Thermoscreens PHV1500A v, PHV2500W V, PHV1500W V, PHV2000W V, PHV3000W V Installation, Operation & Maintenance Instructions Manual

...
9901020-6 Page 1 of 25
PHV V NT VERTICAL AIR CURTAINS
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTI NG INSTALLATION
Thermoscreens Ltd
St. Mary’s Road Nuneaton
Warwickshire England
CV11 5AU
Email: sales@thermoscreens.com
Tel: +44 (0) 24 7638 4646 Fax: +44 (0) 24 7638 8578
www.thermoscreens.com
9901020-6 Page 2 of 25
UN-PACKING YOUR PHV V NT VERTICAL AIR-CURTAIN
The following items are supplied and packaged within the boxes.
PHV V NT Vertical Air Curtain
Motorised Valve
(LPHW units only)
Remote Control
Accessories
M10 stainless steel dome nuts Wall fixing kits Stacking kit (spacer plate, M8 x 25 bolts and M8 nyloc nuts) for stacked units
If anything is missing or damaged please contact your place of purchase immediately.
For your records
Date of Purchase…………………………….. Place of Purchase……………………………. Serial Number…………………………………
For warranty purposes proof of purchase is necessary so please keep a copy of your invoice.
(All documentation supplied with each unit should be stored and kept for future reference).
9901020-6 Page 3 of 25
INSTALLATION OF YOUR VERTICAL APPLICATION PHV V NT AIR CURTAIN
The air curtain must be surface mounted within the building and not exposed to
the external environment or moist conditions. Do not install the air curtain in a
doorway situation where there is a likelihood, or there has been a history of, rain
ingress. The air curtain must not be built into a compartment or recessed.
Location
Prior to commencing any vertical installation it is essential to ensure the correct handing has been selected, i.e. Left Hand (LH) or Right Hand (RH) - . see “Handing Guide” in Figure 1. Maximum doorway width = 2m per air curtain.
The air curtain should be located close to the door opening with the air discharge grille positioned nearest to the door. For maximum effectiveness it is essential to ensure the top of the air curtain is slightly higher than the opening height of the door. Obstructions such as door opening devices, structural beams etc will reduce the efficiency of the air curtain.
Floor Fixing
Before installing the air curtain obtain four suitable M10 fixing bolts, taking into account floor type and unit weight (See Table 1)*. Rawlplug ® M10 Projecting Rawlbolt ® 44356 type may be suitable. For dimensional details refer to the general assembly drawing, Figure 1.
Determine and place the unit in position. A wall bracket is provided to secure the vertical air curtain to the wall and this must be used. So that the wall bracket touches the wall, ensure the back of the base plate touches against the wall, skirting board will need to be cut away if necessary.
Using the base plate as a template, mark the location of the four holes, as indicated in the adjacent picture.
Using a suitable masonry drill bit correctly drill the four marked out holes. Place M10 fixing bolts into each hole, ensuring all bolts are upright.
Reposition the air curtain base plate over the projecting bolts. Tighten each M10 nut as indicated in the adjacent picture. Ensure the vertical unit is secure, level and square. It may be necessary to pack under the base plate to ensure unit is vertical.
Using a hacksaw carefully cut the projecting bolt flush with the nut, ensuring the base plate is not damaged or marked in any way.
Base plate to touch wall (cut away skirting board)
9901020-6 Page 4 of 25
Remove only one M10 nut and refit and resecure bolt with a stainless steel M10 dome nut supplied. Repeat for each of the other three projecting bolts one at a time.
Stacking of Units
PHV1500V and PHV2000V air curtains are delivered as single units. PHV2500V and PHV3000V air curtains are delivered as separate 1.5m + 1m air curtains for a PHV2500V unit and 2m + 1m air curtains for a PHV3000V unit. The 1m air curtain must always be mounted as the top unit using the stacking kit supplied to secure it to the bottom unit. The spacer plate, in the stacking kit must be bolted between the two units using the 4 off M8 x 25 bolts and nyloc nuts. This will allow the removal of access panels when required. All wall brackets must be used to properly secure both the bottom and top air curtains in the stack to the wall (See Figure 1).
* It is the sole responsibility of the installer to ensure that all the fixing points and bolts used are suitable for the air curtain.
Attention: The panels of the air curtain are coated in an easy to peel protective film. Please ensure all the protective film is removed before the air curtain is put into service.
9901020-6 Page 5 of 25
ENTERING AIR
DISCHARGE AIR
View 'A'
View 'B'
View 'A'
As drawn for R.H.
Opposite hand for L.H.
Bolt Holes for M10
Rawl bolts - 4 off
Figure 1 - VERTICAL PHV V NT AIR CURTAIN
PHV1500V
280922571707A(mm)
PHV2000V
PHV2500V PHV3000V
3359
DOORWAY
RHLH
OUTSIDE
INSIDE
"Handing Guide"
A
350
Foot Plate
439.6 Foot Plate
254.6
377.514.7
17
View 'B'
Electrical inlet
Wall Bracket:-
1 off for PHV1500V
& PHV2000V.
2 off for PHV2500V
& PHV3000V
Alternative
water connection
Electrical supply inlet
for PHV2000E V only
Controls
Water connection
Electrical inlet
Controls
(not used on
stacked units)
Water connection
1m Stack Unit
2 Holes for M8 fixing bolts
Distance between
hole centre s 295mm
Overheat reset
button for electric
heated unit
Overheat reset
button for electric
heated unit
2m Max.
Alternative
water connection
9901020-6 Page 6 of 25
Safety and Electrical Connections
All electrical wiring and connections MUST be carried out by a competent qualified electrician in accordance with the latest edition of the IEE wiring regulations and/or local statutory regulations.
A single phase or 3 phase local isolator with a contact separation of at least 3mm in all
poles must be fitted to the supply wiring (the isolator must be fitted in an accessible
position). The air curtain must be earthed. The appliance must be connected using cables having an appropriate
temperature rating (heat resistant). For two air curtains in a stack, electrical power must
be connected separately to the bottom air curtain and to the top air curtain. Ensure that the supply cables, circuit breakers and other electrical installation
equipment are correctly sized for the air curtain being installed; see Table 1 for Power
Ratings. See also data badge inside of unit adjacent to electrical inlet. On a 3 phase electrical supply the unit requires a neutral connection (3N~). Cable glands used for the Electrical Input must be rated IP21 or higher.
Table 1
Air Curtain Electrical
Supply
(V/ph/Hz)
Rated
Power
Input
(kW)
Current
per
phase (A)
Heat
Output
(kW)
Weight
(kg)
PHV1500A V 230/1/50 0.40 1.8 N/A 60 PHV2000A V 230/1/50 0.60 2.7 N/A 77
Top air curtain 230/1/50 0.30 1.3 N/A PHV2500A V
(Stacked Unit)
Bottom air curtain 230/1/50 0.40 1.8 N/A
99
Top air curtain 230/1/50 0.30 1.3 N/A PHV3000A V
(Stacked Unit)
Bottom air curtain 230/1/50 0.60 2.7 N/A
116
PHV1500W V 230/1/50 0.40 1.8 18.0 68 PHV2000W V 230/1/50 0.60 2.7 24.0 87
Top air curtain 230/1/50 0.30 1.3 12.0 PHV2500W V
(Stacked Unit)
Bottom air curtain 230/1/50 0.40 1.8 18.0
114
Top air curtain 230/1/50 0.30 1.3 12.0 PHV3000W V
(Stacked Unit)
Bottom air curtain 230/1/50 0.60 2.7 24.0
133
PHV1500E V 400/3/50 18.40 27.9 9.0/18.0 66 PHV2000E V 400/3/50 24.60 37.5 12.0/24.0 85
Top air curtain 400/3/50 12.30 18.7 6.0/12.0 PHV2500E V
(Stacked Unit)
Bottom air curtain 400/3/50 18.40 27.9 9.0/18.0
109
Top air curtain 400/3/50 12.30 18.7 6.0/12.0 PHV3000E V
(Stacked Unit)
Bottom air curtain 400/3/50 24.60 37.5 12.0/24.0
128
9901020-6 Page 7 of 25
To gain access for making electrical and/or water services the air intake grilles must be removed. Remove intake grilles by unfastening two screws on each grille; M4 x 10mm Pozi screws accessed via larger hole in the side of the grille (See Insert).
Access can now be gained to make the electrical connections and assist with water connections.
When making electrical connections first remove the safety cover plates over the electrical supply terminals. On 2m electric air curtains the safety cover plates are located towards the centre of the air curtain (See Insert).
For two air curtains in a stack electrical and water connections are made separately to the bottom air curtain and to the top air curtain (See Figure 1 View B).
Fitting/Connecting the Ecopower Remote Control
The remote control unit should be located in a suitable place for easy access, it can be fixed to the wall via two key-hole slots. Drill and fix the screws into the wall leaving a small gap between the head and the wall, lower the unit onto the screws, for fixing centres see adjacent figure. Ensure suitable fixing screws are used.
The remote control is supplied with cable and a pre-fitted RJ connecting plug.
Ensure the remote control cable is safely secured and connected to the air curtain as indicated. It can be plugged into either socket.
80mm
3.5mm
6mm
Safety
cover
plates
9901020-6 Page 8 of 25
RJ master/slave cable safely
routed internally between circuit boards of top and bottom air curtains
Figure 2
Route master/slave cable via internal hole in stacking kit
Two Air Curtains in a Stack
When two air curtains are in a 2.5m or 3m stack the Ecopower control wiring needs to be wired “master/slave”, so the air curtain stack is controlled by a single Ecopower remote control.
Plug the control cable from the remote control into one of the RJ sockets at the side of the top air curtain.
Inside the air curtain stack connect the RJ master/slave cable that is already plugged into the top unit circuit board, into the Ecopower PCB of the bottom unit. Route the RJ master/slave cable safely via the hole in the stacking kit (Refer to Figure 2).
Loading...
+ 17 hidden pages