ThermoPlus Air KACE-018A, KACE-009A, KACE-012A, KACE-015A, KACE-024A Installation, Operation And Maintenance Manual

...
WATER COOLED AIR CONDITIONERS
HORIZONTAL & VERTICAL MODELS
R410A
INSTALLATION, OPERATION AND MAINTENANCE
SERIES KACE-009A KACE-012A KACE-015A KACE-018A
KACE-048A KACE-060A KACE-072A KACE-096A KACE-120A KACE-144A
Warning
Mechanical Thermostat may affect Electronic Control card in unit. Connect an electronic Thermostat to unit.
Each air conditioner has been operated and checked out prior to shipment. Failure to operate after installation indicates damage in transit or improper installation.
INSPECTION Check packaging during unloading. Note transit damage on all copies of bill of lading. Inspect air conditioners for hidden shipping damage after packaging is removed. Transit damage claims must be filed promptly with Freight Company by purchaser.
HANDLING Always handle Vertical units upright and Horizontal units flat on their base. Moving a vertical unit on its side, placing a horizontal unit on end, or dropping it may damage internal parts and displace oil from the compressor's crankcase.
STORAGE If job site storage is necessary, place the unit in a clean, warm dry area. Follow instructions under Handling.
LOCATION Note that units with different capacities may have identical dimensions. Labels on unit packaging must be carefully scrutinized and matched to job location. These units are not approved for outdoor installation and therefore must be installed inside the space being conditioned.
PLACEMENT Install air conditioners in a level plane and locate unit around the service panel to ensure that proper access is available including that for filter removal.
¨ For Vertical Units: Install the air conditioner with a piece of
sound insulating material between unit and floor to avoid possible transmission of noise into the building structure. (rubber backed carpeting will suffice for vertical models). For units installed in closets adjacent to conditioned space, provide insulated return air ducting with at least one 90o elbow or provide a sound baffle between the return air grille and unit filter.
1
¨ Horizontal units are provided with isolation hanger
support. See Fig. 2 for proper installation when the unit is suspended.
LOCATION OF SUPPLY & RETURN CONNECTIONS
(SEE FIG. 1 & 2)
WIRING All wiring should conform to the CEC and/or local code requirements. Power disconnect shall be field provided (by others). The wiring diagram is located on electrical box cover on vertical models and on the back of the service panel on horizontal models. Make certain the line voltage and the 24 volt control circuit are properly identified and wired in accordance with the unit wiring diagram.
¨ Water cooled air conditioners are classified as direct
(permanently) connected devices by the CEC. Air conditioners must be properly grounded as per instructions on the unit wiring diagram.
CONDENSATE DRAINAGE Vertical Units: Ensure that the plastic drain tube is
connected to the bottom of the coil drain pan at one end and the other end of the condensate drain tube should extend through the left post on the front side of the unit, see Fig. 1. Connect the drain through a trap to the condensate drain system in conformance to local plumbing codes. Slope the drain line for proper gravity flow of condensate away from unit. The top of the trap and further connections must be below the unit drain connection level. Horizontal Units: The condensate drain tube should be connected to the side of the unit, see Fig. 2. Follow the above instructions (given for the vertical units) for proper condensate draining.
WATER SUPPLY (UNIT CONNECTED ON OPEN WATER CIRCUIT)
The source of water for air conditioner operation is the responsibility of the owner and/or the installing contractor. The air conditioner must not function without water, and predetermined rates of flow (l/s or USGPM) must be maintained for the unit to opera-te at rated capacity. Since the water function is to absorb heat from the refrigerant, the flow rate for each model varies with the entering water temperature (EWT). A pressure-operated water valve is installed for this reason inside the unit and SAE-13 calibra-
ted at the factory for a condensing pressure of 1400 kPa "gauge" (205 PSIG.). Piping size to and from unit must match or exceed the inlet and outlet water connection sizes on the air conditioner.
¨ Never use a hose of a smaller inside diameter than that of
the water connection sizes on the unit.
¨ The hoses must be rated to match or exceed
temperatures and pressures which occur during normal operation of system (temperature between 4o C (40o F) and 43o C (110o F); and pressures up to 1380 kPa (200 PSI).
¨ When hoses are connected they must not be subjected to
any stress in tension or by twisting or kinking.
¨ Hoses available as an accessory to the unit are provided
with hexagonal surfaces on the fittings as are the water fittings on units. Use a properly sized wrench on the hexagonal surface to tighten connections. Never use a wrench on the hose or sleeve that crimps the fitting into the hose.
¨ Do not over-tighten connections. Turn in the mating
threads by hand or with a wrench until snug, then tighten with a wrench beyond the point just enough to seal the joint (for tapered pipe threads this would be an additional 1/2 to one full turn; for union or flare connections no more than 1/4 of a turn).
¨ Before pressurizing the system, closely inspect the hose
and fittings to be sure there are no cuts, abrasions, twists or kinks. Hoses must not be in contact with any sharp edge while in use.
¨ Hose supplier will not take responsibility for hose leakage,
failure or damage resulting from water leaks. SUPPLY DUCTING Flanges around the blower opening are intended for a flexible supply air duct connection to unit. Be certain blower wheel turns freely before making the duct connection. Supply air ductwork must be insulated with 25 or 38 mm thick (1" or 1 1/2") fibreglass, sealed at all joints and must have an exterior vapour barrier. The air conditioner's life expectancy and efficient performance are dependent on adequate air flow. Under no circumstance should the unit be installed where the total external static pressure exceed those shown in the Table 1.
TABLE 1 MODEL EXTERNAL STATIC PRESSURE
Pa inch wg
009 75 0.30 012 75 0.30 015 75 0.30 018 75 0.30 024 188 0.75 030 188 0.75 036 188 0.75 042 188 0.75 048 188 0.75 060 188 0.75 072 25 to 275 0.10 to 1.1 096 25 to 275 0.10 to 1.1 120 25 to 275 0.10 to 1.1 144 25 to 275 0.10 to 1.1
WIRING - LINE VOLTAGE
WATER CONNECTIONS
If flexible hoses are used to make the water in-out connections to the unit, certain precautions must be taken to ensure proper unit operation and avoid hose damage. Check mainpower voltage. Refer to unit wiring diagram and make changes (if required) to permit the unit to operate on the available supply voltage. Connect power as per the unit wiring diagram, conforming to the local and national electrical code requirements. CONNECTION AND LOCATION OF THERMOSTAT Wiring the thermostat to the unit should be done as per the wiring diagram (inside the panel of the electrical box on the vertical units and on the inside of the service panel for horizontal units). Thermostat must be absolutely level when installed and located to best sense the actual room temperature. Avoid false sensing heat or cold from sunlight, open doors or window drafts, supply air outlets, fireplaces, ovens, etc.
HIGH PRESSURE PROTECTION Your unit is protected against excessive high pres-sure by a pressure limiting control. If the pressure rises above 560 psi (2,758 kPa), the pressure switch will shut down the unit.
RESET UNIT To restart, the unit must be turned "OFF" at the thermostat or at the main power switch. Then switch to "ON" position; the unit will start functioning. If not, call a technician to solve the problem. Repeated resetting on unit without getting the fault corrected will cause compressor failure.
START UP INSTRUCTIONS After installation of unit and the ductwork, water and condensate connections, the wiring in accordance with preceding instructions, the unit is ready for start-up. Check all wire connections to the unit and to external control devices for tightness.
¨ Set temperature on the thermostat below room
temperature and start the unit. After operating for five(5) minutes, air supply should have a minimum temperature drop of 10-12o C (18-22o F). Use a surface temperature device or any other device to check the temperature of supply water and return water. The minimum temperature rise should be 6o C (10o F).
¨ If the above conditions are not met, one or more of the
following problems exist: low air flow, low water flow, or unit is possibly defective.
MAINTENANCE AND SERVICE
¨ Do not operate the air conditioner without the air filter in
place. Filters should be serviced regularly, at least every three months. Dirty filters will result in inefficient performance.
¨ Check the air coil and fan wheel yearly for cleanliness and
clean if necessary.
MAN-KACE-A-E-001 2
FIGURE 1
BLOWER AND MOTOR ACCESS PANEL
SUPPLY AIR
RETURN AIR
RIGHT SIDE
ELECTRICAL ACCESS PANEL
BLOWER ACCESS PANEL
WATER REGULATING ACCESS PANEL
3
LEFT SIDE
CONDENSATE DRAIN TUBE
POWER IN
LOW VOLTAGE IN
WATER OUT
WATER IN
FRONT
ELECTRICAL AND COMPRESSOR ACCESS PANEL
Loading...
+ 6 hidden pages