Thermoscreens PHV1500W, PHV1500A, PHV2000A, PHV1000W, PHV2000W Installation & Operation Manual

...
T9901008-1-1 UK (v9) Page | 1
AIR CURTAIN
PHV SURFACE MOUNTED RANGE
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
English
T9901008-1-1 UK (v9) Page | 2
1
CONTENTS ...................................................................................................................................... 2
2 ELECTRICAL SAFETY ..................................................................................................................... 3
3 SPECIFICATIONS ............................................................................................................................ 3
4. INTRODUCTION .............................................................................................................................. 4
5. DELIVERY CONTENTS ................................................................................................................... 5
6. TOOLS REQUIRED .......................................................................................................................... 5
7. INSTALLATION ................................................................................................................................ 6
8. ACCESS FOR ELECTRICAL CONNECTION .................................................................................. 8
9. REMOTE CONTROL INSTALLATION ............................................................................................. 9
10. REMOTE CONTROL SETTINGS ..................................................................................................... 9
11. EXTERNAL CONTROLS ................................................................................................................ 10
12. MULTIPLE AIR CURTAIN SYSTEMS ............................................................................................ 11
13. SYSTEM CONFIGURATION .......................................................................................................... 12
14. FAN SPEED SELECTION .............................................................................................................. 13
15. REMOTE CONTROL OPERATION ................................................................................................ 13
16. COMMISSIONING THE SYSTEM .................................................................................................. 15
17. SIGN OFF ....................................................................................................................................... 15
18. FAULT CONDITIONS ..................................................................................................................... 16
19. SERVICE & MAINTENANCE ......................................................................................................... 17
20. WARRANTY ................................................................................................................................... 18
APPENDIX 1 — Dimensions of PHV Surface Mounted Air Curtain ......................................................... 19
APPENDIX 2A — WIRING DIAGRAM PHV1000E .................................................................................. 20
APPENDIX 2B — WIRING DIAGRAM PHV1500E .................................................................................. 21
APPENDIX 2C — WIRING DIAGRAM PHV2000E ................................................................................. 22
APPENDIX 2D — WIRING DIAGRAM PHV1000W, PHV1500W and PHV2000W ................................. 23
APPENDIX 2E — WIRING DIAGRAM PHV1000A, PHV1500A and PHV2000A .................................... 24
21. DECLARATION OF CONFORMITY ............................................................................................... 25
1 CONTENTS
Page
T9901008-1-1 UK (v9) Page | 3
Electrical Supply and Wiring to the Air Curtain
All electrical wiring and connections MUST be carried out by a competent qualified electrician in accordance with the latest edition of IEE wiring regulations and local statutory regulations if applicable.
A 1 phase or 3 phase local isolator having a contact separation of at least 3mm on all poles
must be fitted in the electrical supply to the air curtain and located in an accessible position adjacent to the unit.
The appliance must be connected by cables having an appropriate heat resistant temperature
rating.
All supply cables, circuit breakers and other electrical installation equipment must be correctly
sized for the air curtain model being installed; see Section 3: Specifications.
Models operating on a 3 phase electrical supply - see Section 3: Specifications - require a
neutral connection (3N~).
A 25mm size cable gland or conduit connector of IP21 rating or above should be used for the
Electrical Supply into the air curtain.
See Wiring Diagrams for connecting electrical supply and control cables to the air curtain. The
air curtain must be earthed.
Air Curtain
Model No
Electrical Supply
(V/ph/Hz)
Rated
Electrical
Power Input
(kW)
Rated
Current per
phase (A)
Heat Output
[Low/High]
(kW)
Weight
(kg)
PHV1000A 230/1/50 0.30 1.3 29 PHV1500A 230/1/50 0.40 1.8 43
PHV2000A 230/1/50 0.60 2.7 58 PHV1000W 230/1/50 0.30 1.3 6.0 / 12.0 35 PHV1500W 230/1/50 0.40 1.8 9.0 / 18.0 47 PHV2000W 230/1/50 0.60 2.7 12.0 / 24.0 64
PHV1000E 400/3/50 12.30 18.7 6.0 / 12.0 32
PHV1500E 400/3/50 18.40 27.9 9.0 / 18.0 45
PHV2000E 400/3/50 24.60 37.5 12.0 / 24.0 62
2 ELECTRICAL SAFETY
3 SPECIFICATIONS
Table 1
T9901008-1-1 UK (v9) Page | 4
Established in the 1960s, Thermoscreens is a leading air curtain manufacturer that exports to over 60 countries worldwide.
As with all our products, the PHV range of air curtains is designed with energy efficiency in mind.
PHV models suffixed E, W or A are designed to be surface mounted inside a building and located horizontally over a doorway.
They must not be installed on the outside of a building or built into a cabinet or recessed in any way.
Please complete the following details for your reference:
Date of Purchase Place of Purchase Serial Number
Proof of purchase is required to make a claim under warranty.
Thermoscreens Ltd
St. Mary’s Road
Nuneaton
Warwickshire
England
CV11 5AU
Email: sales@thermoscreens.com — http://www.thermoscreens.com
Tel: +44 (0) 24 7638 4646 — Fax: +44 (0) 24 7638 8578
4. INTRODUCTION
T9901008-1-1 UK (v9) Page | 5
The following items are supplied in the box at delivery.
The following tools are required for installation:
5. DELIVERY CONTENTS
6. TOOLS REQUIRED
NOTE: If any parts are missing or damaged contact your place of purchase.
PHV Surface Mounted Air Curtain Ecopower Remote Control
(for Electric and Water Heated units)
Note: End caps are supplied loose to
be fitted during installation
Supplied with 6m RJ Control Cable
Outdoor Air Thermostat
(Optional – supplied by Installer)
Wall Brackets and
M6 Fixing Bolts
3-port control valve
(for water heated units)
Fitted in pipework to
air curtain b
y
installer
Used for simple weather
compensation control
(disables heating on a warmer day)
Flat blade screwdrivers  Pozi head screwdrivers  10mm spanner  Adjustable spanner
Electric drill
Ladders Appropriate lifting equipment
Remote Control Switch
(for Ambient units)
3 brackets for
PHV1500/2000 units
T9901008-1-1 UK (v9) Page | 6
Fig 1
Fig 2
4000mm
100mm
Fig 1
The air curtain is designed to be located horizontally over a doorway. It must not be installed outside of the building.
7.1 Location
Mount the air curtain above and as close to the doorway as possible, with:
the discharge grille not more than 4m above floor level  at least 100mm clearance (air gap) above electric/water
heated air curtains, see Fig 1
Beware of doorway top edges, structural beams, door opening/closure devices, etc., which may interfere with the air stream and affect the location of the unit.
7.2 Wall Fixing
Step 1 Bolt all wall brackets to the rear face of the unit
as shown in Fig 2, using the M6 fixing bolts supplied.
Step 2 Drill fixing points in the wall, referring to
Appendix 1 for correct positioning.
Step 3 Screw in the top wall bolts leaving a small gap
between the screw head and the wall.
Step 4 Lower the unit onto the bolts via the key-hole
slots in the top of the wall brackets and screw in the bottom wall bolts.
Step 5 Tighten all fixing bolts until the air curtain is
safely secured to the wall.
7. INSTALLATION
NOTE: Use suitable wall fixing bolts (not supplied) to fix the unit to the wall, taking into account the
type of wall and the weight of the unit (see section 3: Specifications).
NOTE: For the air curtain to work well the width of the open doorway should be less than the length
‘A’ of the air curtain, see Appendix 1.
T9901008-1-1 UK (v9) Page | 7
Fig 3
7.3 Ceiling Suspension
M10 threaded rods (not supplied) are used to suspend the unit from the ceiling.
Suspend the unit from the ceiling as follows:
Step 1 Screw the threaded rods into all of the holes in the
top face of the unit as shown in Fig 3.
Step 2 Fit M10 locking nuts (not provided) to prevent the
rod rotating and coming away from the casing.
Step 3 Secure each suspe nsion rod to a suitable structure that can support the weight of the unit (see
section 3: Specifications for weights).
7.4 LPHW Models
For LPHW models ensure that water isolation valves are fitted in the flow and return pipework adjacent to the air curtain and connected correctly as shown in the diagram in Appendix 1.
For the design of the water pipework system and pump, water flow rates and pressure drops for maximum heat output of the air curtain are given in Table 2 below.
Air Curtain Water Flow Rate
(l/min at 82/71°C)
Water Pressure Drop
(kPa)
PHV1000W, 2-row (12kW) 15.6 5.0 PHV1500W, 2-row (18kW) 23.4 9.5 PHV2000W, 2-row (24kW) 31.2 14.7
Air Curtain Water Flow Rate
(l/min at 60/40°C)
Water Pressure Drop
(kPa)
PHV1000W, 3-row (12kW) 8.6 9.7 PHV1500W, 3-row (18kW) 12.9 10.0 PHV2000W, 3-row (24kW) 17.1 18.3
NOTE: Do not screw hanging rods too far in as they
could interfere with internal components.
WARNING: It is the sole responsibility of the installer to ensure that the fixing locations and
suspension system used are suitable for the air curtain being installed.
NOTE: Water Pressure Drop is across the flow and return pipework to the air curtain and includes for the
coil fitted inside the unit and the valve fitted in the heating pipework to the unit. Water flow rates and pressure drops at different water temperatures can be calculated using the Thermoscreens coil calculation programme. Visit the Thermoscreens website for details.
Table 2
T9901008-1-1 UK (v9) Page | 8
Fig 4
2
1
Fig 6
The installer must connect the 3-port valve in the heating pipework as shown in Figure 4 below:
22mm pipe
A
B
A/B
22mm pipe
22mm pipe
22mm pipe
R E T U R N
F L O W
8.1 How to access terminals
To gain access to the air curtain for connection and commissioning, remove air inlet grilles and bottom access panel as explained below.
First remove the plastic end caps at each end of the unit, if fitted, by pulling off to the side.
8.1.1 Remove air inlet grilles
Using a Pozi No 1 screwdriver, remove each grill with its filter.
To remove, insert screwdriver into the elongated hole at the bottom corner of the grille (see Fig 5) and turn the screw one quarter of a turn anticlockwise.
8.1.2 Remove bottom access panel
Unfasten the securing screw at each end (see 1, Fig 6) and, if applicable, two screws in the centre (PHV1500 and PHV2000 units only).
To remove, slide the access panel (see 2, Fig 6) out forwards.
8. ACCESS FOR ELECTRICAL CONNECTION
NOTE: All air curtain panels are protected in a plastic film. When access panels are removed this
film can be removed.
wire valve to pcb inside air curtain
Fig 5