Thermoscreens PHV2000NT Installation, Operation & Maintenance Instructions Manual

T9901018-1 Page 1 of 26
PHV2000NT CHILLED WATER HEAT PUMP,
SENSIBLE/DRY COOLING UNIT
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
For use with PUHZ-HW140VHA2 or YHA2 Outdoor Units
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTI NG INSTALLATION
Thermoscreens Ltd
St. Mary’s Road Nuneaton
Warwickshire England
CV11 5AU
Email: sales@thermoscreens.com
Tel: +44 (0) 24 7638 4646 Fax: +44 (0) 24 7638 8578
www.thermoscreens.com
English
T9901018-1 Page 2 of 26
Thermoscreens / Mitsubishi Electric
PHV2000NT Chilled Water Heat Pump,
Dry Cooling Unit - Split System
The PHV2000NT Chilled Water Heat Pump System consists of :-
a Thermoscreens 'PHV2000NT Dry Cooling Unit' with Mitsubishi Electric PAC-IF010B-
E Interface PCB and PAR-W21MAA Controller and Siemens RDG400 Manual Room Control for manual control by the end user *
a Mitsubishi Electric PUHZ-HW140VHA2/YHA2 Air to Water Outdoor Unit *
* - supplied by Mitsubishi Electric
Water Pipework Installation and Water Pump(s) ‡  Electrical installation ‡  a 2-pole On/Off Switch for the end user ‡  a 2-pole Isolator for the S1, S2, S3 link
- installation items supplied and fitted by installer
Thermoscreens PHV2000NT
Dry Cooling Unit
Mitsubishi Electric
PUHZ-HW140
Outdoor Unit
Permanent 1-phase mains electrical supply
Siemens RDG400
Manual Room Control
On/Off – Input Cooling Temp Set Point – Input Air Temp Sensor – Input (alternative to return air temp sensor in unit)
S1, S2, S3 link
Permanent electrical supply
(from local switched isolator)
Pump
Flow and Return water pipework
Remote Signals
On/Off - Input Mitsubishi Error - Output Room over-temp alarm - Output
Chilled water pipework Electrical cables
Control cables
Supplied and fitted inside plastic end cap. Not used for control by the end user, only needed so the outdoor unit will run.
2-pole On/Off Switch for End User (easily accessible next to unit) [connect fire alarm circuit here]
Mitsubishi Electric
PAR-W21MAA
S1, S2
Isolator
T9901018-1 Page 3 of 26
DESIGN INFORMATION
The Thermoscreens dry cooling unit is designed to provide up to 12kW * of dry/sensible cooling (SHR/SHF = 1) (e.g. zero latent cooling with no condensate coming from the unit) to areas where cooling is required but with no increase in moisture content of the air, i.e. IT Server Rooms, laboratory areas, etc. It will do this if the room environmental conditions are no higher than 24°C dry bulb with a relative humidity no greater than 40% and the chilled water flow temperature entering the unit is no lower than 10°C **. The 10°C chilled water flow temperature is set at commissioning and controlled by the Mitsubishi Electric PUHZ­HW140 Outdoor Unit. Under design conditions the return water temperature from the dry cooling unit is 13°C with a flow water temperature of 10°C.
* - output may be reduced if antifreeze additives are used. ** - validated by tests carried out at independent test house BSRIA, UK.
Chilled water pipework and water pump(s) must be supplied and installed to supply the chilled water from the PUHZ-HW140 Outdoor Unit to the Thermoscreens dry cooling unit. Hydraulic details for this installation are as follows:
Table 1
Water Volume
Flow Rate for
12kW maximum
output
Hydraulic
Resistance of
water coil in
Thermoscreens
Dry Cooling Unit at
3.2 m
3
/h
(kPa)
Hydraulic
Resistance of heat
exchanger in
Mitsubishi PUHZ
Outdoor Unit at
3.2 m3/h (kPa)
Water Volume of
water coil in
Thermoscreens
Dry Cooling Unit
(litre)
Water Volume of
heat exchanger in
Mitsubishi PUHZ
Outdoor Unit
(litre)
m3/h l/min
3.2 53 36 15 5.1 2.5
A separate, self contained ‘closed/unvented’ water system must be used for the flow and return water pipework between the Thermoscreens dry cooling unit and the Mitsubishi Electric outdoor unit. This should incorporate water pump(s), expansion vessel, pressure relief valve, filling loop, pressure gauge, automatic air vents, water dirt trap device, flow setter valve (recommended), drain valve(s), isolating valves and union fittings for the removal of components. The water system must be suitable for chilled water and installed and commissioned by a qualified technician in accordance with CIBSE Commissioning Code W, CIBSE KS9, BSRIA AG 2/89.3 and BSRIA AG 1.2001.1. For the Mitsubishi Electric system to operate correctly the minimum water volume of the water system must be 80 litres, so a buffer vessel may be necessary. A water dirt trap device should be incorporated into the chilled water system to help protect the system from any contamination and provide an ongoing indication of the system water condition. Please note that the Fernox Boiler Buddy water dirt trap device has a hydraulic pressure drop of 12kPa (clean) at a water flow rate of 3.2m3/h**. If pressure drop in the system becomes an issue it may be necessary to use a commercial type water strainer with a lower hydraulic pressure drop. It is recommended that a flow setter valve is fitted in the water pipework system to verify the water flow rate. We recommend the AV23 SETTER Bypass SD 20-70 l/min DN32 (Code No.223.2561.00) by Taconova www.taconova.com or equivalent.
For a self contained, close coupled 35mm pipework installation the following suggested water pumps are given as a guide only :-
Wilo TOP-S 30/10 (230V/1ph/50Hz) or Grundfos UPS32-120F (230V/1ph/50Hz)
Pump selection must of course be checked by a Building Services Engineer for each installation !
T9901018-1 Page 4 of 26
Because of the relatively high hydraulic pressure drops it may be cost effective to incorporate two water pumps operating in series. Pump(s) need to be 230V/1ph/50Hz with a total maximum current = 2A for all pumps combined. If the pump(s) total current is higher than this an interface relay/contactor will need to be used.
If so required, the cooling duty can be reduced from 12kW and a smaller water pump used. Dry cooling will still be achieved providing the room environmental conditions are no higher than 24°C dry bulb with a relative humidity no greater than 40% and the chilled water flow temperature entering the unit is no lower than 10°C. The following table gives details for this:
Table 2
Cooling Duty
(kW)
Water Volume
Flow Rate
Water Return
Temperature
(
°C)
Hydraulic Resistance
of water coil in
Thermoscreens Dry
Cooling Unit
(kPa)
Hydraulic Resistance
of heat exchanger in
Mitsubishi PUHZ
Outdoor Unit
(kPa)
m3/h l/min
11.5 2.6 44 13.8 24 10
11.0 2.0 33 14.8 14 6
10.5 1.6 26 15.7 9 4
Calculated for Water Flow Temperature = 10°C
In case of emergency, condensate could form on the cooling coil if there was a failure in the air conditioning on site or environmental conditions in the server room went above 24°C/40%Rh due to some other circumstance, e.g. doors left open, extreme weather conditions. To allow for this the Thermoscreens dry cooling unit is supplied with an integral condensate drain tray and outlet pipe to drain condensate away from the unit. A gravity condensate drain system extending to a suitable drain outside of the room must be supplied and fitted by the installer in case this emergency situation were to occur. This should be connected to the 15mm copper drain pipe that protrudes from the right-hand rear of the cooling unit behind the plastic end cap. Condensate pumps are not recommended but if a gravity drain system is impossible and a condensate pump is the only alternative it must not be fitted at the dry cooling unit because of reliability issues with these devices. If the condensate needs to be pumped to a higher level with a condensate pump this should be done in a separate room away from the server room. If there was a spillage of condensate at the pump, therefore, it will not occur in the server room. Suitable condensate pumps are Peristaltic or Rotary Diaphragm type with a suction head. The condensate pump needs to have the facility so it only operates if water is detected in the drain tray. It should also have a pump overrun to empty the drain tray as much as possible. We recommend the Blue Diamond rotary diaphragm type with cooling signal sensor (drainStik) manufactured by Charles Austen Pumps Ltd. (www.miniblue.co.uk).
The condensate drain tray inside of the Thermoscreens dry cooling unit has a metal fixing bracket located at the right hand end so a condensate sensor can be fixed in the tray in the appropriate position by the installer. There is a rubber grommet with 9.5mm hole fitted in the fixing bracket which will accept a 10mm diameter condensate sensor. Different size grommets can be fitted by the installer to suit other condensate sensors or if the grommet is removed a larger condensate sensor can be located in the 13mm diameter hole in the fixing bracket and held with silicon sealant. See also the manufacturer’s instructions that come with the condensate pump for further information.
Valuable or delicate equipment should not be placed beneath the dry cooling unit or directly in the path of the cool air discharge from the unit.
T9901018-1 Page 5 of 26
The Thermoscreens dry cooling unit operates from its own separate 1 phase electrical supply (1L+N+E) with a local switched isolator, see Page 12, and the fan within the unit runs continuously when this electrical supply is connected. If the local switched isolator is not easily accessible by the end user there should be a 2-pole On/Off switch fitted in an easily accessible position next to the dry cooling unit. The Mitsubishi Electric interface pcb fitted inside the dry cooling unit, however, is powered via the S1, S2, S3 wiring from the outdoor unit and a 2-pole S1, S2 isolator is required for this electrical/communications link.
Room temperature control of the Thermoscreens dry cooling unit is done using a Siemens RDG400 Manual Room Control that is supplied with the unit. This room control is used to select the target temperature (set point) of the room air temperature and it then switches the Mitsubishi Electric cooling system On and Off to achieve this temperature. The room air temperature is measured using either a return air temperature sensor in the air intake of the dry cooling unit or via an integral air temperature sensor within the RDG400 manual room control. This is selectable at the time of commissioning. A volt free remote On/Off control switch or BMS Dig/Output signal can be connected to the Thermoscreens dry cooling unit to turn the cooling system On and Off as an alternative to manually switching it On and Off at the RDG400 manual room control via the target temperature.
A separate thermostat with its air sensor positioned in the air intake is incorporated within the Thermoscreens dry cooling unit. This is to provide warning of elevated room air temperatures which could indicate a fault in the air conditioning system or some other problem. This thermostat can be set during commissioning to between 15°C and 35°C and terminals are provided within the unit for external monitoring of the contacts opening or closing on rising temperature. Contacts are rated 16A(4A) at 230v AC.
The Thermoscreens dry cooling unit includes the facility to provide a global error signal should an error occur in the Mitsubishi Electric heat pump system.
A Mitsubishi Electric PAR-W21MAA Remote Controller is supplied and pre-fitted inside the left hand end cap of the Thermoscreens dry cooling unit. It is needed for the Mitsubishi Electric heat pump system to operate and is also useful to diagnose error messages. It is not used for control of the system by the end user, this is done via the Siemens RDG400 manual room control, see above.
The Thermoscreens dry cooling unit is designed only for use with a Mitsubishi Electric air to water heat pump system for use on R410A. The complete Thermoscreens/Mitsubishi Electric air to water heat pump system, including fridge pipework, water pipework system, wiring, controls, etc. must be installed only by an approved Mitsubishi Electric refrigeration contractor in accordance with the relevant installation instructions.
Persons using the dry cooling system must be given adequate instruction and supervision concerning the use of the appliance by a person responsible for their safety. The cooling system is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities.
These instructions must be read in conjunction with the separate Mitsubishi Electric instructions that come with the PUHZ-HW140 Outdoor Unit. All instructions should be kept by the building facilities manager for future reference.
T9901018-1 Page 6 of 26
UNPACKING THE DRY COOLING UNIT
The following items are supplied and packaged within the dry cooling unit box :-
There will also be a PUHZ-HW140VHA2 or YHA2 Air to Water Outdoor Unit supplied by Mitsubishi Electric.
The complete Thermoscreens/Mitsubishi Electric dry cooling system, to provide dry cooling to a server room or other space, including chilled water pipework system and wiring is to be installed only by an approved Mitsubishi Electric contractor.
For your records
Date of Purchase…………………………….. Supplier/Installer………………………..……. Serial Number…………………………………
For warranty purposes proof of purchase is necessary so please keep a copy of your invoice.
IMPORTANT This Dry Cooling Unit is intended only for use with a Mitsubishi Electric PUHZ-HW140VHA2 or YHA2 Air to Water Outdoor Unit.
These instructions must be read in conjunction with the separate instructions that come with the Mitsubishi Electric PUHZ-HW140VHA2 or YHA2 Air to Water Outdoor Unit.
(All documentation supplied with the unit should be stored and kept for future reference.)
If anything is missing or damaged please contact your supplier immediately.
PHV2000NT Dry Cooling Unit
End caps are supplied loose to be fitted during installation
Mitsubishi Electric PAR-W21MAA fitted inside LH end cap
Siemens RDG400
M
anua
l Room Control
Wall Brackets and Fixing Bolts
for if Dry Cooling Unit is to be fixed to a wall
T9901018-1 Page 7 of 26
150mm minimum clearance
COOL AIR
White unit shown for picture clarity only
INSTALLING THE DRY COOLING UNIT
The dry cooling unit has been designed to be mounted on a wall or suspended from above using M10 drop rods. It must not be installed on the outside of the building, or built into a cabinet or recessed in anyway.
Location
The dry cooling unit must be mounted so the unit is horizontal and level and the discharge grille faces downwards. The discharge grille must be at least
2.4m above ground level and located so the downwards flowing cool air will distribute throughout the room or across equipment to be cooled. It should not, however, be positioned directly above valuable or delicate equipment in case of water leaks or an emergency condensate situation, e.g. doors left open, extreme weather conditions. Beware of obstructions in the room that may interfere with air distribution. Leave a gap of 150mm minimum above the unit to allow for installing the water pipework.
Wall Fixing
There are three wall brackets supplied and these need to be bolted to the rear face of the cooling unit as shown in the adjacent picture using the M10 bolts supplied. A suitable wall fixing system (not supplied) needs to be used to fix the brackets to the wall, taking into account the type of wall and the weight of the unit - 76kg.*
Step 1. Refer to Figure 1, Page 8 for mounting details and drill the fixing points in the wall. Step 2. Screw in the top wall bolts leaving a small gap between the bolt head and the wall. Lower the cooling unit onto the bolts via the key-hole slots in the top of the wall brackets and then screw in the bottom wall bolts. Step 3. Ensure all fixing bolts are tightened and the dry cooling unit is safely secured to the wall.
Ceiling Suspension
There are six M10 threaded inserts provided in the top face of the cooling unit (see Figure 1, Page 8 for positions) so it can be suspended on M10 threaded hanging rods with lock nuts (not provided). All six suspension points must be used. Ensure each of the hanging rods is secured onto a suitable structure that can support the weight of the unit - 76kg.* Screw the M10 hanging rods into the threaded inserts by a minimum of 20mm and fit locking nuts to prevent the rod rotating and coming away from the casing. Do not screw the hanging rods too far in or they could interfere with internal components.
* It is the sole responsibility of the installer to ensure that
the building fixing locations and suspension system used are suitable for the dry cooling unit being installed.
White unit shown for picture clarity only
T9901018-1 Page 8 of 26
295
912
1824
798
1596
2296
168
36
255
377
Water Return Connection
60
Electrical Supply and
Control Wiring Inlets
for pipes
c. 150 min.
6 x M10 threaded holes for M10 drop rods
IMPORTANT - Use all 6 drop rod holes
3 Holes x 20mm
Water Connections, Rp1
56
70
(1in. BSP Internal.)
Emergency Condensate Connection
at rear of plastic end cap, 15mm copper
798
215
912
AIR
AIR
Wall Mounting Brackets
FLOW RETURN
Water Flow Connection
FIGURE 1 – DIMENSIONS OF THERMOSCREENS DRY COOLING UNIT
Loading...
+ 18 hidden pages