Thermoscreens C Series, C1000AR, C1500AR, C2000AR, C1000WR Installation, Operation And Maintenance Instructions

...
Page 1
AIR CURTAIN
C RECESSED RANGE
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
T9901013-1-1 CAN-USA-ENG (v9) Page | 1
English
Page 2
1 CONTENTS
CONTENTS ...................................................................................................................................... 2
1
2 ELECTRICAL SAFETY ..................................................................................................................... 3
3 SPECIFICATIONS ............................................................................................................................ 3
4. INTRODUCTION .............................................................................................................................. 4
5. DELIVERY CONTENTS ................................................................................................................... 5
6. TOOLS REQUIRED .......................................................................................................................... 5
7. INSTALLATION ................................................................................................................................ 6
8. LPHW MODELS ............................................................................................................................... 9
9. REMOTE CONTROL INSTALLATION ........................................................................................... 10
10. REMOTE CONTROL SETTINGS ................................................................................................... 10
11. EXTERNAL CONTROLS ................................................................................................................ 11
12. MULTIPLE AIR CURTAIN SYSTEMS ............................................................................................ 12
13. SYSTEM CONFIGURATION .......................................................................................................... 13
14. FAN SPEED SELECTION .............................................................................................................. 14
Page
15. REMOTE CONTROL OPERATION ................................................................................................ 15
16. COMMISSIONING THE SYSTEM .................................................................................................. 16
17. SIGN OFF ....................................................................................................................................... 16
18. FAULT CONDITIONS ..................................................................................................................... 17
19. SERVICE & MAINTENANCE ......................................................................................................... 18
20. WARRANTY ................................................................................................................................... 19
APPENDIX 1 — Dimensions of C Recessed Air Curtain .......................................................................... 20
APPENDIX 2A — WIRING DIAGRAM C1000ER and C1500ER 208V .................................................. 21
APPENDIX 2B — WIRING DIAGRAM C2000ER 208V ......................................................................... 22
APPENDIX 2C — WIRING DIAGRAM C1000ER and C1500ER 480V or 600V .................................... 23
APPENDIX 2D — WIRING DIAGRAM C2000ER 480V or 600V............................................................ 24
APPENDIX 2E — WIRING DIAGRAM C1000WR, C1500WR and C2000WR ....................................... 25
APPENDIX 2F — WIRING DIAGRAM C1000AR, C1500AR and C2000AR ........................................... 26
T9901013-1-1 CAN-USA-ENG (v9) Page | 2
Page 3
2 ELECTRICAL SAFETY
Electrical Supply and Wiring to the Air Curtain
All electrical wiring and connections MUST be carried out by a competent qualified electrici an in accordance with the latest edition of national and local wiring regulations and/or local statutory regulations. “Danger: Disconnect electrical supply before servicing”
A 1 phase or 3 phase local Disconnect, provided by others in accordance with Electrical Code
and Local Electrical Codes, with a contact separation of at least 3mm (1/8in) on all poles, must be fitted in the electrical supply to the air curtain and located in an accessible position adjacent to the unit. Units with dual electrical supplies (see * in Table below) must have a common disconnect to switch off both supplies simultaneously.
The appliance must be connected by cables having an appropriate heat resistant temperature
rating.
All supply cables, circuit breakers and other electrical installation equipment must be correctly
sized for the air curtain model being installed; see Section 3: Specifications.
Models operating on a 480V or 600V, 3 phase electrical supply - see Section 3:
Specifications, Electrical Supply * – also need a separate 208V to 240V electrical supply to operate fan motors and controls.
A 25mm / 1in size cable gland or conduit connector of IP21 rating should be used for the
Electrical Supply into the air curtain.
See Wiring Diagrams for connecting electrical supply and control cables to the air curtain. The
air curtain must be grounded.
3 SPECIFICATIONS
Rated
Air Curtain
Model No
Electrical Supply
(V/ph/Hz)
Electrical
Power Input
(kW)
C1000AR 208…240/1/60 0.115 0.5 – 19 / 42 C1500AR 208…240/1/60 0.161 0.7 – 25 / 55 C2000AR 208…240/1/60 0.23 1.1 – 35 / 77
C1000WR 208…240/1/60 0.115 0.5 3.0 / 6.0 22 / 49 C1500WR 208…240/1/60 0.161 0.7 4.5 / 9.0 30 / 66 C2000WR 208…240/1/60 0.23 1.1 6.0 / 12.0 41 / 90 C1000ER (208V) 208/3/60 8.755 24.5 4.32 / 8.64 20 / 44 C1500ER (208V) 208/3/60 11.693 32.7 5.766 / 11.532 27 / 60 C2000ER (208V) 208/3/60 17.51
C1000ER (480V) C1500ER (480V) C2000ER (480V) C1000E (600V) C1500E (600V) C2000E (600V)
480/3/60 *
+ 208…240/1/60
480/3/60 *
+ 208…240/1/60
480/3/60 *
+ 208…240/1/60
600/3/60 *
+ 208…240/1/60
600/3/60 *
+ 208…240/1/60
600/3/60 *
+ 208…240/1/60
9
0.115 12
0.161 18
0.23 9
0.115 12
0.161 18
0.23
** NOTE. Electric heater circuit current = 47.9 Amps
Rated
Current per
phase (A)
49.0 **
10.9
0.5
14.5
0.7
21.7
1.0
9.3
0.5
12.8
0.7
18.6
1.0
Heat Output
[Low/High]
(kW)
8.64 / 17.28 37 / 82
4.5 / 9.0 20 / 44
6.0 / 12.0 27 / 60
9.0 / 18.0
4.5 / 9.0
6.0 / 12.0
9.0 / 18.0 37 / 82
Weight
(kg / lbs)
37 / 82 20 / 44 27 / 60
Table 1
T9901013-1-1 CAN-USA-ENG (v9) Page | 3
Page 4
4. INTRODUCTION
Established in the 1960s, Thermoscreens is a leading air curtain manufacturer that exports to over 60 countries worldwide.
As with all our products, the C Recessed range of air curtains is designed with energy efficiency in mind.
C models suffixed ER, WR or AR are designed to be surface mounted inside a building and located horizontally over a doorway.
They must not be installed on the outside of a building or built into a cabinet or recessed in any way.
“Caution: This equipment has been investigated with regard to safety from electrical fire and shock hazard only. The mechanical features have not been investigated and are subject to approval by the inspection authority having jurisdiction.”
Please complete the following details for your reference:
Date of Purchase Place of Purchase Serial Number
Proof of purchase is required to make a claim under warranty.
Thermoscreens Canada Toll Free: 877 445 3739 11 King Street, Unit #3 Tel: 705 797 0012 Barrie, Ontario Fax: 705 797 0013 Canada L4N 6BS Email: salescanada@thermoscreens.com
http://www.thermoscreens.com
T9901013-1-1 CAN-USA-ENG (v9) Page | 4
Page 5
5. DELIVERY CONTENTS
pp
y
y
The following items are supplied in the box at delivery.
NOTE: If any parts are missing or damaged contact your place of purchase.
The recessed grille is
C Recessed Air Curtain Ecopower Remote Control
Supplied with
Recessed Grille
lied separatel
su
3-port control valve
(for water heated units)
Fitted in pipework to
air curtain b
installer
Outdoor Air Thermostat
(Optional – supplied by Installer)
Used for simple weather
compensation control
(disables heating on a warmer day)
6m
/ 20ft RJ Control Cable
6. TOOLS REQUIRED
The following tools are required for installation:
Flat blade screwdrivers  Phillips head screwdrivers 10mm wrench Adjustable wrench
T9901013-1-1 CAN-USA-ENG (v9) Page | 5
Electric drill
 Ladders  Appropriate lifting equipment  Appropriate tools for cutting ceiling aperture
Page 6
7. INSTALLATION
The air curtain is designed to be recessed within ceiling voids or bulkheads with in a building and located horizontally over a doorway. It must not be installed outside of the building.
7.1 Location
Mount the air curtain above and as close to the doorway as possible, with:
the recessed grille not more than:
2.6m / 8ft 6in above floor level - 208v operation
3.0m / 9ft 10in above floor level - 230v operation
the air discharge (see 1, Fig 1) section of the
recessed grille nearest the doorway and the air inlet section (see 2, Fig 1) furthest from the doorway
Beware of doorway top edges, structural beams, door opening/closure devices, etc., which may interfere with the air stream and affect the location of the unit.
NOTE: For the air curtain to work well the doorway should be less than the width of the airstream.
7.2 Ceiling Suspension
Step 1 Cut an aperture in the ceiling to the dimensions in
Appendix 1. Cut notches, if necessary, to clear screws in the air curtain casing.
NOTE: For LPHW models, pipework will need to be installed
Step 2 Fix M8 or 5/16 UNC threaded rods (not supplied)
NOTE: Do not let these four hanging rods come below the
above the curtain. Allow sufficient access and height clearance within the ceiling void to do this.
through the 2 holes at each end in the top casing (see Fig 2). Feed the rods through the casing and attach to fixing brackets near the bottom of the unit (see Fig 3, looking up into the air curtain). Use M8 or 5/16 UNC lock-nuts either side of the fixing brackets to secure the hanging rods.
bottom of the unit casing or they may prevent the recessed grille fitting properly.
Fig 1
Fig 2
Fig 3
2
1
T9901013-1-1 CAN-USA-ENG (v9) Page | 6
Page 7
5
M8
or
UNC hanging rods
16
RECESSED AIR CURTAIN
CEILING LEVEL CEILING LEVEL
25 - 50 mm
1 - 2 inch
Bottom surface of recessed air curtain casing
25 - 50 mm
1 - 2 inch
Fig 4
Step 3 Secure each rod to a suitable structure that can support the weight of the unit (see Section 3:
Specifications for weights).
Step 4 Adjust the height of the unit on its hanging rods so the bottom surface of the casing goes
between 25-50mm or 1 to 2 inches up into the ceiling as shown in Fig 4. Ensure the unit is level.
WARNING: It is the sole responsibility of the installer to ensure that the fixing locations and
suspension system used are suitable for the air curtain being installed.
7.3 Attaching the recessed grille to the air curtain
The recessed grille consists of:
Metal frame Hinged inlet/discharge grille  Slotted fixing brackets
There are 4 fixing slotted brackets on the C1000R, C1500R and 6 brackets on the C2000R (see Fig 5).
Fix the grille as follows:
Step 1 Open the hinged inlet grille using a flat bladed
screwdriver to release the quarter turn fasteners (see Fig 6). There are two fasteners on the C1000R unit and three fasteners on C1500R and C2000R units. Before lifting the grille frame into position, remove four (six on C2000R) M6 bolts fitted on the inside edge of air curtain.
Fig 5
Fig 6
Centre brackets for C2000R
T9901013-1-1 CAN-USA-ENG (v9) Page | 7
Page 8
Step 2 Make sure the grille will go the correct way around
(discharge nearest to doorway). Offer the recessed grille up through the cut-out in the ceiling.
Step 3 Using the M6 bolts removed in Step 1, secure grille by
fixing each bolt through the slotted brackets as shown in Fig 8. With the hinged grille open, adjust the height of the grille frame via slots in each bracket, so frame is snug fit against the ceiling with no gaps all the way around.
Step 4 To stop discharge air re-circulating within the air curtain
a sliding separator will need adjusting up or down (see Fig 9). To adjust plate release M6 bolts either end, extend the slide plate so that it will touch the topside of the grille along its whole length and tighten the bolts. It will be necessary to close the hinged grille core to gauge where the separator plate should be fitted.
Step 5 Once the above steps are complete the hinged grille
core can be closed and all the quarter turn fasteners tightened up.
Fig 7
Fig 8
Fig 9
Fig 10
NOTE: Open the hinged grille core to gain access to electrical connections, and for servicing an d
maintenance.
T9901013-1-1 CAN-USA-ENG (v9) Page | 8
Page 9
8. LPHW MODELS
For LPHW models ensure that water isolation valves are fitted in the flow and return pipework adjacent to the air curtain and connected correctly as shown in the diagram in Appendix 1.
For the design of the water pipework system and pump, water flow rates and pressure drops for maximum heat output of the air curtain are given in Table 2 below.
Air Curtain Water Flow Rate
(l/min at 82/71°C / US Gall/min at 180/160°F)
C1000W, 1-row
(6kW)
C1500W, 1-row
(9kW)
C2000W, 1-row
(12kW)
NOTE: Water Pressure Drop is across the flow and return pipework to the air curtain and includes for the
coil fitted inside the unit and the valve fitted in the heating pipework to the unit. Water flow rates and pressure drops at different water temperatures can be calculated using the Thermoscreens coil calculation programme. Visit the Thermoscreens website for details.
7.8 / 2.1 5.1 / 0.74 / 1.7
11.7 / 3.1 10.9 / 1.58 / 3.6
15.6 / 4.1 19.7 / 2.86 / 6.6
The installer must connect the 3-port valve in the heating pipework as shown in Figure 11 below:
Water Pressure Drop
(kPa / psi / ft H2O)
Table 2
22mm pipe
22mm pipe
A
B
wire valve to pcb inside air curtain
A/B
22mm pipe
22mm pipe
R E T U R N
Fig 11
F L
O
W
T9901013-1-1 CAN-USA-ENG (v9) Page | 9
Page 10
9. REMOTE CONTROL INSTALLATION
Mount the Ecopower remote control in a convenient position directly to the wall or onto a switch box.
9.1 Wall mounting
Step 1 Using a screwdriver undo the scre w on the top of the remote control
case and pull the back case away (see Fig 7).
Step 2 Feed one end of the RJ control cable through the back case, secure it,
then screw the back case to the wall using suitable fixings (not supplied).
Step 3 Connect the RJ plug to the RJ socket on the PCB in the remote control.
Step 4 Refit the front case.
9.2 Switch box mounting
Step 1 Using a screwdriver undo the screw on the top of the remote control case and pull the back
case away (see Fig 7).
Step 2 Feed one end of the RJ control cable through the switch box, feed and
secure the RJ control cable through the back case and secure ba ck case to switch box using 2 mounting screws (not supplied) (see Fig 8).
Step 3 Connect the RJ plug to the RJ socket on the PCB in the remote
control.
Step 4 Refit the front case.
NOTE: For optional remote control settings see Section 10.
Fig 7
23/8in
Fig 8
10. REMOTE CONTROL SETTINGS
On the back of the PCB inside the Ecopower Remote Control you will find four DIP switches that provide the following optional features, see Table 3:
DIP Feature Explanation Default Notes
1 Reset on power-up On restoring power after an
electrical interruption all Remote Control settings are retained
2 Stop fan on cold Fans are switched off when
heating level is achieved (AUTO mode only)
3 Never blow cold Air curtain always heats in
AUTO mode
4 Room air
temperature control
T9901013-1-1 CAN-USA-ENG (v9) Page | 10
Enables the room air sensor in the Remote Control
ON WARNING! – Fans start
on their own after power is restored
OFF
OFF Will not go to ambient
mode
OFF Disables all other
temperature sensors
Table 3
Page 11
11. EXTERNAL CONTROLS
11.1 Remote switch contacts IN0, IN1
Terminals IN0 and IN1 on the Ecopower PCB inside the air curtain can be used to provide different control strategies using remote volt-free contacts (see Fig 9). This could be to provide remote On/Off from a timer or BMS Digital/Output contact, to work with a door switch or for simple weather compensation control to disable heating when outdoor air temperatures become warmer. Table 4 describes the different functions:
Fig 9
Table 4
Function
Remote
On/Off
(INHIBIT)
Function
Door
Switch
Control
Summer
Winter
NOTE: Wire volt-free, remote switch contacts to 2-way screw terminals IN0 and IN1 using 2-core
WARNING: Do not apply any voltage to terminals IN0 and IN1 as this will damage the Ecopower
* NOTE: The Ecopower Remote Control must stay plugged-in for the air curtain to keep working.
Unit operates normally in MANUAL Mode or AUTO Mode from the Remote Control
After 30s the heating is disabled and the fan goes to low speed
Unit operates normally in MANUAL Mode or AUTO Mode from the Remote Control
COLD DAY
cable.
PCB inside the air curtain.
An optional plug-in EEPROM is available from Thermoscreens so the Remote Control can be un­plugged and the air curtain stay working. Visit the Thermoscreens website for details.
IN0
Unit switches off after 15s, with fan run-on at Medium fan speed if DIP 2 = OFF
IN1
Unit operates normally in MANUAL Mode or AUTO Mode from the Remote Control Heating is disabled straight away, Fan speeds operate normally from the Remote Control
WARM DAY
Notes
Use the Remote Control to set up unit and then hide it away if required. *
On/Off is then done via IN0 using a remote volt-free contact.
DIP 4 IN0 Notes
ON
OFF
Door Open:­ Normal Control
Door Closed:­ Heating Off Low Fan Speed Simple weather compensation control using an outdoor air thermostat with volt free contacts (see Section 11.3)
T9901013-1-1 CAN-USA-ENG (v9) Page | 11
Page 12
11.2 Overheat safety cut-out indication
A
g
t
For electric heated air curtains the Ecopower PCB includes a fault indication signal for if the overheat safety cut-out on the electric heater operates.
Volt free changeover contacts (6A 250VAC 30VDC) can be wired via the 3-way screw terminal “HEALTHY” (see Fig 10).
Refer to Section 18.1: Overheat safety cut out, for how to reset a overheat safety cut-out situation.
Fig 10
NO
HEALTHY
NC
LARM!
C
11.3 Weather compensation control (Summer/Winter)
To save heating energy on warmer days a simple weather compensation (Summer/Winter) heat control strategy can be used. Fit an outdoor air thermostat with volt-free contacts (supplied by the installer) to a north facing wall.
Use a 2-core cable to connect the outdoor air thermostat to 2-way terminal IN1 on the Ecopower PCB (see Fig 11)
On the Ecopower PCB, set DIP 4 to OFF as per Table 4, (see Section 11.1: Remote switch contacts IN0, IN1).
Switch Contact Closed = Heating Enabled (cold day)
Switch Contact Open = Heating Disabled (warm day)
WARNING: Do not apply any voltage to terminal IN1 as this will damage the Ecopower PCB.
NOTE: To promote increased energy saving a more advanced weather compensation control strategy is available from
Thermoscreens. Using a heating curve, the discharge air temperature of the airstream coming from the air curtain is controlled a
ainst the outside air temperature. Visit the Thermoscreens website for details.
Fig 11
Outdoor Air Thermosta
12. MULTIPLE AIR CURTAIN SYSTEMS
For master/slave control, plug and connect units together with Thermoscreen RJ extension cables (not supplied) as per Figure 12 below. Each air curtain must have its own electrical supply.
T9901013-1-1 CAN-USA-ENG (v9) Page | 12
maximum 8 units
Fig 12
Page 13
13. SYSTEM CONFIGURATION
13.1 Optional features
WARNING: Isolate and disconnect air curtain from the power source before making any changes.
DIP switches on the air curtain Ecopower PCB (see Fig 13) provide the following optional features, as explained below:
Fan heat interlock  Disable fan run-on  Thermostat master (for master/slave installations)  Weather compensation heat control (Summer/Winter)  Door switch control
Feature
DIP setting Default Notes
Fan heat interlock
Allows fan speed to govern heat output on electric heated units.
If low or medium fan speed is selected, a lower heat output
DIP 1
ON
1234
ON
Heat output is governed by fan speed.
results. High heat operates only on high fan speed.
Disable fan run-on
The 2 minute fan run-on after switch off is enabled or disabled on electric heated air curtains.
Thermostat master For master/slave installations. Only the air sensor in the thermostat master air curtain is used to measure air temperature.
DIP 2
ON
1234
DIP 3
ON
1234
OFF
Fan run-on at medium speed enabled.
OFF
Air curtains in master/slave systems all act
independently. Set DIP 3 to ON in the air curtain that will be the master unit.
Weather compensation control or Door switch control
Simple weather compensation control to save heating energy. or Door switch control.
NOTE: Black rectangle is moveable head of DIP switch.
NOTE: A range of advanced factory fitted and plug-in control options are available from Thermoscreens to
enhance the performance of the Ecopower PCB controller inside the air curtain. These include advanced weather compensation control using a heating curv e, outlet air temperature control, ECObus strategies. Visit the Thermoscreens website for details.
®
Modbus BMS control, modulating heater outputs and EEPROMs for non-standard control
DIP 4
ON
1234
OFF
IN1 Weather
compensation
ON
IN1 Door switch
T9901013-1-1 CAN-USA-ENG (v9) Page | 13
Fig 13
This feature is only used with electric heated air curtains to limit very high air temperatures.
Set DIP1 to OFF if unit is water heated or ambient.
Must only be used for water heated or ambient air curtains. Each air curtain must have DIP2 set to ON for no fan run-on. Air sensor thermistors in all slave air curtains will be ignored.
Stops some units blowing cold air and others blowing warm air in master/slave systems on larger doorways. See section 11.1 Remote Switch Contacts IN0 and IN1 for details
Weather compensation control is the same as Summer/Winter control
Page 14
14. FAN SPEED SELECTION
Factory settings for the 3 fan speeds are shown in Tables 5 or 6 below:
Fan running on 208V (refer to wiring diagrams in Appendix 2)
Table 5
Fan Speed
HIGH
(black wire)
MEDIUM
(blue wire)
LOW
(red wire)
Maximum air
velocity at
outlet grille
(
m/s / ft/min)
7.5 / 1475 2.6 / 8ft 6in
Maximum air curtain
mounting height
(
m / ft)
Sound Pressure
Level of air
curtain
[dB(A) at
3m /10ft]
C1000R - 54 C1500R - 54 C2000R - 55 C1000R - 50 C1500R - 50 C2000R - 51 C1000R - 45 C1500R - 45 C2000R - 46
Air Volume
Flow Rate
(
m3/h / cfm)
1125 / 660 1620 / 955
2250 / 1325
1115 / 655 1600 / 940
2225 / 1310
975 / 575
1405 / 825
1950 / 1150
Fan running on 230V (refer to wiring diagrams in Appendix 2)
Sound Pressure
Level of air
curtain
[dB(A) at
3m /10ft]
C1000R - 55 C1500R - 55 C2000R - 56 C1000R - 53 C1500R - 53 C2000R - 54 C1000R - 50 C1500R - 49 C2000R - 50
Air Volume
Flow Rate
(
m3/h / cfm)
1250 / 740 1800 / 1060 2500 / 1470
1140 / 670
1640 / 965 2275 / 1340
1025 / 605
1475 / 870 2050 / 1205
Fan Speed
HIGH
(black wire)
MEDIUM
(blue wire)
LOW
(red wire)
Maximum air
velocity at
outlet grille
m/s / ft/min)
(
8.0 / 1575 3.0 / 9ft 10in
Maximum air curtain
mounting height
(
m / ft)
Sound pressure levels dB(A) at 3m/10ft distance are for a single air curtain mounted at its maximum mounting height, operating in a room with average acoustic characteristics as defined in CIBSE Guide B5 (reverberation time 0.7s at 1kHz) and a room size equivalent to 8 air changes per hour (ac/h). Care needs to be taken when selecting air curtains for an installation as noi se levels can be several dB higher if the mounting height is reduced, if the room is more ‘live’ (i.e. hard surfaces, no furnishings or absorbent materials), if the room is smaller than 8 ac/h equivalent or a combination of these fact ors. Noise levels will also increase if more than one air curtain is installed at the same doorway (e.g. +3dB(A) for 2 equal point sources: direct field).
T9901013-1-1 CAN-USA-ENG (v9) Page | 14
Page 15
15. REMOTE CONTROL OPERATION
Use the Remote Control to operate the air curtain as follows:
1
2
1 On/Off
Turns the air curtain On or Off.
NOTE: If an electric heated air curtain is heating when switched off the fan will run-on for
approximately 2 minutes to dissipate excess heat.
7
Heating level scale
6 4
3
5
2 Manual/Automatic
Switches between Manual and Automatic modes. The Auto On indicator LED is lit for "Auto Mode" and unlit for "Manual Mode".
3 & 4 Heating level controls
Manual mode
Select heating level from zero, to half heat, to full heat by stepping up or down with the heating level controls. The heating level scale shows the level selected.
Automatic mode
Heat output is controlled automatically according to:
Inlet air temperature, or  Room air temperature
This is dependent on the settings made in Section 10: Remote Control Settings (DIP switch 4).
5, 6 & 7 Fan speed
Switch fan speed between Low, Medium and High respectively. The appropriate LED illuminates.
NOTE: On C A (Ambient – non heated) units the LED indicators on the Heating level scale and
AUTO button still illuminate but are ignored as nothing happens in the air curtain.
T9901013-1-1 CAN-USA-ENG (v9) Page | 15
Page 16
16. COMMISSIONING THE SYSTEM
16.1 Verify system operation
To commission the system, verify the following conditions are met:
All fans are working.  Fans operate at Low, Medium and High speeds.  There is no excessive mechanical noise coming from the fans.  When heating is selected, the air stream from the discharge grille warms up across the whole
length of the air curtain.
When set to manual with fans set to high speed, heating increases as higher heat is selected.  Warm air reaches across the doorway with door open or closed.  Ecopower Remote Control operates correctly in both manual and auto modes.
16.2 Instruct customer and hand over
Before leaving site, hand over the installation to the customer/end user or their representative.
Explain that any person operating the air curtain must be given supervision and instruction by the person responsible for their safety, concerning the safe use of the unit and to understa nd any hazards involved. Children and those with reduced physical, sensory or mental capabilities should not operate the air curtain.
Recommend that the doorway should be closed whenever possible but that during times of high pedestrian use it will become an ‘open doorway’. The air curtain then serves an essential purpose by saving energy and providing comfort to occupants.
Explain that the inlet grilles and air filters (if fitted) must be cleaned regularly and the unit serviced at schedule intervals – see section 19: Service & Maintenance.
NOTE: Leave these instructions with the customer/end user or their representative!!
17. SIGN OFF
Complete the following once commissioning is completed:
Installer signature Customer signature Installer name Installer company Customer company Date
T9901013-1-1 CAN-USA-ENG (v9) Page | 16
Customer name
Date
Page 17
18. FAULT CONDITIONS
18.1 Overheat Safety cut-out
An overheat fault in electric heated units may cause the overheat safety cut-out(s) to operate.
This is indicated by flashing LEDs on the Remote Control and a red status LED on the Ecopower PCB inside the air curtain.
Before resetting ensure there is adequate air flow from the air curtain and the unit has been commissioned as per section 16.
To reset a overheat safety cut-out:
Step 1 Switch off the electrical supply to the air curtain.
Step 2 Allow time for the air cu rtain to cool down, typically 10 minutes.
Step 3 Switch on the electrical supply to the air curtain.
Step 4 Press the Auto button on the Ecopower remote control 4 times.
Air curtain heaters will then operate and after 30 seconds the LEDs on the remote control will stop flashing and the status LED on the Ecopower PCB in the air curtain will flash green.
18.2 Fuses
In the event of an electrical fault internal electrical fuses may operate.
There are two 6.3A(T) internal fuses located in two DIN-rail fused terminals inside the air curtain
There are also two internal fuses located on the Ecopower PCB inside the air curtain:
Fuse 6.3A(T) supplies the fan motors within the air curtain  Fuse 100mA(F) controls the circuitry of the Ecopower PCB
18.3 Ecopower PCB status indication
There is a status LED on the Ecopower PCB inside the air curtain (See LED shown on Wiring Diagrams in the Appendix).
This indicates the status of the Ecopower Control system as follows:
1. LED flashing green – operation normal
2. LED flashing red – low supply voltage, remote control not plugged in or RJ cable fault
3. LED permanently red – overheat safety cut-out(s) open circuit from an overheat situation. Indicators on Ecopower Remote Control also flash! (see Section 18: Fault Conditions for how to reset)
T9901013-1-1 CAN-USA-ENG (v9) Page | 17
Page 18
19. SERVICE & MAINTENANCE
WARNING: Failure to adequately maintain the unit and provide a suitable cleaning schedule will
19.1 Every week
NOTE: Weekly maintenance can be carried out by the Cleaner or Janitor from floor level.
Turn off the air curtain to prevent dust entry, then clean the face of the recessed grille using a vacuum cleaner with an extension tube and brush.
19.2 Every 3 months
WARNING: Before servicing, isolate and disconnect the air curtain from the electrical power.
WARNING: The following servicing and maintenance must be carried out by a competent
Clean and inspect the inside of the air curtain as follows:
Step 1 Open the hinged inlet grille using a flat bladed screwdriver to release the quarter turn
Step 2 Clean and remove any build-up of dust and dirt within the air-curtain (inlet/outlet grilles,
NOTE: Build-up of dirt on fan impellers can cause vibration, noise and excessive wear on the
Step 3 Check within the unit to ensure all electrical connections and crimped terminals are tight
Close and secure hinged inlet grille after servicing. Reconnect electrical supply and test to en sure correct operation (see Section 16: Commissioning).
result in a loss of performance and reduced life expectancy of the air-curtain and possible overheating and fire risk with electric heated units.
electrician or a Thermoscreens appointed technician.
fasteners (see Fig 6, Section 7.3).
electric heaters, fan impellers, housings and motors) using a vacuum cleaner and soft brush.
motor bearings.
and that all cables are in good condition.
T9901013-1-1 CAN-USA-ENG (v9) Page | 18
Page 19
20. WARRANTY
All units are covered by a two year warranty.
Failure to adequately maintain the unit may void the warranty. If any problems are encountered, please contact your installer/supplier.
Failing this please contact Thermoscreens Canada.
Care has been taken in compiling these instructions to ensure they are correct. Therm oscreens Canada disclaims all liability for damage resulting from any inaccuracies and/or deficiencies in this documentation. Thermoscreens Canada retain the right to change the specifications stated in these instructions.
Thermoscreens Canada Toll Free: 877 445 3739 11 King Street, Unit #3 Tel: 705 797 0012 Barrie, Ontario Fax: 705 797 0013 Canada L4N 6BS Email: salescanada@thermoscreens.com
T9901013-1-1 CAN-USA-ENG (v9) Page | 19
Page 20
301 / 11.9
353 / 13.9
25 - 50
1.0 - 2.0
C1000R C1500R C2000R
1129 / 44.5 1529 / 60.2 2040 / 80.3
A
140 / 5.5 150 / 5.9140 / 5.5
1179 / 46.4 1579 / 62.2 2090 / 82.3
1209 / 47.6 1609 / 63.4 2120 / 83.5
B
C
301 / 11.9 301 / 11.9 301 / 11.9
1179 / 46.4 1579 / 62.2 2090 / 82.3
D
Width
Length
Ceiling
cut-out
CEILING LEVEL
165 / 6.533 / 1.3
D
l
a c
i
r
t
c
s
l
e
o
l
e
r
t
r
n
o
o
f
c
s
t
d
n
n
i
a
o p
y
l
y
p
r
p
t
n
u
E
s
Rp½ / ½ in. BSPP
LPHW connections
B
C
A
) drop rods
or M8
UNC (
16
5
4 x Holes for
Use all 4 drop rod holes !
mm / inch
206 / 8.1
T9901013-1-1 CAN-USA-ENG (v9) Page | 20
257 / 10.122 / 0.9 22 / 0.9
APPENDIX 1 — Dimensions of C Recessed Air Curtain
Page 21
A*
A1
A2
Black
13NO
1m - 12.0A
1.5m - 16.0A
Red
Black
Blue
1m - 12.0A
1.5m - 16.0A
14NO
5
6
3
4
230V AC Coil
1
2
CONTACTOR
K2
A1
A2
13NO
14NO
5
6
3
4
230V AC Coil
1
2
CONTACTOR
K1
Red
Black Blue
Red
Black Blue
1.44 kW (x3 - 1m)
1.922 kW (x3 - 1.5m)
1.44 kW (x3 - 1m)
1.922 kW (x3 - 1.5m)
2
*
(top elements)
Second Stage Heating
(bottom elements)
First Stage Heating
2
*
1~
Fan Motor 1
B*
White (COMMON)
0
White
5x20mm, glass bodied
F1 = F100mA F2 = T6.3A
Healthy
Alarm
Red
85°C Auto
Thermal Trip
J1
F2 F1
NC C NO
J2
LED
IN0
IN1
J6
R 0 -10V
J5
Summer/Winter
or Door Contact
F3, F4 = T6.3A, 5x20mm, glass bodied
F4
F3
L1
L2
L1
L2
L3
L3
BLOCK
TERMINAL
L1
L2
e
l
b
a C e
v
a
l
S
/
r
e
t
s
a M
Th
J9
ON
1234
REMOTE
CONTROL
White
J10
EEPROM
Black rectangle is
Red
1
J12
J11
moveable head of
Yellow
2
3
L1
DIP switch
4
6
5 L2
J14
High speed
Med speed
Low speed0VHigh speed
Fan 2 Fan 1
Black
Black
9
8
7
Med speed
Blue
10 N
L3
J16
ECO-Power CVR1008-9
0V
Low speed
J17
White
Red
Yellow
Orange
Blue (Med)
234
Blue
Brown
Black (High)
5
Yellow
Orange
Black
3µF
Capacitor
Red (Low)
1
Red
APPENDIX 2A — WIRING DIAGRAM C1000ER and C1500ER 208V
208V / 3ph / 60Hz
To Slave
Air Curtain
T9901013-1-1 CAN-USA-ENG (v9) Page | 21
Page 22
A*
A1
A2
Black
13NO
23.95A
Red
Black
Blue
23.95A
14NO
5
6
3
4
230V AC Coil
1
2
CONTACTOR
K2
A1
A2
13NO
14NO
5
6
3
4
230V AC Coil
1
2
CONTACTOR
K1
Red
Black Blue
Red
Black Blue
1.44 kW (x3)
1.44 kW (x3)
1.44 kW (x3)
1.44 kW (x3)
Second Stage Heating
First Stage Heating
2
*
(top elements)
2
*
(bottom elements)
1~
Fan Motor 1
B*
Red (Low)
Red
1
Blue (Med)
Blue
Black (High)
234
Black
Yellow
Orange
Brown
5
Yellow
Orange
3µF
Capacitor
Fan Motor 2
1~
White (COMMON)
012
White
Red (Low)
Yellow
Orange
Brown
Blue (Med)
Black (High)
4
3
5
Yellow
Orange
Red
Blue
Black
3µF
Capacitor
APPENDIX 2B — WIRING DIAGRAM C2000ER 208V
White (COMMON)
0
White
5x20mm, glass bodied
F1 = F100mA F2 = T6.3A
J1
F2 F1
NC C NO
Th
J2
LED
(x2)
IN1 IN0
J6
R
0 -10V
J5
Summer/Winter
or Door Contact
Red
85°C Auto
Healthy
Alarm
Thermal Trip
F3, F4 = T6.3A, 5x20mm, glass bodied
F4
F3
L1
L2
L1
L2
L3
L3
BLOCK
TERMINAL
L1
L2
e
l
b
a C e
v a
l
S
/
r
e
t
s
a M
Red
Yellow
White
1
J10
J9
ON
1234
EEPROM
Black rectangle is
REMOTE
CONTROL
2 L1
J12
J11
moveable head of
DIP switch
4
5
3
L2
J14
High speed
Med speed
Low speed0VHigh speed
Fan 2 Fan 1
Black
Blue
Red
6
White
Black
Black
9
8
7
Med speed
Blue
10 N
L3
J16
ECO-Power CVR1008-9
0V
Low speed
J17
White
Red
208V / 3ph / 60Hz
To Slave
Air Curtain
T9901013-1-1 CAN-USA-ENG (v9) Page | 22
Page 23
A*
A1
A2
13NO
1.5m - 7.2A at 480V
1.5m - 5.8A at 600V
1m - 5.4A at 480V
1m - 4.3A at 600V
Black
Blue
Red
Black
14NO
5
6
3
4
230V AC Coil
1
2
CONTACTOR
K2
A1
A2
14NO
13NO
5
6
3
4
230V AC Coil
1
2
CONTACTOR
K1
Red Black Blue
Red Black Blue
1.5 kW (x3 - 1m) 2 kW (x3 - 1.5m)
1.5 kW (x3 - 1m) 2 kW (x3 - 1.5m)
2
*
(top elements)
Second Stage Heating
(bottom elements)
First Stage Heating
2
*
1~
Fan Motor 1
B*
WARNING!
F3, F4 = T6.3A, 5x20mm, glass bodied
SOURCE OF ELECTRICAL POWER
UNIT REQUIRES MORE THAN ONE
L1
L2
BLOCK
TERMINAL
480V / 3ph / 60Hz
or 600V / 3ph / 60Hz
Disconnecting means integra l to th e u n it fo r b o t h sources of electrical powe r
L3
L1
L2
L3
is required !
F3
F4
1ph / 60Hz
208V to 240V
Red
L1
L1
85°C Auto
Healthy
Alarm
Thermal Trip
L2
L2
5x20mm, glass bodied
J1
LED
R0 -10V
J5
Summer/Winter
or Door Contact
To Slave
Air Curtain
F1 = F100mA F2 = T6.3A
F2 F1
NC C NO
Th
J2
IN1 IN0
J6
e
l
b
a C e
v
a
l S
/
r
e
t
s
a M
Red (Low)
Blue (Med)
1
Red
Blue
Black (High)
234
Black
Yellow
Orange
Brown
5
Yellow
Orange
3µF
Capacitor
White (COMMON)
0
White
Red
Yellow
White
1
J10
J9
ON
1234
EEPROM
Black rectangle is
REMOTE
CONTROL
2 L1
J12
J11
moveable head of
DIP switch
4
5
3
L2
J14
Med speed
Low speed
High speed
Fan 2 Fan 1
6
0V
High speed
Black
Blue
Black
9
8
7
Med speed
10 N
L3
J16
ECO-Power CVR1008-9
0V
Low speed
J17
White
Red
APPENDIX 2C — WIRING DIAGRAM C1000ER and C1500ER 480V or 600V
T9901013-1-1 CAN-USA-ENG (v9) Page | 23
Page 24
A*
A1
A2
13NO
10.8A - 480V
8.7A - 600V
14NO
5
6
3
4
230V AC Coil
1
2
CONTACTOR
K2
Black
Blue
Red
Black
A1
A2
13NO
8.7A - 600V
10.8A - 480V
14NO
5
6
3
4
230V AC Coil
1
2
CONTACTOR
K1
Red
Black
Blue
Red
Black
Blue
1.5 kW (x3) 1.5 kW (x3)
1.5 kW (x3)
1.5 kW (x3)
2
*
(top elements)
Second Stage Heating
(bottom elements)
First Stage Heating
2
*
1~
Fan Motor 1
B*
WARNING!
F3, F4 = T6.3A, 5x20mm, glass bodied
SOURCE OF ELECTRICAL POWER
UNIT REQUIRES MORE THAN ONE
F3
L1
L2
BLOCK
TERMINAL
480V / 3ph / 60Hz
or 600V / 3ph / 60Hz
Disconnecting means integral to the un it for b o th sources of electrical powe r
L3
L1
L2
L3
is required !
208V to 240V
F4
Red (Low)
Red
1
Blue (Med)
234
Blue
Black (High)
Black
Yellow
Orange
Brown
5
Yellow
Orange
3µF
Capacitor
Fan Motor 2
1~
White (COMMON)
0
White
Yellow
Orange
Brown
Red (Low)
Blue (Med)
Black (High)
234
5
1
Yellow
Orange
Red
Blue
Black
3µF
Capacitor
APPENDIX 2D — WIRING DIAGRAM C2000ER 480V or 600V
Red
85°C Auto
L1
L1
Healthy
Alarm
(x2)
Thermal Trip
L2
L2
5x20mm, glass bodied
J1
R
0 -10V
J5
Summer/Winter
or Door Contact
F1 = F100mA F2 = T6.3A
F2 F1
NC C NO
J2
LED
IN1 IN0
J6
e
l
b
a C e
v
a
l S
/
r
e
t
s
a M
White (COMMON)
0
White
Red
Yellow
White
1
Th
J10
J9
ON
1234
EEPROM
Black rectangle is
REMOTE
CONTROL
2 L1
J12
J11
moveable head of
DIP switch
4
3
J14
High speed
Med speed
Low speed0VHigh speed
Fan 2 Fan 1
Black
Blue
Red
6
5
L2
White
Black
Blue
7
Med speed
Black
9
8
10 N
L3
J16
ECO-Power CVR1008-9
0V
Low speed
J17
White
Red
1ph / 60Hz
To Slave
Air Curtain
T9901013-1-1 CAN-USA-ENG (v9) Page | 24
Page 25
3 PORT VALVE
TERMINAL
White
Orange
Grey
Green/Yellow
Blue
1~
Fan Motor 1
1
234
White (COMMON)
Red (Low)
0
White
Red
5x20mm, glass bodied
F1 = F100mA F2 = T6.3A
J1
F2 F1
NC C NO
Th
or Door Contact
R 0 -10V
J5
J2
LED
IN1 IN0
J9
J6
Brown
Blue
F4
F3
Summer/Winter
F3, F4 = T6.3A, 5x20mm, glass bodied
L1
BLOCK
L2
L1
L2
1ph / 60Hz
208V to 240V
e
l
b
a C e
v
a
l S
/
r
e
t
REMOTE
s
a
M
ON
1234
CONTROL
Black
EEPROM
Black rectangle is
1
J10
Brown
2 L1
J12
J11
moveable head of
DIP switch
White
4
3
5 L2
J14
High speed
Med speed
Low speed0VHigh speed
Fan 2 Fan 1
Black
Blue
Red
Blue
9
8
6
7
Med speed
White
Black
Blue
L3
Low speed
Red
10 N
J16
ECO-Power CVR1008-9
0V
J17
White
Blue (Med)
2
1
Blue
Orange
Black (High)
345
Black
Yellow
Brown
Yellow
Orange
3µF
Capacitor
Fan Motor 2 (2m only)
1~
White (COMMON)
Red (Low)
0
White
Red
Yellow
Orange
Brown
Blue (Med)
Black (High)
4
2
3
1
5
Yellow
Orange
Blue
Black
3µF
Capacitor
To Slave
Air Curtain
T9901013-1-1 CAN-USA-ENG (v9) Page | 25
APPENDIX 2E — WIRING DIAGRAM C1000WR, C1500WR and C2000WR
Page 26
1~
Fan Motor 1
White (COMMON)
Red (Low)
0
White
Red
5x20mm, glass bodied
F1 = F100mA F2 = T6.3A
J1
F2 F1
NC C NO
Th
J2
LED
IN1 IN0
J6
R
0 -10V
F3
F4
Door Contact
J5
F3, F4 = T6.3A, 5x20mm, glass bodied
Brown
1
J10
J9
ON
1234
EEPROM
2 L1
J12
J11
4
3
5 L2
J14
High speed
Med speed
Low speed0VHigh speed
Fan 2 Fan 1
Black
Blue
Red
6
7
Med speed
White
Black
Blue
Red
8 L3
Low speed
Blue
9
10 N
J16
ECO-Power CVR1008-9
0V
J17
White
Yellow
Orange
2
Black (High)
345
Black
Brown
Yellow
Orange
3µF
Capacitor
Blue (Med)
1
Blue
TERMINAL
208V to 240V
BLOCK
1ph / 60Hz
L1
L1
L2
L2
moveable head of
Black rectangle is
DIP switch
e
l
b
a
C
e
v
a
l S
/
r
e
t
REMOTE
s
CONTROL
a M
To Slave
Air Curtain
White (COMMON)
0
White
Red (Low)
1
Red
Blue (Med)
234
Blue
Fan Motor 2 (2m onl y )
1~
Yellow
Orange
Brown
Black (High)
5
Yellow
Orange
Black
3µF
Capacitor
APPENDIX 2F — WIRING DIAGRAM C1000AR, C1500AR and C2000AR
T9901013-1-1 CAN-USA-ENG (v9) Page | 26
Loading...