Thermo Pride C Premiere Series User Manual

AIR CONDITIONING
14 SEER
INSTALLATION & SERVICE MANUAL
Thermo Products, LLC.
MAC-200
ECN 5003-MA
DestroyD
North Judson, Indiana
• • IMPORTANT • •
This envelope contains y This device is potentially dangerous if improperly installed. We recommend installation by qualified heating & air conditioning contractors. Please read the enclosed instructions carefully, before & during installation. Please keep these instructions as permanent reference near appliance.
our assembly instructions and guarantee.
CONTENTS
SECTION PAGE
STALLATION INSTRUCTIONS 3
IN
A. DESCRIPTION OF AIR CONDITIONING CONDENSER 3
B. LOC
IN AND HOW TO MEASURE SUPERHEAT
R OUTDOOR AMBIENT CONDITIONS.
U
S
R
ATION OF OUTDOOR CONDENSING UNIT 4
C. TUB
D. TUB
E. INSTALLATION OF TUBING LINES TO SERVICE VALVES 7
F. DUC
G. ELECTRICAL 9
ITIAL START-UP OF OUTDOOR CONDENSING UNIT 13
ECOMMENDATIONS FOR OPERATING AT LOWER 14
SER INFORMATION 14
PECIFICATIONS 15
EPLACEMENT PARTS 15
ING INSTALLATION 5
ING SIZE REFERENCE CHART 6
T SYSTEM 8
2
INSTALLATION INSTRUCTIONS
NOTE: KEEP INSTRUCTIONS READILY AVAILABLE.
A. DESCRIPTION OF AIR CONDITIONING CONDENSER
The outdoor condensing unit is designed and built with a totally enclosed (hermetic) scroll compressor which offers the advantages of simplicity, quiet operation and reduced condenser size. The entire air conditioning system has been built and performance tested against rigid standards. The installation must comply with the National Electrical Code ANSI/NFPA 70-(latest edition), any state or local codes, and these instructions.
3
B. LOCATION OF OUTDOOR CONDENSING UNIT
The primary consideration in selecting the location of the outdoor-condensing unit is how the location affects the length of the refrigerant tubing lines. Bear in mind, that the longer the tubing line, the greater the pressures drop causing a reduction in the cooling capacity of the unit.
Another consideration in the location selection is the sun load placed on the outdoor condensing unit. Locations, which place the unit in direct exposure to the sun during the majority of a day, should be avoided if possible. Inside corners on the southeast or southwest corners are to be avoided as the heat build-up in such corners would place an increased workload on the unit. Shaded locations on the north side of a home or office are generally best if practical.
Mount the unit on a sturdy base at least one inch above the ground. Be sure to use well-tamped gravel fill beneath the blocks or bricks to prevent settling if concrete blocks or bricks are used. Use a minimum 4"x4" "treated" timbers plus gravel fill to prevent settling if timbers are used.
:A premature compressor failure may result and will "VOID THE WARRANTY" if the
outdoor condensing unit is located in an enclosure such as a garage or not in accordance with these instructions.
Please refer to the Peace of Mind Warranty Certificate included with this product for warranty information.
All models feature an “up-flow” airflow design discharged through the top grill. For this reason, the outdoor condensing unit should not be located under an overhang or any other construction, which would direct the discharged air back to the outdoor condensing unit. The unit should be located as illustrated below.
4
C. TUBING INSTALLATION
The compressor oil is constantly pumped through the liquid line, evaporator coil, and back through the suction line in normal operation of an Air Conditioning system. Please follow the guide lines listed below to insure proper lubrication of the compressor by avoiding oil accumulation at undesirable points in the system.
1. No traps in the suction line are necessary if the outdoor condensing unit is level with the indoor evaporator coil or the indoor evaporator coil is 4 feet or less lower than the outdoor condensing unit. Any horizontal runs of suction line should have minimum 1/2" pitch towards the outdoor condensing unit for every 10 feet of line.
2. A trap is necessary in the suction line at the indoor evaporator coil if the indoor evaporator coil is more than 4' below the outdoor condensing unit and 1 trap per every 10’ of vertical rise thereafter.
: A gradual loop in the tubing can be constructed to take up the excess tubing if you find that
too much tubing has been brought onto a job. Such a loop MUST be kept in a horizontal (flat) plane to avoid trapping the oil. Refrigerant lines should be inserted into a suitable conduit or raceway when the lines are to be buried between the building and the outdoor condensing unit. The lines must be provided with sufficient protection and support to prevent damage when installed above the ground.
5
D. TUBING SIZE REFERENCE CHART
0’-50’ TOTAL LINE LENGTH
MODEL SUCTION LINE LIQUID LINE
AC14241E2 &AC14301E2 3/4” 3/8”
AC14361E2, AC14421E2, AC14481E2 &AC14601E2
AC14483E2, AC14603E2
7/8” 1/2”
50’-75’ TOTAL LINE LENGTH
MODEL SUCTION LINE LIQUID LINE
AC14241E2 &AC14301E2 7/8” 3/8”
AC14361E2, AC14421E2, AC14481E2 &AC14601E2
AC14483E2, AC14603E2
1-1/8” 1/2”
75’-100’ TOTAL LINE LENGTH
MODEL SUCTION LINE LIQUID LINE
AC14241E2, AC14301E2 &AC14361E2 1-1/8” 1/2” AC14421E2, AC14481E2 &AC14601E2
AC14483E2, AC14603E2
1-1/8” 5/8”
NOTES: For line lengths over 25’ adjust charge accordingly per foot of variation from chart.
. .65 oz. per foot for 3/8” and 3/4” line set .674 oz. per foot for 3/8” and 7/8” line set .694 oz. per foot for 1/2” and 7/8” line set .72 oz. per foot for 1/2” and 1-1/8” line set .76 oz. per foot for 5/8” and 1-1/8” line set
These charges are to be used in conjunction with a superheat measurement for best performance.
1. Tubing dimensions are outside diameter.
2. Tubing Type ACR, (Type K heavy wall or Type L medium thick wall)
3. Refrigerant line lengths over 100’ are not recommended.
4. These line size recommendations are based on the use of refrigeration grade tubing and do not include considerations for additional pressure drops due to elbows, valves, or reduced joint sizes.
6
Loading...
+ 11 hidden pages