Thermo Products THJF18, THJF60 User Manual

TABULAR DATA SHEET
MAC-222 ECN 5287-MA 121005
Outdoor Split System Heat Pump 1.5 Thru 5 Tons
MODELS: THJF18* THRU 60
14.5 SEER – R-410A, 1 PHASE
Physical and Electrical Data
MODEL
Unit Supply Voltage 208-230V, 1 60Hz Normal Voltage Range
Minimum Circuit Ampacity 11.9 17.6 17.3 23.7 26.1 28.8 35.3 Max. Overcurrent Device Amps Min. Overcurrent Device Amps
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll 2-Stage Scroll Compressor
Amps Crankcase Heater No No No No No No No Factory External Discharge Muffler Yes Yes Yes Yes Yes Yes Yes Factory External Check Valve NoNoNoNoNoNoNo
HS Kit Required with TXV Fan Motor Amps Rated Load 0.7 0.8 1.3 1.3 1.3 1.3 1.3 Fan Diameter Inches 24 22 24 24 24 24 24
Fan Motor
Coil
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 Vapor Line Set OD (Field Installed) 3/4 3/4 3/4 3/4 7/8 7/8 1-1/8
Unit Charge (Lbs. - Oz.) Charge Per Foot, Oz. 0.62 0.62 0.62 0.62 0.67 0.67 0.75 Operating Weight Lbs. 145 145 176 193 198 248 290
1. Rated in accordance with ANSI/AHRI Standard 110-2002, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. See Hard Start Kit Accessory Installation Manual for Hard Start Kit part number for each model.
5. The Unit Charge is correct for the outdoor unit, matched indoor coil, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
1
2
3
Rated Load 9.0 13.4 12.8 17.9 19.8 28.8 35.3 Locked Rotor 48.0 58.3 64.0 96.7 115.0 115.0 118.0
4
Rated HP 1/10 1/8 1/4 1/4 1/4 1/4 1/4 Nominal RPM 825 1075 850 850 850 850 850 Nominal CFM 2000 2000 3900 3900 3900 3800 3800 Face Area Sq. Ft. 15.72 19.17 23.58 23.58 23.58 23.58 23.58 Rows Deep 1111122 Fin / Inches 22 22 22 22 22 18 18
5
A
S41S3
20 30 30 40 45 50 60 15 20 20 25 30 30 40
No No No No No No No
6 - 15 7 - 14 9 - 14 10 - 9 10 - 14 14 - 2 14 - 2
C
B
THJF24
S41S3
THJF30
S41S3
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
Unit
Model
THJF36
S41S3
187 to 252
Dimensions
1
A 18 24 40 29 29 30 40 34 34
36 40 34 34 42 40 34 34
60 40 34 34
1. Including Fan Guard.
28 34 34
THJF42
S41S3
(Inches)
B C Liquid Vapor
THJF48
S41S3
Refrigerant Connection
Service Valve Size
3/8”
THJF60
S41S3
3/4”
7/8”48 40 34 34
System Charge for Various Matched Systems
3,4
Outdoor Unit
Required Orifice or
1,2
TXV Indoor Unit
THJF18
S41S3
.051/4F1 .059/4G1 .063/4G1 .071/4H1 .075/4J1 4J1 4K1
THJF24
S41S3
THJF30
S41S3
THJF36
S41S3
Additional Charge, oz
THJF42
S41S3
THJF48
S41S3
THJF60
S41S3
FC/MC/PC35 .051/TXV+0 .059/TXV+0 -- -- -- -- -­FC/MC/PC43 .051/TXV+13 .059/TXV+12 .063/TXV+0 .071/TXV+0 -- -- -­FC/MC/PC60 -- -- -- -- .073/TXV 5 -- -­FC/MC/62 -- -- -- -- .075/TXV+0 TXV+0 TXV+0
Footnotes:
1. For applications requiring a TXV use S1-1TVM*** series kit.
2. Approved orifice shipped with outdoor unit.
3. Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit S1-2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be sued in horizontal applications.
Procedures:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting line tubing.
2. Verify the TXV and additional charge required for specific matched indoor unit in the system using the above table.
3. Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data table.
4. For orifice or TXV matches requiring additional charge, the refrigerant needs to be weighed in for specific coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total system charge = base charge as shipped plus charge adder for matched indoor unit and charge adder for line set.