15.REMOTE CONTROL OPERATION ................................................................................................ 15
16.COMMISSIONING THE SYSTEM .................................................................................................. 16
17.SIGN OFF ....................................................................................................................................... 16
All electrical wiring and connections MUST be carried out by a competent qualified electrici an in
accordance with the latest edition of national and local wiring regulations and/or local statutory
regulations. “Danger: Disconnect electrical supply before servicing”
A 1 phase or 3 phase local Disconnect, provided by others in accordance with Electrical Code
and Local Electrical Codes, with a contact separation of at least 3mm (1/8in) on all poles,
must be fitted in the electrical supply to the air curtain and located in an accessible position
adjacent to the unit. Units with dual electrical supplies (see * in Table below) must have a
common disconnect to switch off both supplies simultaneously.
The appliance must be connected by cables having an appropriate heat resistant temperature
rating.
All supply cables, circuit breakers and other electrical installation equipment must be correctly
sized for the air curtain model being installed; see Section 3: Specifications.
Models operating on a 480V or 600V, 3 phase electrical supply - see Section 3:
Specifications, Electrical Supply * – also need a separate 208V to 240V electrical supply to
operate fan motors and controls.
A 25mm / 1in size cable gland or conduit connector of IP21 rating should be used for the
Electrical Supply into the air curtain.
See Wiring Diagrams for connecting electrical supply and control cables to the air curtain. The
** NOTE. Electric heater circuit current = 47.9 Amps
Rated
Current per
phase (A)
49.0 **
10.9
0.5
14.5
0.7
21.7
1.0
9.3
0.5
12.8
0.7
18.6
1.0
Heat Output
[Low/High]
(kW)
8.64 / 17.28 37 / 82
4.5 / 9.0 20 / 44
6.0 / 12.0 27 / 60
9.0 / 18.0
4.5 / 9.0
6.0 / 12.0
9.0 / 18.0 37 / 82
Weight
(kg / lbs)
37 / 82
20 / 44
27 / 60
Table 1
T9901013-1-1 CAN-USA-ENG (v9) Page | 3
4. INTRODUCTION
Established in the 1960s, Thermoscreens is a leading air curtain manufacturer that exports to over 60
countries worldwide.
As with all our products, the C Recessed range of air curtains is designed with energy efficiency in
mind.
C models suffixed ER, WR or AR are designed to be surface mounted inside a building and located
horizontally over a doorway.
They must not be installed on the outside of a building or built into a cabinet or recessed in any way.
“Caution: This equipment has been investigated with regard to safety from electrical fire and shock
hazard only. The mechanical features have not been investigated and are subject to approval by the
inspection authority having jurisdiction.”
Please complete the following details for your reference:
Date of Purchase
Place of Purchase
Serial Number
Proof of purchase is required to make a claim under warranty.
The air curtain is designed to be recessed within ceiling voids or bulkheads with in a building and
located horizontally over a doorway. It must not be installed outside of the building.
7.1 Location
Mount the air curtain above and as close to the doorway as
possible, with:
recessed grille nearest the doorway and the air inlet
section (see 2, Fig 1) furthest from the doorway
Beware of doorway top edges, structural beams, door
opening/closure devices, etc., which may interfere with the
air stream and affect the location of the unit.
NOTE: For the air curtain to work well the doorway should be less than the width of the airstream.
7.2 Ceiling Suspension
Step 1 Cut an aperture in the ceiling to the dimensions in
Appendix 1. Cut notches, if necessary, to clear
screws in the air curtain casing.
NOTE: For LPHW models, pipework will need to be installed
NOTE: Do not let these four hanging rods come below the
above the curtain. Allow sufficient access and height
clearance within the ceiling void to do this.
through the 2 holes at each end in the top casing (see
Fig 2). Feed the rods through the casing and attach to
fixing brackets near the bottom of the unit (see Fig 3,
looking up into the air curtain). Use M8 or 5/16 UNC
lock-nuts either side of the fixing brackets to secure
the hanging rods.
bottom of the unit casing or they may prevent the
recessed grille fitting properly.
Fig 1
Fig 2
Fig 3
2
1
T9901013-1-1 CAN-USA-ENG (v9) Page | 6
5
M8
or
UNC hanging rods
16
RECESSED AIR CURTAIN
CEILING LEVELCEILING LEVEL
25 - 50 mm
1 - 2 inch
Bottom surface of recessed
air curtain casing
25 - 50 mm
1 - 2 inch
Fig 4
Step 3 Secure each rod to a suitable structure that can support the weight of the unit (see Section 3:
Specifications for weights).
Step 4 Adjust the height of the unit on its hanging rods so the bottom surface of the casing goes
between 25-50mm or 1 to 2 inches up into the ceiling as shown in Fig 4. Ensure the unit is level.
WARNING: It is the sole responsibility of the installer to ensure that the fixing locations and
suspension system used are suitable for the air curtain being installed.
7.3 Attaching the recessed grille to the air curtain
There are 4 fixing slotted brackets on the C1000R, C1500R and
6 brackets on the C2000R (see Fig 5).
Fix the grille as follows:
Step 1 Open the hinged inlet grille using a flat bladed
screwdriver to release the quarter turn fasteners (see
Fig 6). There are two fasteners on the C1000R unit and
three fasteners on C1500R and C2000R units. Before
lifting the grille frame into position, remove four (six on
C2000R) M6 bolts fitted on the inside edge of air
curtain.
Fig 5
Fig 6
Centre
brackets for
C2000R
T9901013-1-1 CAN-USA-ENG (v9) Page | 7
Step 2 Make sure the grille will go the correct way around
(discharge nearest to doorway). Offer the recessed
grille up through the cut-out in the ceiling.
Step 3 Using the M6 bolts removed in Step 1, secure grille by
fixing each bolt through the slotted brackets as shown in
Fig 8.
With the hinged grille open, adjust the height of the
grille frame via slots in each bracket, so frame is snug fit
against the ceiling with no gaps all the way around.
Step 4 To stop discharge air re-circulating within the air curtain
a sliding separator will need adjusting up or down (see
Fig 9). To adjust plate release M6 bolts either end,
extend the slide plate so that it will touch the topside of
the grille along its whole length and tighten the bolts. It
will be necessary to close the hinged grille core to
gauge where the separator plate should be fitted.
Step 5 Once the above steps are complete the hinged grille
core can be closed and all the quarter turn fasteners
tightened up.
Fig 7
Fig 8
Fig 9
Fig 10
NOTE: Open the hinged grille core to gain access to electrical connections, and for servicing an d
maintenance.
T9901013-1-1 CAN-USA-ENG (v9) Page | 8
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.