Thermoscreens C1500ENT, C2000ENT, C1000ENT Installation Instructions

Page 1
C RANGE AIR CURTAINS
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING INSTALLATION
Thermoscreens Ltd
St. Mary’s Road Nuneaton
Warwickshire England
CV11 5AU
Email: sales@thermoscreens.com
Tel: +44 (0) 24 7638 4646 Fax: +44 (0) 24 7638 8578
www.thermoscreens.com
4001160-6 UK Page 1 of 16
Page 2
UN-PACKING YOUR C AIR-CURTAIN
The following items are supplied and packaged within the boxes.
C Air Curtain
Please note end caps are supplied loose and can be fitted during installation
Motorised Valve
(Ecopower LPHW units only)
Note Optional filters are available on Water and Ambient models only
and are packed separately.
If anything is missing or damaged please contact your place of purchase immediately.
For your records
Date of Purchase…………………………….. Place of Purchase……………………………. Serial Number…………………………………
For warranty purposes proof of purchase is necessary so please keep a copy of your invoice.
(All documentation supplied with each unit should be stored and kept for future reference).
4001160-6 UK Page 2 of 16
Remote Control
Ecopower Electric & LPHW
Manual Ambient
Wall Brackets & Fixing Bolts
(additional bracket and bolts supplied for C1500/C2000 models)
Page 3
INSTALLATION OF YOUR HORIZONTAL APPLICATION C AIR-CURTAIN
The C air curtain has been designed for surface mounting only inside of the building.
Location
Ensure that the unit is mounted within its height specification of 1.8m minimum to 3.0m maximum (from floor level to the underside of the unit) and that it is situated as close to the door as possible with a 100mm air gap above the air curtain (see adjacent figure). In some cases it may not be possible to mount the air curtain as close to the door as possible as the air stream may strike the top edge of the doorway, a structural beam or a door opening device etc, therefore this will have to be taken into account when locating the unit.
Wall Fixing
Bolt the wall brackets to the rear face of the unit as shown in the adjacent figure (using the bolts supplied). Before fitting the unit to the wall obtain suitable fixing bolts, taking into account wall type and unit weight (see table 1).
Step 1. Refer to Figure 1 for mounting details
and drill the wall accordingly.
Step 2. Screw in the top bolts leaving a small
gap between the head and the wall; lower the unit onto the bolts via key hole slots in the top of the wall brackets and then screw in the bottom bolts.
Step 3. Ensure all fixing bolts are tightened to
stop the unit being lifted off the wall.
Ceiling Suspension
6mm threaded inserts are provided in the top face of the casing (4 x M6 on the 1m and 6 x M6 on the 1.5/2m models, for dimensions see Figure
1) allowing the unit to be suspended on threaded rod (threaded rod is not provided). Ensure each of the threaded rods are secured on to a suitable structure that can support the weight of the unit (for unit weights see Table 1)*. When fitting the threaded rod ensure that it does not interfere with internal components. Fit locking nuts (not supplied) and ensure they are engaged by a minimum of 20mm to stop the threaded rod rotating and coming away from the casing.
*Please note it is the sole responsibility of the installer to ensure that the fixing points and bolts used are suitable for the air curtain being installed.
4001160-6 UK Page 3 of 16
Page 4
75
33
F
C
E
connection interface
Remote control
suitable for 25mm gland
Electrical supply inlets
B
D
A
E
M6 inserts
21
220
C
LPHW connections
Rp 1/2 (1/2in. BSP female)
120
(min)
198
100
2200
C2000
1669
C1500
1928
1408
964704
1748
1208
874
604
161
170
275
1137
908
C1000
Figure 1
4001160-6 UK Page 4 of 16
B(mm)
A(mm)
C(mm) N/A
N/A
710
E(mm)
D(mm)
161
F(mm)
Page 5
Safety and Electrical Connections
All electrical wiring and connections MUST be carried out by a competent qualified electrician in accordance with the latest edition of the IEE wiring regulations and/or local statutory regulations.
A single phase or 3 phase local isolator with a contact separation of at least 3mm in all
poles must be fitted to the supply wiring (the isolator must be fitted in an accessible position).
The air curtain must be earthed.
The appliance must be connected by means of wires having an appropriate
temperature rating (heat resistant) (electric models only).
Ensure that the supply cables, circuit breakers and other electrical installation
equipment are correctly sized for the air curtain being installed; see Table 1 for Power Ratings. See also data badge on the left hand side of unit under end cap.
On a 3 phase electrical supply the unit requires a neutral connection (3N~).
Cable glands used for the Electrical Input must be rated IP21 or higher.
Table 1
Air Curtain Electrical
Supply
Rated Power
Input (kW)
Current per
phase (A)
Heat Output
(kW)
(V/ph/Hz)
C1000A 230/1/50 0.15 0.7 N/A 15 C1500A 230/1/50 0.20 0.9 N/A 21
C2000A 230/1/50 0.25 1.1 N/A 31 C1000W 230/1/50 0.15 0.7 6.0 18 C1500W 230/1/50 0.20 0.9 9.0 26 C2000W 230/1/50 0.25 1.1 12.0 37
C1000E 400/3/50 9.15 13.7 4.5/9.0 16
C1500E 400/3/50 12.20 18.3 6.0/12.0 23
C2000E 400/3/50 18.25 27.2 9.0/18.0 33
To gain access to the electrical
connections the air intake grilles must be removed. Ensure electrical mains supply to the unit is isolated. If end caps are already fitted, remove them from the air curtain first (see insert).
Two air inlet grilles are fitted on 1m,
three on 1.5m and four on 2.0m models.
Remove intake grilles by unfastening
two screws on each grille; M4 x 10mm Pozi No.2 screws accessed via larger hole in the bottom of the grille (see
Optional filter fits inside curve of inlet grille
adjacent figure).
Weight
(kg)
4001160-6 UK Page 5 of 16
Page 6
Access can now be gained to make the
electrical connections.
Once connections have been
completed the inlet grilles should be refitted and if fitted the end caps clipped into place (see insert).
Please note the panels of the air curtain are coated in a protective film which should be
removed before use.
LPHW Models
For LPHW models ensure suitable water mains isolation valves are fitted in the flow and return pipework. When fitting the 3-port valve ensure that the pipe connections are fitted as detailed below and are in accordance with the manufacturers leaflet supplied with the valve.
22mm pipe
22mm pipe
A
B
A/B
15mm pipe
22mm pipe
Air Curtain Water Flow Rate (l/s)
Coil Water Pressure Drop (kPa)
82/72°C
C1000W 0.14 2.77 C1500W 0.21 6.74 C2000W 0.29 13.40
Ambient Models
Ambient units are supplied with a remote switch unit. The switch unit allows the air curtain to be powered ON/OFF and select one of three fan speeds.
R E T U R N
F L O W
4001160-6 UK Page 6 of 16
Page 7
Fitting/Connecting the Remote Control
The Ecopower Plus controller uses extra low voltage to communicate via the RJ control cable supplied. The controller should be located in a suitable place for easy access, it
can be fixed to the wall via various fixing slots provided in the back case or onto an electrical switch box (not provided). To mount controller onto an existing switch box, feed one end of the control cable through the switch box (see insert).
Using a screwdriver undo screw mounted on the top of the controller case. Pull the front case slightly forwards and lift the back case away.
Feed and secure the RJ control cable through one of the openings in the back case and secure back case to switch box using 2 x M3.5 mounting screws (not provided).
With the cable RJ plug locking clip lying nearest to controller PCB, connect the RJ plug to the RJ socket on the board.
Note: For controller DIP switch options refer to
Ecopower Plus Remote Control Operation and DIP Switch Settings.
Refit the controller front case to the back case. The air curtain end of the control cable should be connected to one RJ socket fitted either on the top panel for NT or the Ecopower motherboard inside a recessed air curtain. Ensure the control cable is safely secured.
Multiple Installation (Ecopower only)
To Master/Slave two or more air curtains together a suitable RJ lead should be connected from the Master to the Slave unit. Thermoscreens 3.0m RJ extension leads must be ordered separately. Additional air curtains, up to a maximum of eight units, may be connected as indicated below. For Master/Slave configuration an independent mains supply must be supplied to each air curtain.
4001160-6 UK Page 7 of 16
Page 8
Ecopower Controller Motherboard
Function
Control
Comments
Standard
Fan Heat Interlock –
The heat output is governed by the fan speed. If low or medium fan speed is selected the heat output will operate on only first heat stage. Second stage heating will only
operate on high fan speed.
DIP1 Option
ON
OFF
1 2 3 4
Suitable on vertical electrically heated Designer air curtain. Maximum heat output achieved if maximum fan speed selected. Independently set-up DIP switch on each mother board. This feature operates in manual or
As supplied, the default setting would be for heat and fan settings to be independent (DIP1 OFF).
auto mode.
Disable Fan Run-on –
Disable fan run-on.
Thermostat Master –
Only the air sensor thermistor in the master air curtain will be used for measuring the reference air temperature for the whole master/slave installation.
DIP2 Option (LPHW & Ambient only)
ON
OFF
1 2 3 4
DIP3 Option
ON
OFF
1 2 3 4
Must only be used for LPHW and Ambient air curtains. Independently set-up DIP switch on each mother board.
The air sensor thermistors in all the slave air curtains will be ignored. This will then avoid situations on larger doorways with master/slave air curtains where some units can blow cold air whilst others can blow warm air, because they currently all refer to
As supplied, the default setting would enable fan run-on (DIP2 OFF).
As supplied, the default setting would be for the air sensor thermistor on all units to be measuring (DIP3 OFF).
their own air sensor for control of the heat output of each air curtain. The master air curtain need not be the one that the wall control is plugged into. This dip switch setting must also be used for Global Switching (Master/Slave) via the INHIBIT terminal – see next page.
Overheat Fan Disable –
If DIP4 is on and thermal cut-out(s) operate both heat and fan circuits are isolated and LED’s on wall switch flash. If DIP4 is off and thermal cut-out(s) operate, only the
DIP4 Option (Electric only)
ON
OFF
1 2 3 4
Independently set-up DIP switch on each mother board.
To remove fault, isolate electrical supply to air curtain, reset TOC and reconnect supply.
As supplied, the default setting would enable fan if TOC trips (DIP4 OFF).
heating circuit is isolated and the LED’s on the wall switch flash.
Fan run-on time set two minutes.
Built-in
If “FAN ONLY” has been selected, at switch off, no fan run­on.
- white rectangle indicates the moveable head of each 4 way DIP switch
DIP switches fitted on the Ecopower board provide a selection of optional features as described above. Isolate and switch electrical power off before configuring and/or changing any DIP switch settings.
4001160-6 UK Page 8 of 16
Page 9
Easy plug-in arrangement for remote air sensor thermistor on a 1m lead. Plugging-in
the remote air sensor to J3 disables the standard air sensor thermistor already fitted
on the Ecopower board. As supplied, the board will not have the remote air sensor fitted.
An INHIBIT two screw terminal fitted on the Ecopower board for BMS remote On/Off
feature. If the terminal is linked, i.e. by 2 wires to a remote volt free contact, the unit will run. If it is open circuit across the terminal the unit will switch off. This remote On/Off feature has global switching logic, i.e. if you master/slave several units together you need connect the remote contact to only one of them to turn all units on and off in the master/slave system. For global switching to work on the slave units, need to set DIP3 Option (see previous page) on the unit that the remote contact is wired to and have previously turned the unit on with the wall switch. As supplied, a wire link will be fitted to the terminal block on every unit. For summer settings place a 3.3k resistance
across the INHIBIT terminal, with these settings fans only will run even if controller is
requesting for heat.
Customer Building Management System
ECOPOWER BOARD
A HEALTHY two screw terminal is included on the board for a fault signal indication if
the electric elements overheat cut-out has operated. A healthy system provides a 24V DC signal at the terminals compared to an overheat fault which provides OV DC.
4001160-6 UK Page 9 of 16
Page 10
4001160-6 UK Page 10 of 16
Page 11
4001160-6 UK Page 11 of 16
Page 12
4001160-6 UK Page 12 of 16
Page 13
Ecopower Plus Remote Control Operation and DIP Switch Settings
7
Heating Level Scale
6 4
3
5
1
2
On/Off (I/O)
Press On/Off switch (1) to turn the air curtain On and operate as follows:-
Press Auto switch (2) to cycle between Manual and Automatic modes. The Auto on indicator LED is lit for "Auto Mode" and un-lit for "Manual Mode".
Manual:
Heat output can be selected as Zero, Half Heat or Full Heat. Heating levels are selected by stepping up or down with switches (3) and (4). Heating level indicator LED's go 0%, 50% or 100% to show the level selected.
Automatic:
If DIP switches 1, 2 and 4 on the Ecopower motherboard are set to OFF, the air curtain measures the incoming air temperature and automatically selects the necessary amount of heat to keep it at the level selected.
Fan Speed
Switches (5), (6) and (7) select fan speed low, medium or high respectively. The appropriate LED above each fan speed indicator is illuminated to show which fan speed is selected.
Pressing the On/Off switch (1) again switches the air curtain off with all the LED’s switched off. If a heated air curtain is heating when switched off the fan will run-on at low fan speed for an extended time (approx. 2 minutes) to dissipate excess heat.
Do not switch the air curtain On/Off from the isolator. If the mains supply is isolated or cuts-out during operation the safety thermal cut-out(s) for electric heated air curtains within the air curtain may operate. If this happens the thermal cut-out(s) will need to be reset by a competent technician.
DIP Switch Settings
At the back of the Ecopower Plus remote control PCB there are four DIP switches (see above) that provide the following optional features.
DIP1 Restart on Power-Up – If electrical
supply to the air curtain is interrupted, upon restoring electrical supply, the customer’s settings on the remote control will be retained. The default is with this feature ON.
DIP2 Stop Fan on Cold – Fans switch off
when heating level is achieved (Automatic mode only). The default setting is with this feature OFF.
DIP3 Never Blow Cold – Unit always
heats in Automatic mode (i.e. will not go to ambient mode). The default setting is with this feature OFF.
DIP4 Air Sensor in Controller – The air
sensor in the remote controller is enabled (DIP4 ON) and the air sensor on the Ecopower motherboard in the air curtain is disabled. Temperature control for Automatic Mode is then done at the remote control, which may be an advantage to limit overheating of the door entrance area. The default
setting is with this feature OFF.
4001160-6 UK Page 13 of 16
Page 14
Commissioning
Set the discharge grille vanes so they point straight downwards over the doorway. Once the air curtain is functioning check that the fans operate at Low, Medium and High speeds, that there is no excessive mechanical noise coming from the fans and that all fans are working. If the unit is electric or water heated check that the air stream from the discharge grille warms up across the whole length of the air curtain when heating is selected. Check that heating increases as higher heat is selected and feel to see that the warm air stream is reaching across the doorway with door open or closed. If necessary the vanes of the discharge grille can be angled either inwards or outwards if this gives better penetration/warming of any incoming draughts. If an Ecopower controller is being used check its operation in Manual Mode. Then select Auto Mode and increase the heating set point until the air stream warms up. Reduce the heating set point until the air stream goes cold. Explain to the end user that the doorway should be closed whenever possible but that during times of high pedestrian use it will become effectively ‘open doorway’. The air curtain serves an essential purpose by saving energy and providing comfort to the occupants when compared to an open doorway with no air curtain fitted. Before leaving site it is important that the air curtain installation is “Handed-Over” to the end user or his representative and the operation of it is fully explained and that they understand how it operates. Explain also the service intervals and that the unit must be regularly cleaned and if it has filters fitted that these require regular cleaning or replacement.
Fault Conditions
In the event of a fault the thermal cut out(s) (Note: If the mains supply is isolated during operation then the thermal cut outs may operate) or internal fuses may operate. The
thermal cut out(s) are located on the top face of the unit directly above the element banks (one on the 1 & 1.5m and two on the 2m model). For Ecopower units two internal electrical fuses are located on the Ecopower board; 6.3A (T) supplies the fan motors within the air curtain and 125mA (F) controls the operation of the Ecopower board. For Ambient and Standard LPHW units the fuse is located within the control panel at the left hand end of the air curtain.
If for an electric heated air curtain an overheat fault occurs, or if J2 link is missing for LPHW models, the LED’s on the remote control will flash and the Ecopower board status LED on the board will be permanently red to indicate a fault.
In the case of a fault condition (refer to flowchart) do not attempt to reset the thermal cut outs or replace the fuses, arrange for a Thermoscreens appointed technician or certified electrician to attend the unit to investigate the reason why the thermal cut outs/fuse(s) have operated. Once the cause has been determined and rectified, they will reset/replace the thermal cut out/fuse and function test the unit.
PCB Status
Fitted on the PCB board inside of the air curtain is an LED shown as LED1 on wiring diagrams that will indicate the Ecopower control status.
1. LED flashing green – operation normal.
2. LED flashing red – low supply voltage or controller not plugged into Ecopower motherboard.
3. LED permanently red – thermal cut outs open circuit (electrically heated models) or J2 link missing (LPHW models). Remote Control LED’s will also flash to indicate the thermal cut-out(s) has operated or J2 link is missing.
Note to reset the thermal cut outs please refer to Fault Conditions section detailed above.
4001160-6 UK Page 14 of 16
Page 15
User Fault Finding Flowchart (for Ecopower Control)
Service Agent to
reset thermal cut-
out(s)
Service Agent to
investigate why
thermal cut-out(s)
have operated
Is Electrical
Power
switched on
Yes
Are the fans
operating
correctly
Yes
Select heat output
No
No
Do the LED’s
light up on the remote
control
Yes
Switch on Electrical
Power
Connect remote control and push On/Off switch
to turn unit on
No
No
Is the remote
control plugged in and turned
on
Yes
Yes
Check if thermal
cut-out(s) have
tripped (Electric
Heated only)
No
Contact Installer
No
Contact Installer
Is the unit
discharging
warm air
Yes
Unit is working
satisfactorily
4001160-6 UK Page 15 of 16
Page 16
Service & Maintenance Always disconnect and isolate the mains electricity supply before installing,
maintaining or repairing this equipment. Note: All maintenance/repairs should only be carried out by a competent electrician or Thermoscreens appointed technician.
Once the mains supply is isolated, remove end caps from the air curtain (if fitted). Remove each air intake grille by unfastening two screws on each grille - M4 x 10mm Pozi No.2 screws accessed via the larger hole at the bottom of each grille.
To ensure the air curtain operates at full efficiency the inlet/outlet grilles, fan impellers, housings and motors must be kept free of dust and debris. Build up of dust on the fan impellers can cause vibration, noise and excessive wear on the motor bearings.
Frequency of cleaning will depend on the environment, but we would recommend that the unit be cleaned a minimum of every 3 months (failure to adequately maintain the unit and provide a suitable cleaning schedule will result in performance degradation and reduce the life expectancy of the air-curtain).
Vacuum and clean the build-up of dirt and debris within the air-curtain (please note
that the motor(s) are permanently lubricated and require no additional lubrication). If filters are fitted, ensure these are regularly inspected and cleaned or replaced. All dirty or blocked filters should be immediately replaced.
Once the air curtain has been cleaned check all electrical connections within the unit ensuring terminals are tight and that crimped connections have not become loose. Refit inlet grilles and end caps. Reconnect the electrical supply and fully function test the air-curtain to ensure correct operation (See Commissioning).
If the outer casing requires cleaning this should be done using a warm soft cloth. Do not use solvents or abrasive materials.
Warranty
If any problems are encountered, please contact your installer/supplier. Failing this please contact the Thermoscreens warranty department. All units are covered by a two year warranty period.
Care has been taken in compiling these instructions to ensure they are correct, although Thermoscreens disclaims all liability for damage resulting from any inaccuracies and/or deficiencies in this documentation. Thermoscreens retain the right to change the specifications stated in these instructions.
Thermoscreens Ltd St. Mary’s Road Nuneaton Warwickshire England CV11 5AU
Email: sales@thermoscreens.com Tel: + 44 (0) 24 7638 4646 Fax: + 44 (0) 24 7638 8578
www.thermoscreens.com
4001160-6 UK Page 16 of 16
Loading...