Thermo Pride AH2436E1, AH4260E1 Installation And Service Manual

13 & 14 SEER
AIR HANDLER
INSTALLATION & SERVICE MANUAL
MODELS: AH2436E1, AH4260E1
PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION AND BEFORE PERFORMING ANY SERVICE OR MAINTENANCE. THESE INSTRUCTIONS MUST BE LEFT WITH THE USER AND SHOULD BE RETAINED FOR FUTURE REFERENCE BY QUALIFIED SERVICE PERSONNEL.
: Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency, or manufacturer listed below.
MAC-183
ECN 4849-MA
THERMO PRODUCTS, LLC. BOX 217 NORTH JUDSON, IN 46366 PHONE: (574) 896-2133 MADE IN USA
TABLE OF CONTENTS
SECTION BEGINNING PAGE
SAFETY SECTION 1
KNOCKDOWN OF AIR HANDLER 2
REASSEMBLY OF AIR HANDLER 3
SETTING UP THE A-COIL FOR AIR CONDITIONING 3
INSTALLATION OF HOT WATER COIL 4
BLOWER AIR ADJUSTMENT 6
DUCT SYSTEM 9
DUCT SIZING CHART 10
INDOOR EVAPORATOR COIL 10
TUBING LINE SETS 10
HOW TO MEASURE LIQUID SUB-COOLING 14
MEASURING TEMPERATURE DROP ACROSS THE “A” COIL 15
ELECTRICAL 15
UA ADAPTER CABINET 16
RECOMMENDED SUSPENSION PROCEDURE FOR AH AIR HANDLER 16
ECM TROUBLE SHOOTING 17
TROUBLE SHOOTING CHARTS 20
SEQUENCE OF OPERATION 21
REPLACEMENT PARTS LIST 23
All installations and services must be performed by qualified personnel.
SAFETY SECTION
This page contains various warnings and cautions found throughout this Service and Installation Manual. Please read and comply with the statements on the cover and the statements below.
: Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency, or manufacturer listed below.
: If drilling or screwing into panel or plate is necessary, make certain drill or screw does not
penetrate into any part of evaporator coil or hot water coil and cause damage. Personal injury and/or property damage may result.
: Do not use this system if any part has been under water. Immediately call a qualified service agency to inspect the system and to replace any part of the electrical or control system which has been under water.
: The cooling and heating coils must be cleaned by a qualified service person.
: This air handler is not to be used to condition during construction.
: When testing electrical equipment, always follow standard electrical procedures and
precautions.
: DO NOT wet electronic components during hydronic testing. Wetting electronic
components may damage circuitry and cause a hazardous situation. Dry moisture from all leads and terminals if wetting occurs. Wait at least 24 hours for the circuit to fully dry before energizing the system.
: Personal injury or property damage could result from major repair or service of this system by anyone other than a qualified contractor.
: If you do not follow these instructions exactly an unsafe condition may result causing personal injury, loss of life or property damage. Installation and service personnel are required by some states to be licensed. Persons not qualified shall not install this equipment nor interpret these instructions.
All local codes and regulations take precedence over the instructions in this manual and should be followed accordingly. In the absence of local codes, installation must conform with these instructions, regulations of the National Fire Protection Association and provisions of the National Electric Code.
1
All installations and services must be performed by qualified personnel.
AIR HANDLER
Each air handler is shipped with an evaporator preinstalled. The AH2435E1 is shipped with a 12U2430AG15 evaporator coil for 2 to 3 ton operation. The AH4260E1is shipped with a 12U3648AG17 evaporator coil for 3 to 5 ton operation.
The construction of the air handler permits easy knockdown and reassembly. See Figure A.
FOLLOW THESE STEPS FOR KNOCKDOWN OF AIR HANDLER:
1. Start with unit setting in a vertical position(Figure A).
2. Remove middle door.
3. Remove screws from bottom door, top door, and top front panel. Remove doors and top panel of air
handler.
4. Remove the retention clip from in front of the A-coil drain pan and the horizontal drain pan shipping
screw(s) from the right side casing.
5. Remove the A-coil assembly.
6. Disconnect power leads and unplug circulation pump connector from the blower control board.
Figure A.
2
All installations and services must be performed by qualified personnel.
7. Remove the screws that secure the blower assembly to the blower pan and pull blower sub-assembly
out the front of the unit.
8. Remove screws that secure the blower pan to the side & back casings.
9. Push the front edges of the side casings slightly apart and remove the blower pan.
10. Remove screws from the bottom and the casing back.
11. Remove casing back and side casings from the bottom.
REASSEMBLY OF AIR HANDLER
To reassemble the air handler, reverse steps above starting with number 10.
SETTING UP THE A-COIL FOR AIR CONDITIONING
The AH2436E1 & AH4260E1 come with the A-coil pre-installed for vertical and left to right horizontal airflow.
IMPORTANT: When air handler is installed in attic above a finished ceiling, it is recommended that a safety overflow pan with its own separate drain be installed under the entire unit.
For a right to left horizontal air flow the following steps 1-8 must be followed. Otherwise skip to step 9.
Reversing the horizontal orientation
1. Remove the middle door of the air handler.
2. Remove the bottom door of the air handler.
3. Remove the retention clip from in front of the A-coil drain pan.
4. Remove the horizontal drain pan shipping screw(s) from the right side casing.
5. Remove the A-coil assembly and slip the horizontal drain pan assembly off of the right side of the A­coil. 5a. Remove the bottom right side support L-bracket and remount in the left hand position using the pre­punched holes for a guide.
6. Slip the horizontal drain pan assembly onto the left side of the A-coil.
7. Replace the A-coil assembly into the air handler. The A-coil drain pan should slide under the rear retention clip. The horizontal drain pan assemble should rest against the right panel insulation and the bottom side support.
8. Replace the retention clip for the front of the evaporator drain pan.
For all orientations
9. Cut open the appropriate drain pan drain access hole in the bottom door.
10. Slip the Suction line grommet panel over the suction line up to the bottom door surface.
3
All installations and services must be performed by qualified personnel.
Figure B
11. Make appropriate liquid and suction line connections to coil and braze connections. NOTE: A wet rag makes an excellent heat sink for tubing and grommets.
: If drilling or screwing into panel of plate is necessary, make certain drill does not penetrate
into any part of evaporator coil or hot water coil to avoid personal injury and/or property damage.
13. Position grommet panel on bottom door surface and secure in place with screws. Refer to Figure B.
14. Make appropriate condensate drain connections and seal the access opening.
INSTALLATION OF THE HOT WATER COIL:
1. Remove top door of air handler.
2. Slide hot water coil's side hanger brackets into coil channel(retaining channel) in the air handler. See
Figure C.
3. Push coil into unit until the coil is stopped by the back casing.
4. Cut out appropriate holes in insulation, realign top door and secure into place.
5. Make appropriate hydronic connections to inlet(blower side) and outlet(duct side) of coil and braze
into place.
6. Seal connections through panel with duct sealer or equivalent.
4
All installations and services must be performed by qualified personnel.
Figure C
: If drilling or screwing into panel or plate is necessary, make certain drill does not
penetrate into any part of evaporator coil or hot water coil. Personal injury and/or property damage may result.
NOTE: Drain lines must be pitched no less than 1/4" per foot away from the air handler.
Figure D
5
All installations and services must be performed by qualified personnel.
BLOWER AIR ADJUSTMENT
The ECM blower control must be set in order to establish proper air movement. Use the following steps to do this:
1. Identify to tonnage of the condensing unit that will be used.
2. If Hydronic heat is to be used, identify your BTU heat requirements, preferred supply air temperature, water temperature and water flow through the coil in gallons per minute.
3. Locate the blower control board mounted to the front of the blower assembly.
4. Locate the red switch block labeled SW1 for adjusting the Heating and Cooling blower speed.
5. Locate SW2, just below SW1, for adjusting Blower delays.
Figure E
BLOWER COOLING SPEEDS Refer Table C1 for setting switches 4, 5 & 6 for the A/C sizing.
Table C1 COOLING SWITCH SETTINGS
A/C
TONS
2
2-1/2
3
3-1/2
4
5
Shaded cells represent the factory settings
CFM
800 OFF OFF OFF 1000 1200 1400 1600 1800 2000 2200
AH2436E1 COOL
Settings (SW1)
4 5 6 4 5 6
ON
OFF
OFF OFF
ON
ON ON ON
OFF OFF
AH4260E1 COOL
Settings (SW1)
ON
ON ON
OFF OFF
ON
OFF
OFF
ON ON
OFF OFF
ON ON
BLOWER HEATING SPEEDS
In the next two pages:
1. Locate the page that refers to the Air Handler to be set up.
2. Find the line(s) on the chart that best represents the water temperature and gallons per minute available.
3. Find the point along the curve that best fits the BTU and Supply Air temperature desired.
4. Read the letter associated with that point and use it to find the switch settings in the table below the chart.
(The table below the switch settings represent the actual numbers represented by the chart.)
6
Loading...
+ 18 hidden pages