PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION AND BEFORE
PERFORMING ANY SERVICE OR MAINTENANCE. THESE INSTRUCTIONS MUST
BE LEFT WITH THE USER AND SHOULD BE RETAINED FOR FUTURE
REFERENCE BY QUALIFIED SERVICE PERSONNEL.
: Improper installation, adjustment, alteration, service, or maintenance can
cause injury or property damage. Refer to this manual. For assistance or additional
information consult a qualified installer, service agency, or manufacturer listed below.
MAC-183
ECN 4849-MA
THERMO PRODUCTS, LLC.
BOX 217
NORTH JUDSON, IN 46366
PHONE: (574) 896-2133 MADE IN USA
Page 2
TABLE OF CONTENTS
SECTION BEGINNING PAGE
SAFETY SECTION 1
KNOCKDOWN OF AIR HANDLER 2
REASSEMBLY OF AIR HANDLER 3
SETTING UP THE A-COIL FOR AIR CONDITIONING 3
INSTALLATION OF HOT WATER COIL 4
BLOWER AIR ADJUSTMENT 6
DUCT SYSTEM 9
DUCT SIZING CHART 10
INDOOR EVAPORATOR COIL 10
TUBING LINE SETS 10
HOW TO MEASURE LIQUID SUB-COOLING 14
MEASURING TEMPERATURE DROP ACROSS THE “A” COIL 15
ELECTRICAL 15
UA ADAPTER CABINET 16
RECOMMENDED SUSPENSION PROCEDURE FOR AH AIR HANDLER 16
ECM TROUBLE SHOOTING 17
TROUBLE SHOOTING CHARTS 20
SEQUENCE OF OPERATION 21
REPLACEMENT PARTS LIST 23
Page 3
All installations and services must be performed by qualified personnel.
SAFETY SECTION
This page contains various warnings and cautions found throughout this Service and Installation Manual.
Please read and comply with the statements on the cover and the statements below.
: Improper installation, adjustment, alteration, service, or maintenance can cause injury
or property damage. Refer to this manual. For assistance or additional information consult a
qualified installer, service agency, or manufacturer listed below.
: If drilling or screwing into panel or plate is necessary, make certain drill or screw does not
penetrate into any part of evaporator coil or hot water coil and cause damage. Personal injury and/or
property damage may result.
: Do not use this system if any part has been under water. Immediately call a qualified
service agency to inspect the system and to replace any part of the electrical or control system which has
been under water.
: The cooling and heating coils must be cleaned by a qualified service person.
: This air handler is not to be used to condition during construction.
: When testing electrical equipment, always follow standard electrical procedures and
precautions.
: DO NOT wet electronic components during hydronic testing. Wetting electronic
components may damage circuitry and cause a hazardous situation. Dry moisture from all leads and
terminals if wetting occurs. Wait at least 24 hours for the circuit to fully dry before energizing the
system.
: Personal injury or property damage could result from major repair or service of this
system by anyone other than a qualified contractor.
: If you do not follow these instructions exactly an unsafe condition may result causing
personal injury, loss of life or property damage.
Installation and service personnel are required by some states to be licensed. Persons not qualified shall
not install this equipment nor interpret these instructions.
All local codes and regulations take precedence over the instructions in this manual and should be
followed accordingly. In the absence of local codes, installation must conform with these instructions,
regulations of the National Fire Protection Association and provisions of the National Electric Code.
1
Page 4
All installations and services must be performed by qualified personnel.
AIR HANDLER
Each air handler is shipped with an evaporator preinstalled. The AH2435E1 is shipped with a
12U2430AG15 evaporator coil for 2 to 3 ton operation. The AH4260E1is shipped with a 12U3648AG17
evaporator coil for 3 to 5 ton operation.
The construction of the air handler permits easy knockdown and reassembly. See Figure A.
FOLLOW THESE STEPS FOR KNOCKDOWN OF AIR HANDLER:
1. Start with unit setting in a vertical position(Figure A).
2. Remove middle door.
3. Remove screws from bottom door, top door, and top front panel. Remove doors and top panel of air
handler.
4. Remove the retention clip from in front of the A-coil drain pan and the horizontal drain pan shipping
screw(s) from the right side casing.
5. Remove the A-coil assembly.
6. Disconnect power leads and unplug circulation pump connector from the blower control board.
Figure A.
2
Page 5
All installations and services must be performed by qualified personnel.
7. Remove the screws that secure the blower assembly to the blower pan and pull blower sub-assembly
out the front of the unit.
8. Remove screws that secure the blower pan to the side & back casings.
9. Push the front edges of the side casings slightly apart and remove the blower pan.
10. Remove screws from the bottom and the casing back.
11. Remove casing back and side casings from the bottom.
REASSEMBLY OF AIR HANDLER
To reassemble the air handler, reverse steps above starting with number 10.
SETTING UP THE A-COIL FOR AIR CONDITIONING
The AH2436E1 & AH4260E1 come with the A-coil pre-installed for vertical and left to right horizontal
airflow.
IMPORTANT: When air handler is installed in attic above a finished ceiling, it is recommended that
a safety overflow pan with its own separate drain be installed under the entire unit.
For a right to left horizontal air flow the following steps 1-8 must be followed.
Otherwise skip to step 9.
Reversing the horizontal orientation
1. Remove the middle door of the air handler.
2. Remove the bottom door of the air handler.
3. Remove the retention clip from in front of the A-coil drain pan.
4. Remove the horizontal drain pan shipping screw(s) from the right side casing.
5. Remove the A-coil assembly and slip the horizontal drain pan assembly off of the right side of the Acoil.
5a. Remove the bottom right side support L-bracket and remount in the left hand position using the prepunched holes for a guide.
6. Slip the horizontal drain pan assembly onto the left side of the A-coil.
7. Replace the A-coil assembly into the air handler. The A-coil drain pan should slide under the rear
retention clip. The horizontal drain pan assemble should rest against the right panel insulation and the
bottom side support.
8. Replace the retention clip for the front of the evaporator drain pan.
For all orientations
9. Cut open the appropriate drain pan drain access hole in the bottom door.
10. Slip the Suction line grommet panel over the suction line up to the bottom door surface.
3
Page 6
All installations and services must be performed by qualified personnel.
Figure B
11. Make appropriate liquid and suction line connections to coil and braze connections.
NOTE: A wet rag makes an excellent heat sink for tubing and grommets.
: If drilling or screwing into panel of plate is necessary, make certain drill does not penetrate
into any part of evaporator coil or hot water coil to avoid personal injury and/or property damage.
13. Position grommet panel on bottom door surface and secure in place with screws. Refer to Figure B.
14. Make appropriate condensate drain connections and seal the access opening.
INSTALLATION OF THE HOT WATER COIL:
1. Remove top door of air handler.
2. Slide hot water coil's side hanger brackets into coil channel(retaining channel) in the air handler. See
Figure C.
3. Push coil into unit until the coil is stopped by the back casing.
4. Cut out appropriate holes in insulation, realign top door and secure into place.
5. Make appropriate hydronic connections to inlet(blower side) and outlet(duct side) of coil and braze
into place.
6. Seal connections through panel with duct sealer or equivalent.
4
Page 7
All installations and services must be performed by qualified personnel.
Figure C
: If drilling or screwing into panel or plate is necessary, make certain drill does not
penetrate into any part of evaporator coil or hot water coil. Personal injury and/or property damage may
result.
NOTE: Drain lines must be pitched no less than 1/4" per foot away from the air handler.
Figure D
5
Page 8
All installations and services must be performed by qualified personnel.
BLOWER AIR ADJUSTMENT
The ECM blower control must be set in order to
establish proper air movement. Use the following
steps to do this:
1. Identify to tonnage of the condensing unit that will
be used.
2. If Hydronic heat is to be used, identify your BTU
heat requirements, preferred supply air temperature,
water temperature and water flow through the coil in
gallons per minute.
3. Locate the blower control board mounted to the
front of the blower assembly.
4. Locate the red switch block labeled SW1 for
adjusting the Heating and Cooling blower speed.
5. Locate SW2, just below SW1, for adjusting Blower
delays.
Figure E
BLOWER COOLING SPEEDS
Refer Table C1 for setting switches 4, 5 & 6 for the A/C sizing.
Table C1 COOLING SWITCH SETTINGS
A/C
TONS
2
2-1/2
3
3-1/2
4
5
Shaded cells represent the factory settings
CFM
800 OFF OFF OFF
1000
1200
1400
1600
1800
2000
2200
AH2436E1 COOL
Settings (SW1)
4 5 6 4 5 6
ON
OFF
OFF OFF
ON
ON ON ON
OFF OFF
AH4260E1 COOL
Settings (SW1)
ON
ON ON
OFFOFF
ON
OFF
OFF
ON ON
OFF
OFF
ON
ON
BLOWER HEATING SPEEDS
In the next two pages:
1. Locate the page that refers to the Air Handler to be set up.
2. Find the line(s) on the chart that best represents the water temperature and gallons per minute available.
3. Find the point along the curve that best fits the BTU and Supply Air temperature desired.
4. Read the letter associated with that point and use it to find the switch settings in the table below the
chart.
(The table below the switch settings represent the actual numbers represented by the chart.)
6
Page 9
All installations and services must be performed by qualified personnel.
A
A
p
r
Heat (Kbtu/H)
r
Heat (Kbtu/H)
r
Heat (Kbtu/H)
r
Heat (Kbtu/H)
r
Heat (Kbtu/H)
r
Heat
(Kbtu/H)
r
Heat
(Kbtu/H)
r
Heat
(Kbtu/H)
r
Heat
(Kbtu/H)
r
Heat (Kbtu/H)
r
Heat (Kbtu/H)
r
Heat (Kbtu/H)
r
Heat (Kbtu/H)
r
Heat (Kbtu/H)
r
Heat (Kbtu/H)
AH2436E1 T emp er atu r e & H eat Va l u es at 140, 160& 1 80°F an d
3,4,5& 6 gallo ns per minu te at sel ect ed sp eed s
All installations and services must be performed by qualified personnel.
BLOWER TIME DELAY
In cases where the yellow wires are used to start and stop the hydronic pump, SW2 may used to delay
when the blower is cycled on or off to increase comfort and efficiency.
Use Table D1 to set the switches appropriately
Table D1: Delays before blower cycles “ON or “OFF”
The duct system and load sizing calculation should follow the design standards of Air Conditioning
Contractors of America (ACCA) - manuals D & J - or the American Society of Heating, Refrigeration and
Air Conditioning Engineers, Inc. (ASHRAE) Latest Edition Fundamentals Volume.
To aid you in evaluating existing duct systems quickly, review the chart on Page 11 which shows the
CFM capacity for square inch areas, based on .10" wc static pressure (SP) loss on the supply systems.
Each of the system's components (trunk lines, take-offs, runs and register and grill-free areas) must be
properly sized and matched together to ensure you are obtaining the air handling capacity of the duct
system. A 12x8 duct with a 400 CFM capacity, for example, MAY NOT flow 400 CFM if the register(s)
to which it connects can only flow a total of 200 CFM.
The air handling capacity MUST BE EQUAL TO the supply system at a minimum when sizing the
return air duct system. It is recommended to follow design parameters set down by ACCA or ASHRAE
on the return air duct systems.
9
Page 12
All installations and services must be performed by qualified personnel.
DUCT SIZES FOR HOMES
Velocity Approximately 800 Feet Per Minute
THE INDOOR EVAPORATOR COIL
1. EVAPORATOR COIL is a finned coil through which air in the home is circulated. Heat from the air
is transferred to the liquid refrigerant inside the evaporator coil. The coils for use in AH air handlers are
in an A-shaped configuration (A Models).
CONDENSATE DRAIN PAN is attached to the bottom of the evaporator coil to collect water
2.
condensed out of the air. Two drain fittings are provided for connection to a convenient drain point.
3.
HORIZONTAL CONDENSATE DRAIN PAN is attached to the right side of the first one for
horizontal left to right air flow. It may relocated to the left side as well. A drain fitting is provided for
connection to a convenient drain point.
TUBING LINE SETS
1.
SUCTION LINE is an insulated large copper tube connecting the outlet of the A/C evaporator to the
suction inlet of the A/C CONDENSER.
10
Page 13
All installations and services must be performed by qualified personnel.
2. LIQUID LINE is a single small tube connecting the outlet of the A/C condenser to the expansion
valve inlet on the A/C evaporator coil.
It is not recommended to use the AC10 series condensers with these air handlers. The “non-bleed” TXV on
& AC1360
1
Suction Liquid Suction Liquid Suction Liquid
3/4” 3/8” 7/8” 3/8” 1-1/8” 1/2”
7/8” 3/8” 1-1/8” 1/2” 1-1/8” 1/2”
the evaporators may cause the condenser to stall during warm weather.
NOTES:
For line lengths over 25’ adjust charge accordingly per foot of variation from chart.
.65 oz. per foot for 3/8” and 3/4” line set
.674 oz. per foot for 3/8” and 7/8” line set
.694 oz. per foot for 1/2” and 7/8” line set
.72 oz. per foot for 1/2” and 1” line set
.76 oz. per foot for 5/8” and 1-1/8” line set
These charges are to be used in conjunction with a liquid sub-cooling measurement for best performance.
11
Page 14
All installations and services must be performed by qualified personnel.
TUBING INSTALLATION
The compressor oil is constantly pumped through the refrigerant lines in normal operation of an air
conditioning system. To ensure proper lubrication of the compressor by avoiding oil accumulation at
undesirable points in the system, follow the guidelines listed below:
1. No traps in the suction line are necessary if the outdoor condensing unit is level with the indoor
evaporator coil or the indoor evaporator coil is 4 feet or less lower then the outdoor condensing unit.
Any horizontal runs of suction line should have minimum 1/2" pitch for every 10 feet of line towards
the outdoor condensing unit. See Figure F.
Figure F.
2. A trap is necessary in the suction line at the indoor evaporator coil if the indoor evaporator coil is
more than 4 feet below the outdoor condensing unit.
Figure G1.
12
Page 15
All installations and services must be performed by qualified personnel.
NOTE: Multiple suction line traps are recommended for longer or multiple suction lines. See Figure G1.
An inverted trap should be installed on the horizontal suction line near the evaporator coil to prevent
liquid flood back to the compressor (See Figure G2.) if the indoor evaporator coil is located 10’ or more
above the condensing unit.
Figure G2.
A gradual loop in the tubing can be constructed to take up the excess tubing if you find that too much
tubing has been brought onto a job. Such a loop MUST be kept in a horizontal (flat) plane to avoid
trapping the oil.
Refrigerant lines should be inserted into a suitable conduit or raceway when the lines are to be buried
between the building and the outdoor condensing unit. The lines must be provided with sufficient
protection and support to prevent damage when installed above ground.
When making "on the job" tubing, a solder of 95% tin, 5% antimony or any of the silver solders such as
SilFos, Phos-Copper, Easy-Flo 35 or 45, should be used. No attempt will be made here to instruct proper
soldering or brazing technique but it is necessary that the installer be properly instructed in accordance
with good existing practices.
All joints and fittings must be properly leak tested as per EPA guidelines after “on the job” tubing has
been made up. The line set and the evaporator coil must be evacuated to 29.96” Hg (1000 microns) or
lower when all joints and fittings are leak free. The service valves on the condenser may then be opened
to release the refrigerant to the system. Verify proper system performance. See condensing unit manual
for additional performance data.
13
Page 16
All installations and services must be performed by qualified personnel.
HOW TO MEASURE LIQUID SUB-COOLING
(NOTE: A good electronic thermometer and accurate liquid pressure gauge with a check valve in the
Schraeder fitting are necessary).
: Failure to use a liquid side hose fitting with a built in check valve may result in personal
injury and significant refrigerant loss.
Sub-cooling is measured by taking a temperature and pressure reading. See Figure I. The pressure reading
is gauged at the pressure port located on the liquid service valve. The temperature reading is taken at the
liquid line at the 3:00 o'clock or 9:00 o'clock position with the liquid line as the center of the clock.
Figure I.
Make sure the tube where the temperature is measured is not in direct sunlight.
Read the temperature at the liquid line.
Read the liquid pressure.
Then convert pressure into temperature.
Next, subtract the measured tube temperature from the converted suction temperature.
The end result is the liquid sub-cooling.
EXAMPLE:
Measured Temp = 95oF
Measured Pressure = 211PSI which equates to a 105oF saturation temperature.
(Listed temperature for measured pressure according to R-22 temperature scale on manifold gauge or R22 section of pressure temperature chart)
The difference equals the degrees superheat = 10oF
14
Page 17
All installations and services must be performed by qualified personnel.
A liquid sub-cooling of about 10oF leaving the condenser is good over a wide range of operating
conditions for a system with a TXV in the evaporator like the AH2436E1 & AH4260E1.
MEASURING TEMPERATURE DROP ACROSS THE “A” COIL:
The temperature drop across the coil should be around 18oF to 23oF difference between inlet and outlet
air. This should be measured as close to the air handler as possible, to eliminate duct losses.
ELECTRICAL
All wiring must conform to the provisions of local codes or in the absence of local codes with the
provisions of the National Electrical Code, ANSI/NFPA No. 70-Latest Edition and this instruction
manual. Equivalent type wire must be used if any of the original wire supplied with the unit needs to be
replaced. A 10 amp time delayed fuse or circuit breaker is recommended.
NOTE: Condensing unit is not included in above amp rating.
15
Page 18
All installations and services must be performed by qualified personnel.
The following points must be checked by the installer and/or electrician before the air conditioning
system is started:
1. Check every electrical connection of "PUSH-ON" or "SCREW-ON" terminals to ensure it is on tightly
on its proper post.
2. Review wiring diagram for proper routing.
UA ADAPTER CABINET
The UA adapter cabinet is designed to be used in conjunction with the AH AIR HANDLER to allow a
free standing (vertical discharge) installation. The UA cabinet is shipped completely assembled and ready
for installation.
The return air opening can face either left or right by exchanging the front filter door and rear filter blockoff assemblies.
The AH AIR HANDLER is then placed on the UA adapter cabinet, inlet side down.
The UA cabinet is equipped with a permanent washable air filter.
AH AIR HANDLER RECOMMENDED SUSPENSION PROCEDURE
The detail below is the proper and safest way to suspend the AH. These components should be easily
found at your local hardware store.
ECM TROUBLE SHOOTING
DIAGNOSTC FEATURES
16
Page 19
All installations and services must be performed by qualified personnel.
•
The control board is equipped with 4 green Input Status LEDs and 1 red Board Status LED. These are
intended to provide a quick view into furnace performance without requiring a voltmeter.
The green Input Status LEDs are driven by the “Y”, “W”, “G”, and “DEHUM” inputs and are located
directly below those inputs. They will light to indicate the presence of these signals.
The red Board Status LED has two functions:
It will light when the board recognizes a valid input signal and will stay lit until all valid signals are
removed. This is intended to show that the board is functioning and able to respond to input signals.
It will flash rapidly while120VAC is missing from the LIMIT switch. This is intended to give a quick
visual indication of the High LIMIT switch.
B. GENERAL GUIDELINES TO TROUBLESHOOTING GE ECM – DRIVEN SYSTEMS
: Disconnect power from unit before removing or replacing connectors, or servicing
motor. Wait at least 5 minutes after disconnecting power before opening motor.
SYMPTOM CAUSE/PROCEDURE
Motor rocks slightly when starting
Motor won’t start
• No movement
• Motor rocks, but won’t start • Check for loose or compliant motor mount
Motor oscillates up & down while being tested off
of blower
Motor starts, but runs erratically
• Varies up and down or intermittent
• “Hunts” or “puffs” at high CFM (speed) • Does removing panel or filter reduce “puffing”?
• Stays at low CFM despite system call for cool or
heat CFM
• Stays at high CFM • “R” missing/not connected at motor
• This is normal start-up for ECM
• Check power at motor
• Check low voltage (24 VAC R to C) at motor
• Check low voltage connections
(G,PWM,W,R,C,) at motor
• Check for unseated pins in connectors on motor
harness
• Test with a temporary jumper between R – G
• Check motor for tight shaft
• Perform motor/control replacement check
• Run Moisture Check
• Make sure blower wheel is tight on shaft
• Perform motor/control replacement check
• It is normal for motor to oscillate with no load on
shaft.
• Check line voltage for variation or “sag”
• Check low voltage connections
(G,PWM,W,R,C,) at motor, unseated pins in
motor harness connectors
• Check “Bk” for erratic CFM command (in
variable speed applications)
• Check-out system controls – T’stat?
• Perform Moisture Check
Reduce restriction
Reduce max airflow
• Check low voltage (T’stat) wires and connections
• Verify fan is not in delay mode – wait until delay
complete
• “R” missing/not connected at motor
• Perform motor/control replacement check
Is fan in delay mode? –wait until delay time
17
Page 20
All installations and services must be performed by qualified personnel.
complete
• Perform motor/control replacement check
• Blower won’t shut off • Current leakage from controls into G,Y or W?
Check for Triac switched t’stat or solid state relay
Excessive noise
• Noisy blower or cabinet • Check for loose blower housing, panels, etc.
• “Hunts” or “puffs” at high CFM (speed) • Does removing panel or filter reduce “puffing”?
Evidence of Moisture
• Motor failure or malfunction has occurred and
moisture is present
• Evidence of moisture present inside air mover • Perform Moisture Check
DODON’T
• Check-out motor, controls, wiring and
connections thoroughly before replacing motor
• Orient connectors down so water can’t get in
Install “drip loops”
• Use authorized motor and control model #’s for
replacement
• Keep static pressure to a minimum:
Recommend high efficiency, low static
filters
Recommend keeping filters clean
Design ductwork for min static, max
comfort
Look for and recommend ductwork
improvement, where necessary, in
replacement
• Size the equipment wisely• Oversize system then compensate with low
• Check orientation before inserting motor
connectors
• Determine if it’s air noise, cabinet, duct or motor
noise – interview customer, if necessary
• High static creating high blower speed?
Check for air whistling thru
seams in ducts, cabinets or panels
Check for cabinet/duct deformation
Reduce restriction
Reduce max airflow
• Replace motor and perform Moisture Check
• Automatically assume the motor is bad.
• Locate connectors above 7 and 4 o’clock
positions
• Replace one motor or control model # with
another (unless an authorized replacement)
• Use high pressure drop filters – some have ½”
O drop!
H
2
• Use restricted returns
airflow
• Plug in power connector backwards
• Force plugs
Moisture Check
• Connectors are orientated “down” (or as recommended by equipment manufacturer)
• Arrange harnesses with “drip loop” under motor
• Is condensate drain plugged?
• Check for low airflow (too much latent capacity)
• Check for undercharged condition
• Check and plug leaks in return ducts, cabinet
Comfort Check
• Check proper airflow settings
18
Page 21
All installations and services must be performed by qualified personnel.
• Low static pressure for lowest noise
• Set low continuous-fan CFM
• T’stat in bad location?
Figure K: ECM PIN CONNECTORS
Troubleshooting table above and Figure K adapted from GE Industrial Systems publication GED-7161C,
“Troubleshooting GE ECM – Driven Systems”.
19
Page 22
All installations and services must be performed by qualified personnel.
A
A
A
A
A
A
A
TROUBLESHOOTING CHARTS
THIS GUIDE SHOULD BE USED IN THE CASE OF A STOPPED OR MANFUNCTIONED ECM
BLOWER MOTOR. THE FOLLOWING SHOUL D HEL P ESTABLISH THE TY PE O F
MALFUNCTION OR DEVIATION FROM THE NORMAL BLOWER OPERATION.
TO USE THIS DIAGRAM, YOU JUST NEED TO FOLLOW THE INSTRUCTIONS IN THE BOXES.
CONFIRM IF EI THER BL O WER
DOES BLOWER SPIN FREELY?
YES
IS THERE 115V
SUPPLIED TO MOTOR?
YES
DISCONNECT 16 PIN
HARNESS FROM
MOTOR. IS THERE 12VDC
CROSS PIN12 & PIN1
ND PIN12 & PIN3
T THE HARNESS PLUG?
YES
NO
NO
NO
IS THERE 24VAC
CROSS R &
B/C ON THE
INTEGRATED
CONTROL?
DISCONNECT 16PIN
HARNESS FROM
INTEGRATED CONTROL.
IS THERE 12VDC ACROSS
PIN 6 & PIN 1
T THE CONRO L ?
YES
WHEEL IS RUBBING AGAINST
HOUSING OR MOTOR SHAFT
IS SPINNING FREELY, REPAI R
OR REPLACE AS NECESSARY.
CHECK 115V SUPPLY,
CONNECTION FUSES,
SERVICE SWITCH AND
DOOR SWITCH.
NO
NO
CHECK 24VAC
TO INTEGRATED CONTROL.
REPLACE
INTEGRATED
CONTROL.
TURN THERMOSTAT MANUAL FAN
SWITCH ON (IF AVAILABLE) OR JUM PER
BETWEEN R & G ON INTEGRATED CONTROL.
IS THERE VOLTAGE GREATER THAN
12VDC BETWEEN PIN15 & PIN1?
YES
CHECK CONNECTION ON H ARN ESS AND MOTOR,
RECONNECT HARNESS TO M O TOR , IF
CONNECTIONS ARE GOOD AND MOTOR STILL
DOES NOT RUN REPLACE MOTOR.
YES
CHECK HARNESS
CONNECTIONS
ND WIRE.
NO
CHECK CONNECTIONS AND WIRES
T INTEGRATED CONTROL, IF OK
REPLACE INTEGRATED CONTROL.
20
Page 23
All installations and services must be performed by qualified personnel.
A
NoN
BLOWER Off-
Delay Active?
No
HEAT
Mode On?
No N
COOL
Mode On?
No No No
Yes
W
Active?
1.BURNER Off
2. HEAT mode Off
3. BLOWER Off-Delay Started
4. Status LED Off
Yes Yes Yes
1. A/C Off
2. COOL mode Off
3.BLOWER Off-Delay Started
4. Status LED Off
Y
Active?
Sequence of Operation
On-Delay
Ended?
On-Delay
Ended?
LIMIT
ctive?
YesYesYes Yes
o
BURNER On
Yes
DEHUM
Active?
No
BLOWER = COOL
BLOWER
= LOW
FAN Mode
On?
LIMIT
Active?
W Active?
Y Active?
No
G Active?
Yes Yes
No No
1. BLOWER Off (No Delay)
2. Status LED Off
Yes
No
Yes
No
Yes
Yes
No
G
Active?
1. HEAT mode On
2. BLOWER = HEAT
3. Status LED Flashes
1. HEAT mode On
2. Blower On-Delay Started
3. Burner On
4. Status LED On (continuous)
1. COOL mode On
2. Blower On-Delay Started
3. Condenser On
4. Status LED On (continuous)
1. FAN mode On
2. BLOWER = LOW
3. Status LED On (continuous)
BLOWER = LOW
21
Page 24
All installations and services must be performed by qualified personnel.
Sequence of Operation Glossary
Inputs: LIMIT - 120vac power from the High Limit Switch used to power the burner.
W- Switched 24vac indicating a Heat call from the thermostat.
Y - Switched 24vac indicating a Cool call from the thermostat.
G - Switched 24vac indicating a call for blower operation from the thermostat.
DEHUM - Switched 24vac indicating a call for Dehumidification from a de-humidistat.
2 Stage Control
Inputs: LIMIT - 120vac power from the High Limit Switch used to power the burner.
W1- Switched 24vac indicating a Heat call from the thermostat. (Low fire)
W2- Switched 24vac indicating a Heat call from the thermostat. (High fire)
Y - Switched 24vac indicating a Cool call from the thermostat.
G - Switched 24vac indicating a call for blower operation from the thermostat.
DEHUM - Switched 24vac indicating a call for Dehumidification from a de-humidistat.
NOTE: 2-Stage T-stat
W1 – Low Fire
W2 – High Fire
Connect 2-Stage T-stat to both W1 and W2.
Single Stage T-stat
W2
Connect single stage T-stat to W2 only.
BLOWER Speeds:
HEAT - The Heating Blower speed selected by positions 1, 2 & 3 of SW1 (CFM tables on page 4)
COOL - The Cooling Blower speed selected by positions 4, 5 & 6 of SW1 (CFM tables on page 4)
LOW - The LOW Blower speed selected by positions 4, 5 & 6 of SW1 (CFM tables on page 4)
ECM – PSC Replacement
In an emergency situation, a defective ECM motor can be replace with a PSC motor to provide temporary
circulating air flow for heating or cooling. This is done by replacing the ECM motor in the motor
mounting bracket with a PSC motor of similar Horsepower. Wire the common lead (typically white) of
the replacement PSC motor to the neutral (common) terminal on the fan control board (N - 1 through 7).
Connect the high-speed replacement PSC motor lead (typically black) to the EAC terminal on the fan
control board. The EAC contact is energized with 115VAC any time the control board is calling for fan
operation whether in heating or cooling mode. This replacement should be only used in emergency
situations and only until a replacement ECM motor can be obtained and reinstalled.
22
Page 25
All installations and services must be performed by qualified personnel. All installations and services must be performed by qualified personnel.
REPLACEMENT PARTS
23
23
Page 26
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.