2 ELECTRICAL SAFETY
Electrical Supply and Wiring to the Air Curtain
All electrical wiring and connections MUST be carried out by a competent qualified electrici an in
accordance with the latest edition of national and local wiring regulations and/or local statutory
regulations.
A 1 phase or 3 phase local isolator having a contact separation of at least 3mm on all poles
must be fitted in the electrical supply to the air curtain and located in an accessible position
adjacent to the unit.
The appliance must be connected by cables having an appropriate heat resistant temperature
rating.
All supply cables, circuit breakers and other electrical installation equipment must be correctly
sized for the air curtain model being installed; see section 3: Specifications.
Models operating on a 3 phase electrical supply - see section 3: Specifications - require a
neutral connection (3N~).
A 25mm size cable gland or conduit connector of IP21 rating or above should be used for the
Electrical Supply into the air curtain.
See Wiring Diagrams for connecting electrical supply and control cables to the air curtain. The
The air curtain is designed to be located horizontally over a doorway. It must not be installed outside of
the building.
7.1 Location
Mount the air curtain above and as close to the doorway as
possible, with:
the discharge grille not more than 3m above floor level
at least 100mm clearance (air gap) above electric/water
heated air curtains, see Fig 1
Beware of doorway top edges, structural beams, door
opening/closure devices, etc., which may interfere with the air
stream and affect the location of the unit.
NOTE: For the air curtain to work well the width of the open doorway should be less than the length
‘A’ of the air curtain, see Appendix 1.
100mm
3000mm
Fig 1
7.2 Wall Fixing
NOTE: Use suitable wall fixing bolts (not supplied) to fix the unit to the wall, taking into account the
Step 1 Bolt all wall brackets to the rear face of the unit
Step 2 Drill fixing points in the wall, referring to
Step 3 Screw in the top wall bolts leaving a small gap
Step 4 Lower the unit onto the bolts via the key-hole
Step 5 Tighten all fixing bolts until the air curtain is
type of wall and the weight of the unit (see Section 3: Specifications).
as shown in Fig 2, using the M6fixing bolts
supplied.
Appendix 1 for correct positioning.
between the screw head and the wall.
slots in the top of the wall brackets and screw in
the bottom wall bolts.
Fig 2
safely secured to the wall.
T9901009-1-1 UK (v9) Page | 6
Page 7
7.3 Ceiling Suspension
M10 threaded rods (not supplied) are used to suspend the
unit from the ceiling.
Suspend the unit from the ceiling as follows:
Step 1 Screw the threaded rods into all of the holes in the
top face of the unit as shown in Fig 3.
NOTE: Do not screw hanging rods too far in as they
Step 2 Fit M10 locking nuts (not provided) to prevent the
Step 3 Secure each suspension rod to a suitable structure that can support the weight of the unit (see
WARNING: It is the sole responsibility of the installer to ensure that the fixing locations and
could interfere with internal components.
rod rotating and coming away from the casing.
section 3: Specifications for weights).
suspension system used are suitable for the air curtain being installed.
Fig 3
7.4 LPHW Models
For LPHW models ensure that water isolation valves are fitted in the flow and return pipework
adjacent to the air curtain and connected correctly as shown in the diagram in Appendix 1.
For the design of the water pipework system and pump, water flow rates and pressure drops for
maximum heat output of the air curtain are given in Table 2 below.
Air Curtain Water Flow Rate
(l/min at 82/71°C)
T1000W, 2-row
(9kW)
T1500W, 2-row
(12kW)
T2000W, 2-row
(18kW)
NOTE: Water Pressure Drop is across the flow and return pipework to the air curtain and includes for the
coil fitted inside the unit and the valve fitted in the heating pipework to the unit.
Water flow rates and pressure drops at different water temperatures can be calculated using the
Thermoscreens coil calculation programme. Visit the Thermoscreens website for details.
11.7 9.0
15.6 16.6
23.4 12.5
Water Pressure Drop
(kPa)
Table 2
T9901009-1-1 UK (v9) Page | 7
Page 8
The installer must connect the 3-port valve in the heating pipework as shown in Figure 4 below:
22mm pipe
R
22mm pipe
wire valve to pcb inside air curtain
22mm pipe
A
B
A/B
22mm pipe
F
E
L
T
O
U
W
R
N
Fig 4
8. ACCESS TO ELECTRICAL CONNECTIONS
8.1 How to access terminals
To gain access to the air curtain for connection and commissioning, remove air inlet grilles and bottom
access panel as explained below.
First remove the plastic end caps at each end of the unit, if fitted, by pulling off to the side.
NOTE: All air curtain panels are protected in a plastic film. When access panels are removed this
8.1.1 Remove air inlet grilles
Using a Pozi No 1 screwdriver, remove each grill with its filter.
To remove, insert screwdriver into the elongated hole at the bottom
corner of the grille (see Fig 5) and turn the screw one quarter of a turn
anticlockwise.
8.1.2 Remove bottom access panel
Unfasten the securing screw at each end (see 1, Fig 6) and, if
applicable, two screws in the centre (T1500 and T2000 units only).
To remove, slide the access panel (see 2, Fig 6) out forwards.
film can be removed.
Fig 5
Fig 6
1
2
T9901009-1-1 UK (v9) Page | 8
Page 9
9. REMOTE CONTROL INSTALLATION
Mount the Ecopower remote control in a convenient position directly to the wall or onto a switch box.
9.1 Wall mounting
Step 1 Using a screwdriver undo the scre w on the top of the remote control
case and pull the back case away (see Fig 7).
Step 2 Feed one end of the RJ control cable through the back case, secure it,
then screw the back case to the wall using suitable fixings (not
supplied).
Step 3 Connect the RJ plug to the RJ socket on the PCB in the remote control.
Step 4 Refit the front case.
9.2 Switch box mounting
Step 1 Using a screwdriver undo the screw on the top of the remote control case and pull the back
case away (see Fig 7).
Step 2 Feed one end of the RJ control cable through the switch box, feed and
secure the RJ control cable through the back case and secure ba ck
case to switch box using 2 mounting screws (not supplied) (see Fig 8).
Step 3 Connect the RJ plug to the RJ socket on the PCB in the remote
control.
Step 4 Refit the front case.
NOTE: For optional remote control settings see Section 10.
Fig 7
Fig 8
10. REMOTE CONTROL SETTINGS
On the back of the PCB inside the Ecopower Remote Control you will find four DIP switches that
provide the following optional features, see Table 3:
DIP Feature Explanation Default Notes
1 Reset on power-up On restoring power after an
electrical interruption all Remote
Control settings are retained
2 Stop fan on cold Fans are switched off when
heating level is achieved (AUTO
mode only)
3 Never blow cold Air curtain always heats in
AUTO mode
4 Room air
temperature control
T9901009-1-1 UK (v9) Page | 9
Enables the room air sensor in
the Remote Control
ON WARNING! – Fans start
on their own after power
is restored
OFF
OFF Will not go to ambient
mode
OFF Disables all other
temperature sensors
Table 3
Page 10
11. EXTERNAL CONTROLS
11.1 Remote switch contacts IN0, IN1
Terminals IN0 and IN1 on the Ecopower PCB inside the air
curtain can be used to provide different control strategies
using remote volt-free contacts (see Fig 9). This could be to
provide remote On/Off from a timer or BMS Digital/Output
contact, to work with a door switch or for simple weather
compensation control to disable heating when outdoor air
temperatures become warmer. Table 4 describes the
different functions:
Fig 9
Table 4
Function
Remote
On/Off
(INHIBIT)
Function
Door
Switch
Control
Summer
Winter
NOTE: Wire volt-free, remote switch contacts to 2-way screw terminals IN0 and IN1 using 2-core
WARNING: Do not apply any voltage to terminals IN0 and IN1 as this will damage the Ecopower
* NOTE: The Ecopower Remote Control must stay plugged-in for the air curtain to keep working.
Unit operates
normally in
MANUAL Mode or
AUTO Mode
from the Remote
Control
After 30s the
heating is disabled
and the fan goes to
low speed
Unit operates
normally in
MANUAL Mode or
AUTO Mode
from the Remote
Control
COLD DAY
cable.
PCB inside the air curtain.
An optional plug-in EEPROM is available from Thermoscreens so the Remote Control can be unplugged and the air curtain stay working. Visit the Thermoscreens website for details.
IN0
Unit switches off
after 15s, with fan
run-on at Medium
fan speed if
DIP 2 = OFF
IN1
Unit operates
normally in
MANUAL Mode or
AUTO Mode
from the Remote
Control
Heating is disabled
straight away,
Fan speeds
operate normally
from the Remote
Control
WARM DAY
Notes
Use the Remote Control to set up unit and
then hide it away if required. *
On/Off is then done via IN0 using a remote
volt-free contact.
DIP 4 IN0 Notes
ON
OFF
Door Open: Normal Control
Door Closed: Heating Off
Low Fan Speed
Simple weather
compensation control
using an outdoor air
thermostat with volt free
contacts
(see Section 11.3)
T9901009-1-1 UK (v9) Page | 10
Page 11
11.2 Overheat safety cut-out indication
g
A
t
For electric heated air curtains the Ecopower
PCB includes a fault indication signal for if the
overheat safety cut-out on the electric heater
operates.
Volt free changeover contacts (6A 250VAC
30VDC) can be wired via the 3-way screw
terminal “HEALTHY” (see Fig 10).
Refer to Section 18.1: Overheat Safety cut
out, for how to reset a overheat safety cut-out
situation.
Fig 10
NO
HEALTHY
NC
LARM!
C
11.3 Weather compensation control (Summer/Winter)
To save heating energy on warmer days a simple weather
compensation (Summer/Winter) heat control strategy can
be used. Fit an outdoor air thermostat with volt-free
contacts (supplied by the installer) to a north facing wall.
Use a 2-core cable to connect the outdoor air thermostat to
2-way terminal IN1 on the Ecopower PCB (see Fig 11)
On the Ecopower PCB, set DIP 4 to OFFas per Table 4,
(see Section 11.1: Remote switch contacts IN0, IN1).
WARNING: Do not apply any voltage to terminal IN1 as this will damage the Ecopower PCB.
NOTE: To promote increased energy saving a more advanced weather compensation control strategy is available from
Thermoscreens. Using a heating curve, the discharge air temperature of the airstream coming from the air curtain
is controlled a
ainst the outside air temperature. Visit the Thermoscreens website for details.
Fig 11
Outdoor Air
Thermosta
12. MULTIPLE AIR CURTAIN SYSTEMS
For master/slave control, plug and connect units together with Thermoscreen RJ extension cables (not
supplied) as per Figure 12 below. Each air curtain must have its own electrical supply.
maximum 8 units
Fig 12
T9901009-1-1 UK (v9) Page | 11
Page 12
13. SYSTEM CONFIGURATION
13.1 Optional features
WARNING: Isolate and disconnect air curtain from the power source before making any changes.
DIP switches on the air curtain Ecopower PCB (see Fig 13) provide
the following optional features, as explained below:
Fan heat interlock
Disable fan run-on
Thermostat master (for master/slave installations)
Weather compensation heat control (Summer/Winter)
Door switch control
Feature
DIP setting Default Notes
Fan heat interlock
Allows fan speed to govern heat
output on electric heated units.
If low or medium fan speed is
selected, a lower heat output
DIP 1
ON
1234
ON
Heat output is
governed by fan
speed.
results. High heat operates only
on high fan speed.
Disable fan run-on
The 2 minute fan run-on after
switch off is enabled or disabled
on electric heated air curtains.
Thermostat master
For master/slave installations.
Only the air sensor in the
thermostat master air curtain is
used to measure air temperature.
DIP 2
ON
OFF
Fan run-on at
1234
DIP 3
ON
medium speed
enabled.
OFF
Air curtains in
master/slave
1234
systems all act
independently.
Set DIP 3 to ON in the air curtain
that will be the master unit.
Weather compensation control
or Door switch control
Simple weather compensation
control to save heating energy.
or
Door switch control.
NOTE: Black rectangle is moveable head of DIP switch.
NOTE: A range ofadvanced factory fitted and plug-in control options are available from Thermoscreens to
enhance the performance of the Ecopower PCB controller inside the air curtain. These include
advanced weather compensation control using a heating curv e, outlet air temperature control,
ECObus
strategies. Visit the Thermoscreens website for details.
®
Modbus BMS control, modulating heater outputs and EEPROMs for non-standard control
DIP 4
ON
1234
OFF
IN1 Weather
compensation
ON
IN1 Door switch
Fig 13
This feature is only used with
electric heated air curtains to
limit very high air
temperatures.
Set DIP1 to OFF if unit is
water heated or ambient.
Must only be used for water
heated or ambient air
curtains. Each air curtain
must have DIP2 set to ON for
no fan run-on.
Air sensor thermistors in all
slave air curtains will be
ignored.
Stops some units blowing
cold air and others blowing
warm air in master/slave
systems on larger doorways.
See section 11.1 Remote
Switch Contacts IN0 and IN1
for details
Weather compensation
control is the same as
Summer/Winter control
T9901009-1-1 UK (v9) Page | 12
Page 13
14. FAN SPEED SELECTION
If required, select fan speed at commissioning to suit outdoor environmental conditions and indoor
noise levels.
Factory settings for the 3 fan speeds are as follows:
HIGH fan speed (black wire) is wired into motor tapping
2
MEDIUM fan speed (blue wire) is wired into motor
tapping 3
LOW fan speed (red wire) is wired into motor tapping 4
Set fan speeds according to Table 5 below:
(refer also to wiring diagrams in Appendix 2)
motor tapping: 54321
Fan Speed
(air curtain as
delivered)
Motor Speed
Tapping
1 (highest speed)
Maximum air curtain
mounting height
(m)
3.0
Sound Pressure
Level of air
curtain
[dB(A) at 3m]
T1000 - 57
T1500 - 58
T2000 - 58
HIGH
(black wire)
2
2.8
T1000 - 56
T1500 - 57
T2000 - 57
MEDIUM
(blue wire)
3
2.5
T1000 - 55
T1500 - 56
T2000 - 56
LOW
(red wire)
4
2.2
T1000 - 54
T1500 - 55
T2000 - 54
5 – (lowest speed)
2.0
T1000 - 51
T1500 - 52
T2000 - 53
Sound pressure levels dB(A) at 3m distance are for a single air curtain mounted at its maximum mounting height, operating in a
room with average acoustic characteristics as defined in CIBSE Guide B5 (reverberation time 0.7s at 1kHz) and a room size
equivalent to 8 air changes per hour (ac/h). Care needs to be taken when selecting air curtains for an installation as noise levels
can be several dB higher if the mounting height is reduced, if the room is more ‘live’ (i.e. hard surfaces, no furnishings or
absorbent materials), if the room is smaller than 8 ac/h equivalent or a combination of these factors. Noise levels will also increase
if more than one air curtain is installed at the same doorway (e.g. +3dB(A) for 2 equal point sources: direct field).
Switch fan speed between Low, Medium and High respectively.
3
4
2
1
T9901009-1-1 UK (v9) Page | 14
Page 15
15.2 Ecopower Remote Control (for Electric and Water Heated units)
Use the Remote Control to operate the air curtain as follows:
1
2
7
Heating level scale
6
4
3
5
1 On/Off
Turns the air curtain On or Off.
NOTE: If an electric heated air curtain is heating when switched off the fan will run-on for
approximately 2 minutes to dissipate excess heat.
2 Manual/Automatic
Switches between Manual and Automatic modes.
The Auto On indicator LED is lit for "Auto Mode" and unlit for "Manual Mode".
3 & 4 Heating level controls
Manual mode
Select heating level from zero, to half heat, to full heat by stepping up or down with the heating level
controls. The heating level scale shows the level selected.
Automatic mode
Heat output is controlled automatically according to:
Inlet air temperature, or
Room air temperature
This is dependent on the settings made in Section 10: Remote Control Settings (DIP switch 4).
5, 6 & 7 Fan speed
Switch fan speed between Low, Medium and High respectively. The appropriate LED illuminates.
T9901009-1-1 UK (v9) Page | 15
Page 16
16. COMMISSIONING THE SYSTEM
16.1 Verify system operation
To commission the system, verify the following conditions are met:
All fans are working.
Fans operate at Low, Medium and High speeds.
There is no excessive mechanical noise coming from the fans.
When heating is selected, the air stream from the discharge grille warms up across the whole
length of the air curtain.
When set to manual with fans set to high speed, heating increases as higher heat is selected.
Warm air reaches across the doorway with door open or closed.
Ecopower Remote Control operates correctly in both manual and auto modes.
16.2 Instruct customer and hand over
Before leaving site, hand over the installation to the customer/end user or their representative.
Explain that any person operating the air curtain must be given supervision and instruction by the
person responsible for their safety, concerning the safe use of the unit and to understa nd any hazards
involved. Children and those with reduced physical, sensory or mental capabilities should not operate
the air curtain.
Recommend that the doorway should be closed whenever possible but that during times of high
pedestrian use it will become an ‘open doorway’. The air curtain then serves an essential purpose by
saving energy and providing comfort to occupants.
Explain that the inlet grilles and air filters (if fitted) must be cleaned regularly and the unit serviced at
schedule intervals – see section 19: Service & Maintenance.
NOTE: Leave these instructions with the customer/end user or their representative!!
17. SIGN OFF
Complete the following once commissioning is completed:
Installer signature Customer signature
Installer name
Installer company Customer company
Date
T9901009-1-1 UK (v9) Page | 16
Customer name
Date
Page 17
18. FAULT CONDITIONS
18.1 Overheat Safety cut-out
An overheat fault in electric heated units may cause the overheat safety cut-out(s) to operate.
This is indicated by flashing LEDs on the Remote Control and a red status LED on the Ecopower PCB
inside the air curtain.
Before resetting ensure there is adequate air flow from the air curtain and the unit has been
commissioned as per section 16.
To reset a overheat safety cut-out:
Step 1 Switch off the electrical supply to the air curtain.
Step 2 Allow time for the air curtain to cool down, typically 10 minutes.
Step 3 Switch on the electrical supply to the air curtain.
Step 4 Press the Auto button on the Ecopower remote control 4 times.
Air curtain heaters will then operate and after 30 seconds the LEDs on the remote control will stop
flashing and the status LED on the Ecopower PCB in the air curtain will flash green.
18.2 Fuses
In the event of an electrical fault internal electrical fuses may operate.
There are two internal fuses located on the Ecopower PCB inside the air curtain:
Fuse 6.3A(T) supplies the fan motors within the air curtain
Fuse 100mA(F) controls the circuitry of the Ecopower PCB
18.3 Ecopower PCB status indication
There is a status LED on the Ecopower PCB inside the air curtain (See LED shown on Wiring
Diagrams in the Appendix).
This indicates the status of the Ecopower Control system as follows:
1. LED flashing green – operation normal
2. LED flashing red – low supply voltage, remote control not plugged in or RJ cable fault
3. LED permanently red – overheat safety cut-out(s) open circuit from an overheat situation
(see Section 18: Fault Conditions for how to reset)
T9901009-1-1 UK (v9) Page | 17
Page 18
19. SERVICE & MAINTENANCE
WARNING: Failure to adequately maintain the unit and provide a suitable cleaning schedule will
19.1 Every week
NOTE: Weekly maintenance can be carried out by the Cleaner or Janitor from floor level.
Turn off the air curtain to prevent entry of dust then clean the face of the air inlet grilles and air filters
inside the grilles using a vacuum cleaner with an extension tube and brush.
19.2 Every 3 months
WARNING: Before servicing, isolate and disconnect the air curtain from the electrical power.
WARNING: The following servicing and maintenance must be carried out by a competent
Clean and inspect the inside of the air curtain as follows:
Step 1 Remove plastic end caps at each end of the unit by pulling off to the side.
Step 2 Use a Pozi No.1 screwdriver to remove air inlet grilles by releasing the fasteners at the
Step 3 Clean and remove any build-up of dust and dirt within the air-curtain (inlet/outlet grilles,
NOTE: Build-up of dirt on fan impellers can cause vibration, noise and excessive wear on the
Step 4 Check within the unit to ensure all electrical connections and crimped terminals are tight
Step 5 On electric heated air curtains remove the fan deck(s) as follows to inspect electric
Unclip the fan motor electrical connector.
Unfasten 4 x M6 nuts/bolts on each fan deck.
Unfasten M4 screws at bottom edge of fan deck.
Carefully lift the fan deck away from the air curtain.
Refit fan decks(s) and air inlet grilles after servicing. Reconnect electrical supply and test to ensure
correct operation (see Section 16: Commissioning).
result in a loss of performance and reduced life expectancy of the air-curtain and
possible overheating and fire risk with electric heated units.
electrician or a Thermoscreens appointed technician.
bottom corners of each air inlet grille. See Fig 5, Section 8.1.1.
electric heaters, fan impellers, housings and motors) using a vacuum cleaner and soft
brush.
motor bearings.
and that all cables are in good condition.
heaters, electrical wiring and connections and to remove dust, dirt and debris:
T9901009-1-1 UK (v9) Page | 18
Page 19
20. WARRANTY
All units are covered by a two year warranty.
Failure to adequately maintain the unit may void the warranty. If any problems are encountered,
please contact your installer/supplier.
Failing this please contact the Thermoscreens warranty department.
Care has been taken in compiling these instructions to ensure they are correct. Therm oscreens Ltd.
disclaims all liability for damage resulting from any inaccuracies and/or deficiencies in this
documentation. Thermoscreens Ltd. retain the right to change the specifications stated in these
instructions.
APPENDIX 1 — Dimensions of T Surface Mounted Air Curtain
Page 21
1m - 1 kW (x3)
1.5m - 2kW (x3)
1m, 1.5m - 2 kW (x3)
Black Black
(top elements)
Second Stage Heating
Black Black
(bottom elements)
First Stage Heating
Capacitor:
1m - 2.5µF
1.5m - 3.15µF
1~
Fan Motor 1
Orange
Violet
Brown (High)
Blue (COMMON)
0
White
Red (Low)
Grey
2
345
1
Black
Blue
Red
F1 = F100mA
F2 = T6.3A
Healthy
Alarm
Red
55°C Auto
Thermal Trip
Grey
Brown
Black
Blue
E
L2
L2
L3
L3
N
E
N
L1
BLOCK
TERMINAL
L1
J1
F2 F1
NC C NO
Th
J2
LED
IN0
IN1
J9
ON
J6
R
0 -10V
J5
Summer/Winter
or Door Contact
le
b
a
C
e
v
la
S
/
r
e
t
REMOTE
s
a
M
1234
CONTROL
Yellow
White
Brown
1
2
3
L1
J10
J12
EEPROM
J11
moveable head of
Black rectangle is
DIP switch
Yellow
White
Black
4
6
5
L2
J14
High speed
Med speed
Low speed0VHigh speed
Fan 2Fan 1
Black
White
7
Med speed
Blue
Grey
Low speed
Red
Yellow
Blue
9
8
10
N
L3
J16
ECO-Power CVR1008-9
0V
J17
White
APPENDIX 2A — WIRING DIAGRAM T1000E and T1500E
400V / 3ph / 50Hz
To Slave
Air Curtain
T9901009-1-1 UK (v9) Page | 21
Page 22
Brown
Black
White
White
White
Black Black
1 kW (x3)1 kW (x3)
Black Black
(top elements)
Second Stage Heating
A1
A2
13NO
14NO
5
6
4
3
230V AC Coil
CONTACTOR
1
2
2 kW (x3)2 kW (x3)
Grey
Blue
Yellow
Yellow
Yellow
Black Black
Black Black
(bottom elements)
First Stage Heating
1~
Fan Motor 1
Violet
Brown (High)
Blue (COMMON)
Grey
234
0
1
2.5µF
Capacitor:
Orange
Red (Low)
5
TERMINAL
White
Black
Blue
Red
F1 = F100mA
F2 = T6.3A
Summer/Winter
J1
F2 F1
NC C NO
Th
J2
LED
IN0
IN1
J9
J6
R 0 -10V
J5
or Door Contact
e
l
b
a
C
e
v
a
l
S
/
r
e
t
REMOTE
s
a
M
Healthy
Alarm
Red
(x2)
55°C Auto
Thermal Trip
E
N
L1
L2
L1
L2
L3
L3
E
N
BLOCK
ON
1234
CONTROL
Yellow
Brown
2
L1
J12
J11
moveable head of
DIP switch
White
3
High speed
Fan 2Fan 1
Black
Blue
White
1
J10
EEPROM
Black rectangle is
White
Black
4
J14
Grey
Blue
9
8
7
6
5
L2
10
N
L3
J16
2.5µF
Capacitor:
Fan Motor 2
1~
(COMMON)
Orange
Violet
Brown (High)
Blue
012
White
Low speed
ECO-Power CVR1008-9
0V
J17
White
0V
Low speed
Med speed
High speed
Med speed
White
Black
Blue
Red
Red
Red (Low)
Grey
4
3
5
Black
Blue
Red
APPENDIX 2B — WIRING DIAGRAM T2000E
400V / 3ph / 50Hz
To Slave
Air Curtain
T9901009-1-1 UK (v9) Page | 22
Page 23
3 PORT VALVE
Brown (High)
1
Grey
234
Black
1~
Capacitor:
1m - 2.5µF
1.5m - 3.15µF
Orange
Violet
Red (Low)
5
Blue
Red
Fan Motor 2 (2m only)
1~
2.5µF
(COMMON)
Brown (High)
Blue
Grey
234
0
1
Capacitor:
Orange
Violet
Red (Low)
5
White
Grey
Green/Yellow
Orange
Blue
Fan Motor 1
1
4
2
3
E
F1 = F100mA
F2 = T6.3A
J1
F2 F1
NC C NO
Th
J2
LED
Blue
Brown
Summer/Winter
IN1IN0
J9
ON
J6
R 0 -10V
J5
or Door Contact
1234
White
Brown
Black
1
J10
J12
EEPROM
J11
2
3
L1
4
6
5
L2
J14
0V
Med speed
Low speed
High speed
Fan 2Fan 1
High speed
9
8
7
L3
0V
Med speed
Low speed
J16
Blue
10
N
J17
Blue (COMMON)
0
White
ECO-Power CVR1008-9
White
Black
Blue
Red
moveable head of
Black rectangle is
L
EE
N
BLOCK
TERMINAL
L
N
e
l
b
a
C
e
v
a
l
S
/
r
e
t
REMOTE
s
a
M
DIP switch
CONTROL
White
Black
Blue
Red
White
Black
Blue
Red
230V / 1ph / 50Hz
To Slave
Air Curtain
T9901009-1-1 UK (v9) Page | 23
APPENDIX 2C — WIRING DIAGRAM T1000W, T1500W and T2000W
Page 24
1~
Capacitor:
1m - 2.5µF
Fan Motor 1
1.5m - 3.15µF
1~
2.5µF
Capacitor:
F1 (5A)
White
Brown (High)
Blue (COMMON)
0
White
Brown
Red
1
Grey
234
Black
Blue
1
Violet
Grey
234
Orange
Red (Low)
5
Orange
Violet
Red (Low)
5
Brown (High)
Blue (COMMON)
0
Fan Motor 2 (2m only)
Red
Blue
Black
White
Black
Blue
Red
1
L
E
NN
BLOCK
TERMINAL
L
E
230V / 1ph / 50Hz
4
2
3
Switch
Control
Remote
21
3
I
0
4
Low speed
Medium speed
High speed
65
On/Off
APPENDIX 2D — WIRING DIAGRAM T1000A, T1500A and T2000A
7
8
Fan
Speed
T9901009-1-1 UK (v9) Page | 24
Page 25
21. DECLARATION OF CONFORMITY
Thermoscreens Ltd.
St. Mary’s Road
Nuneaton
Warwickshire
CV11 5AU
United Kingdom
Telephone: +44 (0)24 7638 4646
www.thermoscreens.com
EC DECLARATION OF CONFORMITY
as defined by the EC Council Directive on Machinery 2006/42/EC,
the Low Voltage Directive 2006/95/EC, Electromagnetic Compatibility Directive 2004/108/EC,
the Energy related Products Directive 2009/125/EC
Herewith we declare that the air movement equipment designated below, on the basis of its design
and construction in the form brought onto the market by us in accordance with the relevant safety,
health and performance requirements of the Machinery.
If alterations are made to the machinery without prior consultations with us, this decla ration becomes
invalid.
Designation of Equipment: AIR CURTAINS
Series Type: T1000A; T1000E; T1000W; T1500A; T1500E; T1500W;
T2000A; T2000E; T2000W
(in Casing Styles: Surface Mount)
Relevant EC Council the Machinery Directive (2006/42/EC)
Directives: the Low Voltage Directive (2006/95/EC)
the Electromagnetic Compatibility Directive (2004/108/EC)
the Energy related Products Directive (2009/125/EC)
Applied Harmonised Machinery - EN ISO 14121-1:2007, EN 294:1992, EN 414:2000
Standards: LVD - EN 60335-1:2012, EN 60335-2-30:2009+A11:2012
EMC - EN 61000-6-1:2007, EN 61000-6-3:2007+A1:2011,
EN 61000-3-2:2006+A2:2009, EN 61000-3-3:2008
ErP - Commission Regulation (EU) No.327/2011,
ISO 5801:2007, ISO 12759:2010
Basis of Self Attestation:Quality Assurance to BS EN ISO 9001: 2008 B.S.I. Registered Firm Certificate Number FM 85224
SGS Test Report ELS150049/2/R/DC/11;
SGS Test Report EMC150049/1
CE Marking Association Test Report 6799 and 6800
Responsible Person: Mr. P.Casey, Operations Director, Thermoscreens Ltd.
Date: 20 March 2014
Signed:
T9901009-1-1 UK (v9) Page | 25