Thermo Scientific Revco BOD-10, BOD-30 Installation and Operation

Page 1

1 Introduction

Installat ion and Operation
BOD10 and BOD30
WARM ALARM SET POINT
BOD10

1.1 Specificatio ns

Capacity BOD Bottle Capacity Temperature
Range
Solid-State Electronic Insulation Interior Shelves Voltage Dimensions
Shipping Weight
Control Uniformity
Exterior Interior
BOD30
6.1 cu. ft. 20.0 cu. ft.
92 Standard BOD Bottles 400+ Standard BOD Bottles
0 to +50°C -20 to +60°C
Micro (Single Set Point) Micro (Single Set Point)
+/-0.5°C Typical +/-0.5°C Typical
Yes - High and Low Yes - High and Low
CFC-Free Foamed-in-place CFC-Free Foamed-in-place
ABS Thermoplastic ABS Thermoplastic
1 Fixed/1 Adjustable 4 Fixed Shelves/1 Basket
115/1/60 115/1/60
23 7/8 in. W x 25.5 in. D x 35.75 in. H 33 in. W x 29 in. D x 69.8 in. H
21 in. W x 20 in. D x 24 in. H 28 in. W x 22 in. D x 56 in. H
115 lbs (52 kg.) 300 lbs. (136 kg.)
1
Page 2
Installat ion and Operation
BOD10 and BOD30

2 Safety Considerations

WARNING!
components. Replacement parts must be O.E.M. exact replacement equipment. Modification or use of the equipment in a manner other than expressly intended may cause deat h or serious injury. This includes use of user-supplied components and materials not specifically designed for the unit. Reconfiguring the controller may cause death or serious injury.
The manufacturer shall not be l iable for any damages, including incidental and/or consequential damages, regardless of the legal t heory asserted, including negligence and/or strict liability.
Before using, user sh all determine the suitability and inte grity of the product for t he intended use and that the un it has not been altered in any way. User assume s all risk and liability what soever therewith .
WARNING!
operation, this unit must be properly grounded before it is used. Failure to ground the equipment may cause personal injury or damage to the equipment. Always conf orm to the National Electric al Code and local codes. Do not connect unit to alr eady overloaded power lines.
WARNING!
before attempting any maintenance to equipment or controls.
Do not modify or change system
For personal safety and trouble-free
Disconnect unit from main power

3 Pre-Installation

3.1 Unpacking

At delivery, examine the exter ior for physical dam age while the carrie r’s represen tat i ve is pr es ent. If e xteri or da mage i s pre sent , careful ly unpack and inspect the unit and all accessories for damage.
If there is no exterior da m age, unpack and inspect the equipment within five days of delivery. If you find any damage, keep the packing materials and immediately report the damage to the carrier. Do not return goods to the manufacturer without written au th orization. When sub m it ting a clai m for shippi ng dam age, request that the carrier inspect the shippi ng container and equipment.

4 Installation

Do not exceed the electrical a nd temperature ratings printed on the data plate locat ed inside the un it.
CAUTION!
could result in dangerous conditions. To preclude hazard and minimize risk, follow all instructions and operate within the design limits noted on the dataplate.

4.1 Location

Install th e un it in a l e v el area fr ee from vibr at ion wit h a m inim um of three inches of space on the sides and rear and 12 inches at the top.
Do not position the equipm ent in direct sunligh t or near heating diffusers, radiators, or other sources of heat. The ambient temperature range at the location m ust be 59 to 90°F (15 to 32°C).

4.2 Wiring

CAUTION!
power source. Incorrect voltage can result in severe damage to the equipmen t.
DANGER!
operation, this unit must be properly grounded before it is used. Failure to ground the equipment may cause personal injury or damage to the equipment. Always conform to the National Electrical Cod e and local codes. Do not connect the unit to overloaded power lines.
Always connect the refrigerated incubator to a dedicated (separ ate) circuit. Electrical codes require fu se or circuit breaker protecti on f or branch c ir cuit cond uct ors. Use t ime delay f use s f or #12 AWG circuits.

4.3 Leveling

The unit must be leveled right to left and front to back. On the BOD30, rotate the leveling feet, located under the front corners of the uni t, until the unit is level. The BOD10 does not have leveling feet; shims should be used where necessary.
Improper operation of the equ ipment
Connect the equipment to the correct
For personal safety and trouble-free

3.2 Included Parts

The shelves are packaged and secured inside the cabinet. The contro l key, door key, and this manual are als o shipped inside the incubator.
2
Page 3
Installat ion and Operation
BOD10 and BOD30

4.4 Shelves

For s afety during shippi ng, the shelves are packaged and secured inside the cabinet.

Figure 1. Shelving Detail

4.4.1 6.1 cu. ft. Models

The compact 6. 1 cu. f t. m ode ls ha v e t wo s helv es , o ne is f i xed a nd the othe r is adjust able. Place the adjustable shelf on the shelf bracke ts insid e th e inc uba tor and push the shel f down and toward the back of the incubator.

4.5 Door Seal

To check the door seal , complete th e following steps:

1. Open the door.

2. Insert a strip of paper (8.5 x 11 in.) between the door gasket and the cabinet flange and close the door.

3. Slowly pul l the paper strip from the outside. You should feel some re sistanc e.

4. Repeat this test a 4 in ch intervals around the door. If the door does not sea l properly, the gasket must be replace d.
CAUTION!
fitting gasket allows moist air to be drawn into the cabinet, resulting in quicker fros t buildup on th e evaporator coil, longer running time, poor temperature maintenance, and increased operation cost. The full Hermeti c mo to r- com pres so r s in th es e un its ha v e so li d hold-down nuts.
nuts.
Door seal integrity is critical. A loose
Do not loosen the visible mounting

4.6 Remote Alarm Terminals

The BOD30 incubator has connections for freestanding alarms. These ter minals are located at the back of the incubator. The terminals are: Common, Normally Closed, and Normally Open.

4.4.2 20.0 cu. ft. Mo dels

The 20.0 cu. ft. models have 4 shelv es. The two shallow er shelves fit in the bottom section of the incubator, the two wider shelv es in the top section of the incubator. Place a shelf on t he shelf brackets inside the inc ubator and push the shelf down and toward the back of the incubator.
3
Page 4

5 Operation

5.1 Control Panel Features

Installat ion and Operation
BOD10 and BOD30
OFF
POWER ON ALARM ON
1543

Figure 2. Control Panel (6.1 cu. ft. model)

OFF
POWER ON ALARM ON
13245
LIGHTS
10
CALIBRATE
TEMPERATURE
FAILURE
AUDIO SILENCE
10
CALIBRATE
TEMPERATURE
FAILURE
AUDIO SILENCE
67
CABINET
TEMPERA TURE
CONTROL
SET POINT
COLD ALARM
SET POINT
WARM ALARM
SET POINT
89
CABINET
TEMPERA TURE
CONTROL
SET POINT
COLD ALARM
SET POINT
WARM ALARM
SET POINT
9
8111213
SCAN
67
SCAN
14
°
C
131211
14
°
C

Figure 3. Control Panel (20.0 cu. ft. model)

Before the initial start up, take some time to become familiar with the controls on your refrigerated incubator. Figure 2 and Figure 3 illustrate the control panel .
1. Three position keyed Power On Switch.
2. Interior light switch (20.0 cu ft mode ls only).
3. Calibrate . Press this pad to calibrate the cabinet temperature (refer to Section 5.4.1 on page6).
4. T emperature failure. This indicator lights when the incubator temperat ure deviates abov e or below the alarm temperature setti ngs.
5. Audio Silence. Press this pad to silence the alarm.
6. Cabinet T empera ture In dicator. This indicator lights when the temperat ure display window is showing the actual cabinet temperat ure (refer to Section 5.4.1 on page 6).
7. Control Set Point. This indicator lights when the temperature display wi ndow is showing th e cabinet temperature set point (refer to Section 5.3.1 on page5).
8. Cold Alarm Set Point. This indicator lights when the temperat ure display window is showing the cold alarm se t point (refer to Section5.3.2 on page 5).
9. Warm Alarm Set Point. This indicator lights when the temperature display window is showing the warm alarm setpoint (refer to Section 5.3.3 on page 5).
10. Warning indicator lights.
11. Scan key. Use this pad to select the Control, Cold Alarm, or Warm Alarm Set Po in t fu nction.
12. Decrement Pad ( ). Use this pad to decrease temperature values.
13. Increment Pad ( ). Use this pad to increase temperature values.
14. Digital Temperature Display Window. This window displays chamber temperature, alarm values, etc. depending on the operati ng status of the refrigerated in cubator and the procedure being performed.
15. Circuit b reaker (not sho w n). The circuit breaker is located on the back of the control on a BOD30. The BOD10 does no t have a circuit breaker.
4
Page 5
Installat ion and Operation
BOD10 and BOD30

5.2 Initial Start Up

Tu rn the key switch to the POWER ON position. The Power On LED and the Cabinet Temperature LED illum inate.
The alarm function is not active at this time.
Note:
The display cycles through an initialization mode for a few seconds, then the Temperature Di splay Window shows the curren t cabinet temperature. The indicator light next to Cabinet Temperat ure is green.
Do not turn the key to ALARM ON until all sta rt-up procedures are complete and the incubator is stabilized.

Table 1. Factory Temperature Settings

Cabinet Temperature: Cold Set Point: War m Set Point:
22°C 12°C 32°C

5.3 Set Poin t Operation

CAUTION!
in 20.0 cu ft models, the control automatically initiates a defro st cy cl e every eight hou r s . Th ere wil l b e a sl ig ht elevation in cabinet temperature during this cycle.
CAUTION!
the 20.0 cu ft models or above 30 models , the incubator comp ressor is automatically disabled.
If the Control Set Point is 4
If the Control Set Point is above 40
°
C or below
°
C in the 6.1 cu ft
°
C in

5.3.1 Contr ol Set Point

IMPORTANT NOTE:
When the control set point is changed, the cold ala rm and warm alarm set points automatically re ference the new control set point. For example, control set point = 3°C, cold alarm set point = 2°C, and warm alarm set point = 4°C. If the control set point is changed to 10°C, the cold alarm automatically changes to 9°C and the warm alarm set point change s to 11°C. Since the incubator temperature is less than 9°C, the cold alarm will sound. To prevent activation o f the alarms, manually adjust the cold alarm set point 1° below the current incubator temper ature an d the warm alarm set point 1° above the new control set point. W hen the temperature stabilizes to the new co ntrol set point, adj ust the alarm set points accordingl y (refer to Section 5.3.2 and Section 5.3.3).
To change the control set point temperature, complete the following steps :
1. Press the Scan key until the LED indicat or light nex t to the Control Set Point pad is yellow. The display shows the current set point.
If no keys are pressed within t en se conds, t he tem pera tu r e
Note:
display reverts to the cabinet temperature.
2. Press and hold or to adjust the set point tem perature.
CAUTION!
switch to the ALARM ON position to activate the alarm.
You must turn the thr ee-position key

5.3.2 Cold Alarm Set Point

To change the cold alarm set point, complete the following steps:
1. Press the Scan key until the LED indicator light next to the Cold Alarm Set Point pad is yello w. The display shows the current set point.
If no keys are pressed within t en se conds, t he tem pera ture
Note:
displa y reverts to the cabinet temperature.
2. Press and hold or to adjust the set point tem perature.
To avoid nuisance alar m s due to door opening, etc., we
Note:
re com m end that the set point be no cl oser than 1° to the Control Set Point.
CAUTION!
switch to the ALARM ON position to activate the alarm.
You must turn the thr ee-position key

5.3.3 Warm Alarm Set Poi nt

To change the warm alarm set point, complete the following steps:
1. Press the Scan key until the LED indicator light next to the Warm Alarm Set Point pad is yellow. The display shows the current set point.
If no keys are pressed within t en se conds, t he tem pera ture
Note:
displa y reverts to the cabinet temperature.
2. Press and hold or to adjust the set point tem perature.
To avoid nuisance alar m s due to door opening, etc., we
Note:
re com m end that the set point be no cl oser than 1° to the Control Set Point.
CAUTION!
switch to the ALARM ON position to activate the alarm.
You must turn the thr ee-position key

5.3.4 Alarm Op eration

When the alarm system is activated, warm and cold alarm conditions cause the heating and co oling systems to shut down. This is to protect the contents of the incubator from extreme temperature conditions.
If th e control display indicat es an alarm condition, v erify that the temperature and alarm setpoints are correct for your application. Also check the power supply and door seal. If the setpoints are correc t and there is nothing visibly wrong with your unit, call Technical Service.
5
Page 6
Installat ion and Operation
BOD10 and BOD30

5.4 Calibration

If it is necessary to verify incubator operation, complete the following steps :
1. Place a thermome ter, graduated in 0.1°C increments, in side
the incubator.
CAUTION! Do not
touch the shelves. If the bulb touches any part of the incubator or shelves, the temperature reading will not be accurate. We recommend that the thermometer be
hung
inside the incubator with air ci rculating freely
around the sensing bulb.
allow the thermometer bulb to
2. Allow th e incu bat or to r un undi stur be d for at l east ei ght ho urs so that the temperature can stabilize.

3. After the temperature is stabil ized, read the thermo meter temperat ure.

CAUTION!
quickly, do not remove the thermometer from the incubator. The thermometer temperature starts to change as soon as the incu bator door is ope ned.
Look at the thermometer temperature

5.4.1 Control Temperature Calibration

To calibrate the co n tr ol tempera ture, comp lete the fo ll owi n g steps :
1. Press Calibrat e. The LED indicator next to Control Temperature glows re d. The Temperature Dis pl ay Window shows the current control temperature.
If no keys are pressed within t en se conds, t he tem pera tu r e
Note:
display reverts to the cabinet temperature.
2. Press and hold or to display the desired value.
CAUTION!
changed permanently.
The calibration of the control is now
3. Allow the incubator to stabilize for one to two hours.
4. Make any necessary changes to the set p oints after the incubator stabilizes at the new temperature.

5.5 Operation

After the Control Temperature and set points are set to your specifications and the incubator temperature is stabil ized, turn the control key to ALARM ON.
You can now load product into the incubator.
CAUTION!
product to maintain airflow for temperature uniformity.
Allow sufficient air space aro und the
When the door is opened, the evaporator fan shuts down
Note:
to pr ev ent warmu p of samp les and the int erio r l ight t ur ns on (BOD30 units only).
CAUTION!
power goes off and immediately on again, the built-in compressor overload device functions to take the compressor off-line. This process is normal and the overload device restarts the compressor within a few minute s.
If a short power failure occurs and

6 Maintenance

CAUTION!
by trained personnel.

6.1 Defrost Water Pan (BOD30 only)

When the unit automatically defrosts in freeze mode, defrost water is collected in a pan, located above the motor compressor in the bac k of the unit. Thi s water is evaporated by heat from the motor compressor which leaves a residue in the pan. Clean the defros t w ater pan wit h wa rm w at er a nd s oa p appro xim a tely e v ery 90 days.

6.2 Cabinet Interior

The insid e of the cabinet should be cleaned whenever necessary with one of the followin g solutio n s:
Amphyl so lution, mixed according to the manufacturer’s
direct ions. Roccal II solution, mixed according to the manufacturer’s
directions. Two table spoons of baking soda per quart of warm water .
Stubborn smudges can be cleaned with mild soap and water.
CAUTION! Do not
detergent-containing mixture. Detergent will discolor the interior plastic parts.
Shelv es can be removed for wa shing. Be careful with the sealing gas ket on the door. If the gask et is
damaged, it will not seal properly and will require replacement.
Dry all interior su rfaces before restarting the unit.
Note:

6.3 Cabinet Exterior

Every th ree to six months, sweep arou nd the base, unde rneath, and behind the incubator.
Remove the kickplate located on the lower front on the
Note:
20.0 cu. ft. models before sweeping.
Maint enance should only be per formed
use detergent or any
Do not use solvents
.
6
Page 7

7 Troubleshooting

7.1 Troubleshooting Procedures

Installat ion and Operation
BOD10 and BOD30
WARNING!
T roubleshooting procedures involve working with high voltages which can cause injury or death. T roubleshooting
should only be performed by trained perso nnel.
Symptom Problem Solution
No power
No lights on control panel
Unit does not maintain set point temperature
Overtemperature Alarm sounding
Undertemperature indicator on Set Point
Circuit breaker
Power switch House electrical power Check the branch circuit feeding the incubator. Refer to Section 4.2 on page 2. Stabilization
External heat
Condenser
Alarm set point Interior fan Check that the fan is operating.
Door switch The door switch is stuck (20.0 cu. ft. models only). Condenser
Check the service cord at the electrical outlet for proper fit. The plug should be tight in the socket. If the outlet is defective, replace the outlet.
Check to see if the breaker is tripped. Reset the breaker if necessary . The circuit breaker is located on the back of the control (BOD30 only).
Check the incubator control panel main power switch. Refer to Section 5.2 on page 5.
Unit has not had time to stabilize after the last temperature selection. Refer to Section 5.4.1 on page 6.
Unit is in direct sunlight or located in the discharge from a heating/air conditioning outlet. Refer to Section 4.1 on page 2.
Check that the rear condenser coil is clear of dust accumulation (6.1 cu. ft. model only).
The set point temperature is too close to the cabinet temperature setting. Refer to Section 5.3 on page 5.
Check that the rear condenser coil is clear of dust accumulation (6.1 cu. ft. model only).
The set point temperature is too close to the cabinet temperature setting. Refer to Section 5.3 on page 5.

8 Accessories

Part No. Description
6314 Roccal II, 3.5 liter bottle 6315 Amphyl Spray, disinfecting agent, 12 cans/case 6316 O-Syl, 3.5 liter bottle
7
Page 8
For your future refe renc e and when contacting the factory, please have the following inf ormation readily available:
Model Number:
Serial Number:
Date Purchased:
The above inf ormat ion can be found on the dataplate attached to the equipment. If available, please pr ovide the date purchased, the source of purchase (specific agent/rep or ganization), and purchas e order number.

If You Need Assistance

REVCO SALES DIVISION
Phone: 828/658-2711 Toll Free (U.S.): 800/252- 7100 F A X : 828/645-3368
LABORATORY PAR TS and SERVICE
Phone: 800-438-4851 FAX: 828-658-2576
TECHNICAL SUPPORT
Toll Free (U.S.): 800-438- 4851

275 Aiken Road

Asheville, NC 28804
U.S.A.
Loading...