on fan impellers can cause vibration, noise and excessive wear on the
Step 3 Check within the unit to ensure all electrical connections and crimped terminals are tight
Step 4 On electric heated air curtains, remove the fan deck(s) as follows to inspect electric
heaters, electrical wiring and connections and to remove dust, dirt and debris:
Un clip the fan motor electrical connector.  Unfasten 4 x M6 nuts/bolts on each fan deck.  Unfasten M4 screws at bottom edge of fan deck.  Carefully lift the fan deck away from the air curtain.
Close and secure hinged inlet grille after servicing. Reconnect electrical supply and test to en sure correct operation (see Section 16: Commissioning).
electrician or a Thermoscreens appointed technician.
fasteners (see Fig 6, Section 7.3).
fan impellers, housings and motors) using a vacuum cleaner and soft brush.
motor bearings.
and that all cables are in good condition.
T9901012-1-1 UK (v9) Page | 19
Page 20
20. WARRANTY
All units are covered by a two year warranty.
Failure to adequately maintain the unit may void the warranty. If any problems are encountered, please contact your installer/supplier.
If any problems are encountered, please contact your installer/supplier.
Failing this please contact the Thermoscreens warranty department.
Care has been taken in compiling these instructions to ensure they are correct. Therm oscreens Ltd. disclaims all liability for damage resulting from any inaccuracies and/or deficiencies in this documentation. Thermoscreens Ltd. retain the right to change the specifications stated in these instructions.
Thermoscreens Ltd Email: sales@thermoscreens.com St. Mary’s Road Nuneaton Tel: + 44 (0) 24 7638 4646 Warwickshire England Fax: + 44 (0) 24 7638 8578 CV11 5AU www.thermoscreens.com
T9901012-1-1 UK (v9) Page | 20
Page 21
P S B .
n
i
4
3
p R
WITH STANDARD RECESS GRILLE
APPENDIX 1A — DIMENSIONS OF T RECESSED AIR CURTAIN
T9901012-1-1 UK (v9) Page | 21
Page 22
P S B .
n
i
4
3
p R
WITH WIDER RECESS GRILLE
APPENDIX 1B — DIMENSIONS OF T RECESSED AIR CURTAIN
T9901012-1-1 UK (v9) Page | 22
Page 23
Red
Healthy
Alarm
1m9 - 1 kW (x3) 1m12, 1.5m12 - 2 kW (x3)
1.5m18 - 3 kW (x3)
1m9, 1m12, 1.5m12 - 2 kW (x3)
1.5m18 - 3 kW (x3)
F1 = F100mA F2 = T6.3A
J1
NC C NO
J2
LED
White
Brown
F2 F1
1
Th
J10
J12
Black BlackBlack Black
(top elements)
Second Stage Heating
(bottom elements)
First Stage Heating
Capacitor:
1m - 2.5µF
1.5m - 6µF
1~
Fan Motor 1
Orange
Brown (High)
Violet
1
Grey
2
345
Blue
Red (Low)
Red
T1500E18R
Blue (COMMON)
0
White
Black
Yellow
White
Yellow
White
Yellow
Black
4
2
3
L1
J14
Grey
Blue
8
6
5 L2
9
7
10 N
L3
J16
TERMINAL
IN1 IN0
J9
ON
J6
R0 -10V
or Door Contact
J5
1234
Low speed
ECO-Power CVR1008-9
0V
J17
White
0V
Med speed
Low speed
Med speed
High speed
Black
Blue
Red
J11
High speed
Fan 2 Fan 1
EEPROM
Brown
55°C Auto
Thermal Trip
Grey
Black
Blue
Summer/Winter
WIRING DIAGRAM T1000E9R, T1000E12R, T1500E12R AND
Black rectangle is
moveable head of
L2
L2
L3
L3
N
E
N
a
l S
/
r
e
t
s
a M
e
l
b
a C e
v
REMOTE
L1
BLOCK
L1
E
DIP switch
CONTROL
400V / 3ph / 50Hz
To Slave
Air Curtain
APPENDIX 2A
T9901012-1-1 UK (v9) Page | 23
Page 24
White
White
White
Blue
Brown Black Grey
A1
13NO
5 3
230V AC Coil
CONTACTOR
1
Black Black
1 kW (x3) 1 kW (x3)
A2
14NO
6 4 2
2 kW (x3) 2 kW (x3)
Yellow
Yellow
Yellow
Black Black
1~
Fan Motor 1
Orange
Violet
Brown (High)
Blue (COMMON)
Grey
2
0
345
1
Black Black
(top elements)
Second Stage Heating
Black Black
(bottom elements)
First Stage Heating
2.5µF
Capacitor:
Red (Low)
TERMINAL
White
Black
Blue
Red
F1 = F100mA F2 = T6.3A
Summer/Winter
or Door Contact
R0 -10V
J5
J1
F2 F1
NC C NO
Th
J2
LED
IN0
IN1
J9
J6
e
l
b
a C e
v
a
l
S
/
r
e
t
REMOTE
s
a M
Healthy
Alarm
Red
(x2)
55°C Auto
Thermal Trip
E
N
L1
L2
L1
L2
L3
L3
E
N
BLOCK
White
J10
ON
1234
EEPROM
Black rectangle is
CONTROL
Brown
1
J12
J11
moveable head of
Yellow
2
3
L1
Black
DIP switch
White
High speed
Fan 2 Fan 1
Blue
White
Grey
Black
4
6
5 L2
J14
Blue
9
8
7
10 N
L3
J16
2.5µF
Capacitor:
Fan Motor 2
1~
(COMMON)
Orange
Violet
Brown (High)
1
Black
Grey
234
Blue
Red
Red (Low)
5
Blue
0
White
Low speed
0V
White
ECO-Power CVR1008-9
J17
0V
Low speed
Med speed
High speed
Med speed
White
Black
Blue
Red
Red
APPENDIX 2B — WIRING DIAGRAM T2000E18R
400V / 3ph / 50Hz
To Slave
Air Curtain
T9901012-1-1 UK (v9) Page | 24
Page 25
A1
A2
13NO
Brown Black Grey
14NO
5
6
4
3
230V AC Coil
CONTACTOR
1
2
2 kW (x3) 2 kW (x3)
White
White
White
Black Black
Black Black
(top elements)
Second Stage Heating
A1
Blue
Brown Black Grey
A2
13NO
14NO
6
5
4
3
230V AC Coil
CONTACTOR
1
2
2 kW (x3) 2 kW (x3)
Yellow
Yellow
Yellow
Black Black
Black Black
(bottom elements)
First Stage Heating
1~
Fan Motor 1
Brown (High)
Violet
Blue (COMMON)
Grey
012
345
2.5µF
Capacitor:
Orange
Red (Low)
White
Black
Blue
Red
F1 = F100mA F2 = T6.3A
Healthy
Alarm
Red
(x2)
55°C Auto
Thermal Trip
E
L2
L2
L3
L3
N
E
N
L1
BLOCK
TERMINAL
L1
J1
F2 F1
NC C NO
Th
J2
LED
IN0
IN1
J9
J6
R 0 -10V
Summer/Winter
or Door Contact
J5
e
l
b
a C
e
v
a
l S
/
r e
t
REMOTE
s
a M
ON
1234
CONTROL
Yellow
White
Brown
1
J10
EEPROM
moveable head of
Black rectangle is
2 L1
J12
J11
DIP switch
4
3
5 L2
J14
Low speed
High speed
Med speed
Fan 2 Fan 1
Black
Blue
Red
6
0V
White
High speed
Black
Blue
Blue
9
8
7
10 N
L3
J16
Capacitor:
2.5µF
Fan Motor 2
1~
(COMMON)
Orange
Violet
Brown (High)
ECO-Power CVR1008-9
0V
Low speed
Med speed
J17
White
Red
Blue
012
White
Grey
Black
345
Blue
Red
Red (Low)
APPENDIX 2C — WIRING DIAGRAM T2000E24R
400V / 3ph / 50Hz
To Slave
Air Curtain
T9901012-1-1 UK (v9) Page | 25
Page 26
3 PORT VALVE
Summer/Winter
White
Orange
Grey
1
F1 = F100mA F2 = T6.3A
J1
F2 F1
NC C NO
J2
LED
IN1 IN0
J6
R 0 -10V
or Door Contact
J5
Green/Yellow
Blue
4
2
3
E
White
Black
Brown
1
Th
J10
J12
J9
ON
1234
EEPROM
J11
2
3
L1
4
6
5 L2
J14
0V
Med speed
Low speed
High speed
Fan 2 Fan 1
High speed
7
Med speed
Low speed
Fan Motor 1
Blue (COMMON)
White
Blue
9
8
10 N
L3
J16
ECO-Power CVR1008-9
0V
J17
1~
Capacitor:
1m - 2.5µF
1.5m - 6µF
Orange
Violet
Brown (High)
0
Black
1
Grey
234
Red (Low)
5
Blue
Red
Fan Motor 2 (2m only)
1~
2.5µF
Violet
234
Orange
Capacitor:
Red (Low)
5
(COMMON)
Blue
Brown (High)
Grey
0
1
White
Black
Blue
Red
White
Black
Blue
Red
TERMINAL
White
Black
Blue
Red
Black rectangle is
moveable head of
L
EE
N
BLOCK
L
N
le
b
a
C
e
v
a
l
S
/
r
e
t
REMOTE
s
a
M
DIP switch
CONTROL
230V / 1ph / 50Hz
To Slave
Air Curtain
T9901012-1-1 UK (v9) Page | 26
APPENDIX 2D — WIRING DIAGRAM T1000WR, T1500WR and T2000WR
Page 27
1~
Capacitor:
1m - 2.5µF
Fan Motor 1
1.5m - 6µF
1~
2.5µF
Capacitor:
Orange
Violet
Brown (High)
Blue (COMMON)
Grey
0
1
2
Red (Low)
345
Brown (High)
Blue (COMMON)
0
Orange
Violet
2
Red (Low)
345
Grey
1
Fan Motor 2 (2m only)
White
Black
Blue
Red
White
F1 (5A)
Brown
Red
Blue
Black
White
Black
Blue
Red
1
L
E
NN
BLOCK
TERMINAL
L
E
230V / 1ph / 50Hz
4
2
3
Switch
Control
Remote
21 3
I
0
4
Low speed
Medium speed
High speed
65 7
On/Off
8
Fan
Speed
APPENDIX 2E — WIRING DIAGRAM T1000AR, T1500AR and T2000AR
T9901012-1-1 UK (v9) Page | 27
Page 28
20. DECLARATION OF CONFORMITY
Thermoscreens Ltd. St. Mary’s Road Nuneaton Warwickshire CV11 5AU United Kingdom Telephone: +44 (0)24 7638 4646 www.thermoscreens.com
EC DECLARA
as defined by the EC Council Directive on Machinery 2006/42/EC,
the Low Voltage Directive 2006/95/EC, Electromagnetic Compatibility Directive 2004/108/EC,
the Energy related Products Directive 2009/125/EC
Herewith we declare that the air movement equipment designated below, on the basis of its design and construction in the form brought onto the market by us in accordance with the relevant safety, health and performance requirements of the Machinery. If alterations are made to the machinery without prior consultations with us, this declaration becomes invalid.
Designation of Equipment: AIR CURTAINS Series Type: T1000A; T1000E9; T1000E 12; T1000W; T1500A; T1500E12;
T1500E18; T1500W; T2000A; T2000E18; T2000E24; T2000W (in Casing Styles: Recessed)
Relevant EC Council the Machinery Directive (2006/42/EC) Directives: the Low Voltage Directive (2006/95/EC)
the Electromagnetic Compatibility Directive (2004/108/EC) the Energy related Products Directive (2009/125/EC)
Applied Harmonised Machinery - EN ISO 14121-1:2007, EN 294:1992, EN 414:2000 Standards: LVD - EN 60335-1:2012, EN 60335-2-30:2009+A11:2012
EMC - EN 61000-6-1:2007, EN 61000-6-3:2007+A1:2011, ErP - Commission Regulation (EU) No.327/2011,
TION OF CONFORMITY
EN 61000-3-2:2006+A2:2009, EN 61000-3-3:2008 ISO 5801:2007, ISO 12759:2010
Basis of Self Attestation: Quality Assurance to BS EN ISO 9001: 2008
B.S.I. Registered Firm Certificate Number FM 85224 SGS Test Report ELS150049/2/R/DC/11; SGS Test Report EMC150049/1 CE Marking Association Test Report 6799 and 6800
Responsible Person: Mr. P.Casey, Operations Director, Thermoscreens Ltd. Date: 20 March 2014
Signed:
T9901012-1-1 UK (v9) Page | 28
Loading...