![](/html/d7/d797/d7978034b3aa904d4b1391f9967a5033a56abc76df7d22524d4f04cefb08d7ac/bg1.png)
THERMOLEC
Installation
Instructions
for
Electric
Boilers (USA)
JULY 2006
VERSION 9
1
1
![](/html/d7/d797/d7978034b3aa904d4b1391f9967a5033a56abc76df7d22524d4f04cefb08d7ac/bg3.png)
Installation Guidelines for Thermolec Electric Boilers Model B
1 Important
1.1 These instructions should be used as a general guide only. Electrical Code and local utility requirements must
be followed and take precedence over these instructions.
1.2 Thermolec electric boilers are manufactured with quality components for maximum life, durability and
minimum service. To ensure a satisfactory installation it is imperative that you read these instructions
carefully before installing and operating the heating system.
Failure to do so may result in breach of warranty.
2 Unpacking
2.1 Inspect the unit and check whether there are missing parts.
2.2 Report any damage or claims to the carrier immediately.
2.3 For all returns to be accepted they must be authorized by the manufacturer.
3 Location and dimensions
3.1 These boilers are designed for wall mounting. Please see Table 1 below for overall dimensions.
Table 1 also gives the minimum clearances to combustible material as well as recommended distances for
ease of service (e.g. replacement of tubular elements).
Table 1
Dimensions and Clearances
Overall dimensions Clearances
Models Width Height Depth Front Back Top Right Others
Short Models
up to 23 kW 1ph
18" 18" 9-1/2"
36" 0" 12" 6"
up to 18 kW 3ph
Long Models
18" 28" 9-1/2"
36" 0" 24" 6" 12"
up to 42 kW
3.2 The boiler room should be well ventilated as to maintain the temperature below 77°F.
3.3 The unit must be mounted level on a vertical wall with the outlet tting on the left side of the unit.
12"
2
![](/html/d7/d797/d7978034b3aa904d4b1391f9967a5033a56abc76df7d22524d4f04cefb08d7ac/bg4.png)
4 Components
4 or 6 mounting holes
Electronic
temperature
sensor
Outlet 1-1/4’’ NPT
Incoloy elements High-limit
thermal cut-out
Solid state relays
9 1/2”
Mono or Dual energy
controller
Adjustable
electronic
aquastat
(output
temperature)
Temperature /
pressure
gauge
Inlet 1-1/4’’ NPT
Outdoor reset sensor
Fig. 3
Fig. 1
Diverting valve
terminals
18”
Diverting valve
control relay
Pump relay
Ground lug
Pump relay terminals
(dry contacts 10A)
18”
Thermostat terminals Fig. 2
Magnetic back-up contactor
Boiler control
transformer
Circuit breaker
3-way valve control
transformer
Fuse and
fuse holder
Note : The model shown here is a typical FFB boiler 20kW / 240 Volts / 1phase.
5 Standard specifications for all models
Table 2 on the following page give specifications and current for the standard models.
3
![](/html/d7/d797/d7978034b3aa904d4b1391f9967a5033a56abc76df7d22524d4f04cefb08d7ac/bg5.png)
Table 2
Wire Size 12 10 8 6 4 3 2 1 0 00 000
Amps @ 75°C (167°F)
20 30 45 65 85 100 115 130 150 175 200
Amps @ 90°C (194°F)
20 30 45 65 85 105 120 140 155 185 210
Notes :
Cable Amps Capacity vs Wire Size
1- This table should be used as a guide only. Always select the wire size according to the local
Electrical Code.
2- Always use wire suitable for 75°C (167°F) minimum, 300V or 600V as required.
3- All models with suffix "U" over 12 kW at 240V / 1ph require two feeders. Divide the Total
Amps by 2 to select the proper wire size.
Standard Models Specifications @ 240V / 1ph
Dual-Energy Models B-5U-FFB B-6U-FFB B-8U-FFB B-9U-FFB B-10U-FFB B-12U-FFB B-15U-FFB
Mono-Energy Models B-5U-M B-6U-M B-8U-M B-9U-M B-10U-M B-12U-M B-15U-M
kW
BTU / H
Total Amps 20.83 25.00 33.33 37.50 41.67 47.92 62.50
No. Of Power Supplies 1 x 30A 1 x 30A 1 x 50A 1 x 50A 1 x 60A 1 x 60A 1 x 60A
(Breaker Size) 1 x 30A
Dual-Energy Models B-18U-FFB B-20U-FFB B-23U-FFB B-27U-FFB B-30U-FFB B-35U-FFB B-40U-FFB
Mono-Energy Models B-18U-M B-20U-M B-23U-M B-27U-M B-30U-M B-35U-M B-40U-M
kW
BTU / H
Total Amps 75.00 83.37 95.83 112.50 125.00 145.83 166.67
No. Of Power Supplies 1 x 60A 2 x 60A 2 x 60A 2 x 50A 3 x 60A 4 x 50A 4 x 60A
5 6 8 9 10 11.5 15
17,060 20,472 27,296 30,708 34,120 39,238 51,180
18 20 23 27 30 35 40
61,416 68,240 78,476 92,124 102,360 119,420 136,480
A06 x 1A05 x 1)eziS rekaerB(
Standard Model Specifications @ 3ph
Dual-Energy Models B-18U-FFB B-24U-FFB B-30U-FFB B-35U-FFB B-40U-FFB
Mono-Energy Models B-18U-M B-24U-M B-30U-M B-35U-M B-40U-M
kW
BTU / H
Amps @ 208V / 3ph 48.00 66.69 83.37 96.00
No. Of Power Supplies 1 x 60
Breaker Size
Amps@ 480V / 3ph 21.68 28.90 36.13 42.15 48.00
Disconnect Switch 30
18 24 30 35 40
61,416 81,888 102,360 119,420 136,480
2 x 50
2 x 60
2 x 60
n/a
Note:
Other models, voltages and capacities available upon request. Please contact the factory.
Please use Table 3 below to select the wire size for the power supply.
Table 3
4
![](/html/d7/d797/d7978034b3aa904d4b1391f9967a5033a56abc76df7d22524d4f04cefb08d7ac/bg6.png)
6 Water circulation and plumbing notes
Capacity (kW) US Gallons / min
Recommended Water Flow Rate vs Capacity
Maximum Flow Rate Pipe Diameter
US Gallons / min (Type L Copper)
4.3 3/4"
10.1 1"
17.3 1-1/4"
Maximum Flow Rate @ 15 psi
6.1 The system is designed to operate with a maximum output temperature of 180°F or
lower and a temperature rise across the unit of 20°F or lower.
Please refer to Table 4 for the recommended flow rate versus the capacity of the boiler.
Table 4
6.2 In order to ensure an adequate flow rate :
6.21 Pressure loss (referred as "Head") caused by water friction in the system should not exceed the
capacity of the pump.
6.22 Please refer to Table 5 below to find the copper pipe diameter (type L) recommended to
accommodate the water flow found in Table 4 above.
Table 5
6.23 Elbows and valves will greatly add to the head loss in the system. An appropriate water flow rate
must be maintained to avoid tripping of the temperature limiter. Pipes with diameters larger than
6.3 The installation must have a drain valve, an expansion tank, maintenance valves and an automatic
pressure reducing fill valve set at 15 PSI (104 kPA). A "T" fitting (1-1/4" NPT) must be installed at the
supply outlet of the unit. This "T" must be equipped with a reducing bushing 1-1/4" to 3/4" NPT, facing
upwards, to accept a 3/4" NPT pressure relief valve. This safety valve must be installed vertically. Except
for the pressure relief valve, the above plumbing supplies are not supplied with the unit. Please refer to
illustrations A, B and C at the end of this manual.
specified in Table 5 will not help to increase water flow.
5
![](/html/d7/d797/d7978034b3aa904d4b1391f9967a5033a56abc76df7d22524d4f04cefb08d7ac/bg7.png)
6.4 The automatic pressure relief valve supplied with the boiler is required to prevent dangerous pressure
build-ups in the system in case of system malfunction and may under certain conditions vent hot water.
Do not install the system where water could damage rugs, furniture, etc. When piping the relief valve to a
drain, check with local authority for recommended method of installation. Do not open or tamper with the
relief valve. If operated frequently or used to drain or flush the system, the valve could fail to seat properly
and thus leak.
Important safety notice : This safety valve is mandatory and must be installed as shown in the
illustrations A, B and C at the end of this manual. The omission of the safety valve installation will
create a very serious safety hazard and will void all warranties.
6.5 Automatic air vents should be installed at the highest point of the installation, ideally on all radiator units
for best results or at points where air could possibly be trapped in the system.
Caution : Make sure the system has been reasonably vented before starting the unit.
7 Mechanical installation
7.1 Mounting brackets are located on the sides of the boiler. Depending on the size of the unit, four or six
holes are provided. The unit may be attached directly to a combustible surface.
7.2 Use a circulator pump of appropriate capacity for the intended application. The pump should be placed as
close as possible to the boiler. Ensure that the water direction is correct. An arrow indicating the
circulation direction is generally visible on the pump casing.
7.3 Install inlet and outlet piping.
7.4 Install air vents, valves, the pressure relief valve supplied with the unit, expansion tank, etc.
7.5 When everything is finished, install the temperature / pressure gauge.
8 Electrical installation
8.1 Disconnect all power sources before opening the main panel and working within.
8.2 Read the nameplate and other markings carefully and wire strictly in accordance with the wiring diagram.
8.3 Wires and protective equipment must be sized according to the applicable Electrical Code.
8.4 Use only wires suitable for minimum 167°F.
8.5 Install the outdoor sensor on an exterior North wall and connect it with 18/2 wire to terminals
"OT / OT" on the electronic board (TH-600 controller).
8.6 On the electronic aquastat (marked "WATER TEMPERATURE"), select the maximum water temperature
required (1-10) by the type of installation. Please see Table 6 below for the temperature obtained
according to the knob position. The minimum water temperature is reset automatically by the outdoor
sensor. Please see the variation graph in Fig 5.
Table 6
Water Temperature controlled by Electronic Aquastat
Set-point
Maximum
temperature
10987654321
°C
78 73 68 61 54 49 44 40 37 36
°F
172 163 154 142 129 120 111 104 99 97
Minimum
temperature
°C
°F
48 48 48 45 40 38 34 31 29 28
118 118 118 113 104 100 93 88 84 82
6