Thermoscreens T Series, T2000AR, T1000AR, T1500AR, T1000WR Operation And Maintenance

...
T Series.
Recessed Range
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
English
T9901012-1-1 UK (v9) Page | 1
1. CONTENTS
Page
1. CONTENTS ...................................................................................................................................... 2
2. ELECTRICAL SAFETY ..................................................................................................................... 3
3. SPECIFICATIONS ............................................................................................................................ 3
4. INTRODUCTION .............................................................................................................................. 4
5. DELIVERY CONTENTS ................................................................................................................... 5
6. TOOLS REQUIRED .......................................................................................................................... 5
7. INSTALLATION ................................................................................................................................ 6
8. LPHW MODELS ............................................................................................................................... 9
9. REMOTE CONTROL INSTALLATION ........................................................................................... 10
10. REMOTE CONTROL SETTINGS ................................................................................................... 10
11. EXTERNAL CONTROLS ................................................................................................................ 11
12. MULTIPLE AIR CURTAIN SYSTEMS ............................................................................................ 12
13. SYSTEM CONFIGURATION .......................................................................................................... 13
14. FAN SPEED SELECTION .............................................................................................................. 14
15. REMOTE CONTROL OPERATION ................................................................................................ 15
16. COMMISSIONING THE SYSTEM .................................................................................................. 17
17. SIGN OFF ....................................................................................................................................... 17
18. FAULT CONDITIONS ..................................................................................................................... 18
19. SERVICE & MAINTENANCE ......................................................................................................... 19
20. WARRANTY ................................................................................................................................... 20
APPENDIX 1A — DIMENSIONS OF T RECESSED AIR CURTAIN WITH STANDARD RECESS
GRILLE ...................................................................................................................................................... 21
APPENDIX 1B — DIMENSIONS OF T RECESSED AIR CURTAIN WITH WIDER RECESS GRILLE ... 22
APPENDIX 2A — WIRING DIAGRAM T1000E9R, T1000E12R, T1500E12R AND T1500E18R ............ 23
APPENDIX 2B — WIRING DIAGRAM T2000E18R ................................................................................. 24
APPENDIX 2C — WIRING DIAGRAM T2000E24R ................................................................................. 25
APPENDIX 2D — WIRING DIAGRAM T1000WR, T1500WR and T2000WR ......................................... 26
APPENDIX 2E — WIRING DIAGRAM T1000AR, T1500AR and T2000AR ............................................. 27
20. DECLARATION OF CONFORMITY ............................................................................................... 28
T9901
012-1-1 UK (v9) Page | 2
2. ELECTRICAL SAFETY
Electrical Supply and Wiring to the Air Curtain
All electri accordance with the latest edition of the IEE wiring regulations and/or local statutory regulations.
cal wiring and connections MUST be carried out by a competent qualified electrician in
A 1 phase or 3 phase local isolator having a contact separation of at least 3mm
s must be fitted in the electrical supply to the air curtain and located in an accessible
pole position adjac
Models operating on 3 phase electrical supply - see section 3: Specifications -
A 25mm size cable gland or conduit connector of IP21 rating or above should be used
See Wiring Diagram for connecting electrical supply and control ca
The appliance must be connected by cables having an appropriate heat resistan temperature rating.
All supply cables, circuit breakers and other electrical installation equipment mu
ctly sized for the air curtain model being installed; see section 3: Specifications.
corre
neutral con
the Electri
The air
ent to the unit.
nection (3N~).
cal Supply into the air curtain.
curtain must be ea
rthed.
bles to the air curtain.
on all
t
st be
require a
for
3. SPECIFICATIONS
Air Curtain
Model No
T1000AR 230/1/50 0.25 1.1 N/A 27 T1500AR 230/1/50 0.35 1.7 N/A 40
T2000AR 230/1/50 0.45 2.0 N/A 50 T1000WR 230/1/50 0.25 1.1 6.0 / 12.0 29 T1500WR 230/1/50 0.35 1.7 9.0 / 18.0 42 T2000WR 230/1/50 0.45 2.0 12.0 / 24.0 53
T1000E9R 400/3/50 9.25 14.1 6.0 / 9.0 28 T1000E12R 400/3/50 12.25 18.7 6.0 / 12.0 28 T1500E12R 400/3/50 12.35 18.9 6.0 / 12.0 41 T1500E18R 400/3/50 18.35 27.9 9.0 / 18.0 41 T2000E18R 400/3/50 18.45 28.1 12.0 / 18.0 52 T2000E24R 400/3/50 24.45 36.8 12.0 / 24.0 52
Electrical
Supply
(V/ph/Hz)
Rated
Electrical
Power Input
(kW)
Rated
Current
per phase
(A)
Heat Output
[Low/High]
(kW)
Weight
Table 1
(kg)
T9901
012-1-1 UK (v9) Page | 3
4. INTRODUCTION
Established in the 1960s, Thermoscreens is a leading air curtain manufacturer that exports to over 60 countries worldwide.
As with all our products, the T recessed range of air curtains are designed with energy efficiency in mind.
T models suffixed ER, WR or AR are designed to be recess mounted inside a building and located horizontally over a doorway.
They must not be installed on the outside of a building.
Please complete the following details for your reference:
Date of Purchase Place of Purchase
Serial Number
Proof of purchase is required to make a claim under warranty.
Thermoscreens Ltd
St. Mary’s Road
Nuneaton
Warwickshire
England
CV11 5AU
Email: sales@thermoscreens.com — http://www.thermoscreens.com
Tel: +44 (0) 24 7638 4646 — Fax: +44 (0) 24 7638 8578
T9901012-1-1 UK (v9) Page | 4
y
5. DELIVERY CONTENTS
The following items are supplied in the box at delivery.
NOTE: If any parts are missing or damaged contact your place of purchase.
T Recessed Air Curtain Ecopower Remote Control
Recessed Grille
The recessed grille is
supplied separately
(for Electric and Water Heated units)
Supplied with 6m RJ Control Cable
3-port control valve
(for water heated units)
Fitted in pipework to
air curtain b
installer
(Optional – supplied by Installer)
(disables heating on a warmer day)
Remote Control Switch
(for Ambient units)
Outdoor Air Thermostat
Used for simple weather
compensation control
6. TOOLS REQUIRED
The following tools are required for installation:
Flat blade screwd rivers  Pozi hea d screwdrivers  10mm spanner  Adjustable spanner
T9901012-1-1 UK (v9) Page | 5
 Electric drill  Ladders  Appro priate lifting equipment  Appropriate tools for cutting ceiling
aperture
7. INSTALLATION
The air curtain is designed to be recessed within ceiling voids or bulkheads with in a building and located horizontally over a doorway. It must not be installed outside of the building.
7.1 Location
Mount the air curtain above and as close to the doorway as possible, with:
the recesse d grille not more than 3m above floor
level
the air discharge (see 1, Fig 1) section of the
recessed grille nearest the doorway and the air inlet section (see 2, Fig 1) furthest from the doorway
Beware of doorway top edges, structural beams, door opening/closure devices, etc., which may interfere with the air stream and affect the location of the unit.
NOTE: For the air curtain to work well the doorway should be less than the width of the airstream.
7.2 Ceiling Suspension
Step 1 Depending on whether a standard or wider width
recessed grille is used, cut an aperture in the ceiling to the dimensions in Appendices 1. Cut notches, if necessary, to clear screws in the air curtain casing.
NOTE: For LPHW models, pipework will need to be installed
Step 2 Fix M10 threaded rods (not supplied) through the 2
NOTE: Do not let the hanging rods come below the bottom
above the curtain. Allow sufficient access and height clearance within the ceiling void to do this.
holes at each end in the top casing (see Fig 2). Feed the rods through the casing and attach to fixing brackets near the bottom of the unit (see Fig 3, looking up into the air curtain). Use M10 lock-nuts either side of fixing brackets to secure hanging rods. An additional threaded rod is fitted on a 1.5m unit with two extra threaded rods fitted on a 2m unit, see Appendices 1.
of the unit casing or they may prevent the recessed grille fitting properly.
Fig 1
Fig 2
Fig 3
2
1
T9901012-1-1 UK (v9) Page | 6
M10 hanging rods
RECESSED AIR CURTAIN
CEILING LEVEL CEILING LEVEL
25 - 50
Bottom surface of recessed air curtain casing
25 - 50
Fig 4
th
Step 3 If you are installing model T1500R, fit a 5
of the unit. For model T2000R, fit 5
th
M10 threaded rod into the hanging point in the middle
and 6th threaded rods, see Appendices 1 and Fig 4.
Step 4 Secure each rod to a suitable structure that can support the weight of the unit (see section 3:
Specifications for weights).
Step 5 Adjust the height of the unit on its hangi ng rods so the bottom surface of the casing goes
between 25-50mm up into the ceiling as shown in Fig 4. Ensure the unit is level.
WARNING: It is the sole responsibility of the installer to ensure that the fixing locations and
suspension system used are suitable for the air curtain being installed.
7.3 Attaching the recessed grille to the air curtain
The recessed grille consists of:
Metal frame Hinged standard or wider width inlet/discharge grille  Slotted fixing brackets
There are 4 fixing slotted brackets on the T1000R with 6 brackets fitted on T1500R and T2000R (see Fig 5a and Fig 5b).
Centre brackets for 1.5m and 2m
Fig 5a; standard width grille
Less angled bracket
Fig 5b; wider width grille
More angled bracket
Centre brackets for 1.5m and 2m
T9901012-1-1 UK (v9) Page | 7
Fix the grille as follows:
Step 1 Open the hinged inlet grille using a flat bladed
screwdriver to release the quarter turn fasteners (see Fig 6). There are two fasteners on the T1000R unit and three fasteners on T1500R and T2000R units. Before lifting the grille frame into position, remove four (six on T1500R/T2000R) M6 bolts fitted on the inside edge of air curtain.
Step 2 Make sure the grille will go the correct way
around (discharge nearest to doorway). Offer the recessed grille up through the cut-out in the ceiling.
Step 3 Using the M6 bolts removed in Step 1, secure
grille by fixing each bolt through the slotted brackets as shown in Fig 8. For illustration purposes Fig 8 details a wider recess grille. With the hinged grille open, adjust the height of the grille frame via slots in each bracket, so frame is snug fit against the ceiling with no gaps all the way around.
Step 4 To stop discharge air re-circulating within the
air curtain a sliding separator will need adjusting up or down (see Fig 9). To adjust plate release M6 bolts either end, extend the slide plate so that it will touch the topside of the grille along its whole length and tighten the bolts. It will be necessary to close the hinged grille core to gauge where the separator plate should be fitted.
Step 5 Once the above steps are complete the
hinged grille core can be closed and all the quarter turn fasteners tightened up.
Fig 6
Fig 7
Fig 8
Fig 9
NOTE: Open the hinged grille core to gain access to
electrical connections, and for servicing and maintenance.
Fig 10
T9901012-1-1 UK (v9) Page | 8
8. LPHW MODELS
For LPHW models ensure that water isolation valves are fitted in the flow and return pipework adjacent to the air curtain and connected correctly as shown in the diagram in Appendix 1.
For the design of the water pipework system and pump, water flow rates and pressure drops for maximum heat output of the air curtain are given in Table 2 below.
Air Curtain
Water Flow Rate
(l/min at 82/71°C)
Water Pressure Drop
(kPa)
T1000WR, 2-row (12kW) 15.6 16.1 T1500WR, 2-row (18kW) 23.4 10.4 T2000WR, 2-row (24kW) 31.2 16.3
Table 2
Air Curtain
Water Flow Rate
(l/min at 60/40°C)
Water Pressure Drop
(kPa)
T1000WR, 3-row (12kW) 8.6 8.3 T1500WR, 3-row (18kW) 12.9 18.2 T2000WR, 3-row (24kW) 17.1 15.0
NOTE: Water Pressure Drop is across the flow and return pipework to the air curtain and includes for the
coil fitted inside the unit and the valve fitted in the heating pipework to the unit. Water flow rates and pressure drops at different water temperatures can be calculated using the Thermoscreens coil calculation programme. Visit the Thermoscreens website for details.
The installer must connect the 3-port valve in the heating pipework as shown in Figure 11 below:
22mm pipe
22mm pipe
wire valve to pcb inside air curtain
22mm pipe
A
B
A/B
22mm pipe
R E T U R N
F L O
W
Fig 11
T9901012-1-1 UK (v9) Page | 9